Badger Meter 220BR Installation & Operation Manual Download Page 12

Series 200 Flow Sensors

IMPELLER ASSEMBLY AND SHAFT 
REPLACEMENT

If you are replacing an existing Badger Meter sensor and 
have already calibrated your flow monitor/transmitter, 
no calibration changes are necessary.  For installation of 
a new flow monitor or for relocation of a sensor in a new 
pipe size, please refer to the calibration instructions in 
flow monitor manual.

1.  Depressurize pipe from which sensor is to be 

removed.  If the sensor is one of the Series 225/IR225 
or 226/IR226, consult the installation section on hot 
tap sensors. 

 

NEVER disturb the securing lock nuts with pipe under 
pressure without hot tap insertion tool Model HTT 
installed.

2.  Remove the three lock nuts that secure the 

positioning collar to the threaded rods of metal 
sensor.  

NOTE:

  Before removing lock nuts, record the dimension 

from top of 2 inch NPT adapter to the bottom of the 
positioning collar. This dimension will be required later to 
reinstall. 

NOTE DIRECTION OF ARROW

USE PLIERS HERE

NOTE DIRECTION OF

IMPELLER

USE METAL PIN TO

REMOVE CERAMIC SHAFT

Figure 4:  Impeller Assembly and Shaft Replacement

3.  Remove the sensor from the hex adapter or the tee.

4.  Note the impeller blade orientation relative to flow 

arrows and the alignment hole in metal sensors beside 
one of the sighting holes.  In order to maintain proper 
calibration, the impeller will have to be reinstalled in 
the same manner with the impeller blades pointing 
toward the small alignment hole, and into the flow 
direction as indicated by the flow arrows.

5.  To remove the old impeller blade assembly, push the 

old shaft out of the sleeve with the new shaft (or small 
diameter rod) just far enough to grab the end with a 
pair of pliers and pull the shaft completely out.  The 
impeller assembly will now be free and will drop out. 

6.  Inspect the shaft and bearings for wear, and replace 

as necessary.

7.  Refer to figure 4. To reinstall, position the impeller in 

the cavity oriented as in step 4 so that the impeller 
blades point into the flow direction and toward 
the small alignment hole located beside one of the 
sighting holes on metal sensors. 

8.  Carefully push the shaft through the sleeve and 

impeller taking care not to damage the bearings.  
Make sure that the shaft is inserted far enough so 
that it clears the sleeve on each side of the impeller 
housing. 

NOTE:

 

 If shaft is not carefully installed, the bearing can be 

deformed preventing free rotation.

9.  Inspect the O-rings for damage and replace as 

necessary. Clean the O-rings and the sleeve and 
relubricate with silicone grease from the packet 
provided or some other acceptable lubricant.

10.  Install the sensor into the 2 inch NPT adapter or tee 

so that alignment hole is facing upstream and flow 
arrows point in the direction of the actual flow. Since 
the positioning collar was not loosened during this 
operation, the studs should all line up perfectly when 
the sighting holes are parallel to pipe. If this has been 
accidentally loosened, please refer to the installation 
instructions for the alignment of the flow sensor unit.

11.  Install and tighten the nuts.

12.  For metal sensors, double check that the distance 

from the top of the 2 inch NPT adapter to the bottom 
of the positioning collar equals the dimension as 
measured in step 2, and holes in sleeve sight exactly 
down the pipe, the arrows point in direction of flow 
and alignment holes located beside one sighting 
hole is pointing towards the source. If not, refer to 

installation

 section in this manual.

13.  This completes the replacement procedure. The 

system may now be repressurized and tested.

TROUBLESHOOTING

1.  If the voltage at the sensor input is less than 7 VDC 

in a no flow situation, disconnect the sensor from 
the barrier strip and measure the voltage at the 
sensor input terminals of the barrier strip again. It 
should be between 8 VDC and 20 VDC. If the voltage 
at the sensor input is still below 7 VDC or 3 VDC, 
the problem may be with the monitor (hardware or 
programming).

Page 12

 

August 2012

Summary of Contents for 220BR

Page 1: ...Series 200 Insertion Style Flow Sensors Installation Operation Manual 872020 EN August 2012 Rev 8 IMPORTANT This manual contains important information READ AND KEEP FOR REFERENCE...

Page 2: ...and 226SS 4 If the Pipe is Depressurized and Drained 5 INSTALLATION INTO A PRESSURIZED PIPELINE USING MODEL HTT 5 ELECTRICAL INSTALLATION STANDARD SENSORS 6 ELECTRICAL INSTALLATION IR SENSORS 6 ELECTR...

Page 3: ...eter impeller flow monitor or transmitter Badger Meter non magnetic flow sensors provide an accurate rate of liquid flow as well as total accumulated flow A number of sensor models are offered which c...

Page 4: ...ure removal of sensor for service or cleaning if necessary HOT TAP INSTALLATION FOR 225BR 226BR AND 226SS Badger Meter Series 200 hot tap style liquid flow sensors are designed for use in cases where...

Page 5: ...flow sensor tube into the hex mounting adapter The sleeve should be inserted past the top two O rings in the adapter approx 1 to 1 1 4 inches Take care not to push the tube in too far as the impeller...

Page 6: ...wo remaining lock nuts down until they just contact the positioning collar Do not tighten at this time 8 Remove the Model HTT Insertion Removal Tool by loosening the two thumbscrews removing the clevi...

Page 7: ...or transmitter locate the section of terminal strip on the monitor labeled SENSOR INPUT or SENSOR Connect the red wire to IN SIGNAL or SIGNAL terminal and the black wire to GND SIGNAL or COM terminal...

Page 8: ...Series 200 Flow Sensors Page 8 August 2012...

Page 9: ...ndards Columns 4 and 5 The K value and Offset that should be used in our frequency equation Freq Gpm K Offset This equation describes the frequency of the output signal of all Badger Meter flow sensor...

Page 10: ...8 071 41 063 0 283 80 2 500 Std Wt Sch 40 8 625 7 981 40 086 0 281 80 2 500 Sch 60 8 625 7 813 38 288 0 279 80 2 500 Extra Strong Sch 80 8 625 7 625 36 315 0 276 80 2 500 PVC Class 125 8 625 8 095 41...

Page 11: ...11 400 12 000 22 inch Std Wt Sch 20 22 00 21 25 301 975 0 621 500 15 000 Extra Strong Sch 30 22 00 21 00 294 642 0 616 500 15 000 Sch 80 22 00 19 75 259 513 0 573 500 15 000 24 inch Std Wt Sch 20 24 0...

Page 12: ...tion the impeller in the cavity oriented as in step 4 so that the impeller blades point into the flow direction and toward the small alignment hole located beside one of the sighting holes on metal se...

Page 13: ...00 hex adapter valve bronze UNS C83600 Sensor Sleeve and Hex Adapter for 220SS and 226SS Series 300 stainless steel Temperature Ratings Standard version 2210F 1050C continuous service High temperature...

Page 14: ...Series 200 Flow Sensors This page intentionally left blank Page 14 August 2012...

Page 15: ...Installation Operation Manual This page intentionally left blank Page 15 August 2012...

Page 16: ...6 800 876 3837 414 355 0400 M xico Badger Meter de las Americas S A de C V Pedro Luis Ogaz n N 32 Esq Angelina N 24 Colonia Guadalupe Inn CP 01050 M xico DF M xico 52 55 5662 0882 Europe Middle East a...

Reviews: