This screen allows the entering of the desired totalizer
unit label. Press the UP or DOWN arrow keys to select
the desired letter and the RIGHT arrow key to move the
cursor under the letter to be changed. After the desired
letters are selected press the ENTER key. The following
screen will appear:
TOTALIZER MULTIPLIER
X 1,000
This screen allows the selection of the desired totalizer
multiplier. Press the UP or DOWN arrow keys to select
the desired multiplier and then depress the ENTER key.
The following screen will appear:
-TOTALIZER WORD-
0000 0000 0000
The Totalizer Word is required to set up the time base
to properly totalize in the selected option units. The
totalizer word is defined as follows:
HEX
1,000,000
x
ec
in Units/S
element
primary
of
Flow
Max.
Multiplier
Totalizer
=
EXAMPLE:
Maximum flow = 1800 x 1 BPM (Barrels/min)
Totalizer multiplier = BAR x 100
Totalizer Word =
[100/(1800/60)] x 1,000,000 = 3333333.33
Converted to Hexadecimal = 32DCD5 (see the Decimal
to Hexadecimal Conversion Section).
The TOTALIZER WORD IS 0000 0032 DCD5.
Note:
The totalizer word must be greater than HEX
0000 0001 0000.
Use the UP and DOWN arrow keys to change each
digit to the required value and the RIGHT arrow key to
move the cursor. The ENTER key must be pressed after
each set of four digits. After the last set of four digits
have been programmed, the next screen will be the
CONTACT INTEGRATOR screen. Return to Page 3-5 to
continue the programming procedure.
This completes the programming for the totalizer when
optional flow units are used.
3-9