background image

STATUS MODE 

 
  The Status Mode contains the Alarms Tripped screen 
and the Self Test screen. To enter into the Status Mode 
press the MENU key and the following screen will 
appear: 
 
 

PRESS UP FOR CALIBRATION 

PRESS DOWN FOR STATUS 

 
 
  Pressing the DOWN arrow key will allow entry into the 
Status Mode screens. If you decide not to enter the Status 
Mode, press the MENU key and you will return to the 
normal operation screen. 
 
  Press the DOWN arrow key and the following screen 
appears: 
 
 

- ALARMS TRIPPED - 

IN  LO  HI  CHT  INT  EE 

 
 
  The Alarms Tripped screen will display any conditions 
that have occurred. 
 
  To clear the alarms press the DOWN arrow key. 
Should an alarm still be tripped, it will still be shown on 
the display. 
 
  The definition of the alarms are as follows: 
 
  IN  =  There is no 4-20 mA signal or the input current 
is below the pen arm zero current value. 
 
  LO  =  This indicates that the low alarm set point has 
been tripped. This set point may be changed, refer to the 
Calibration Section of this manual. 
 
  HI  =  This indicates that the high alarm set point has 
been tripped. This set point may be changed, refer to the 
Calibration Section of this manual. 
 
  CHT  =  This indicates that the chart has made a 
complete rotation and the chart needs to be changed. 
 
  INT  =  Indicates a contact integrator pulse output has 
occurred. 
 
  EE  =  EEPROM read/write error which indicates a 
failure in the microprocessor. Consult the factory. 
 
 
 
 
 

 
 
 
  To return to the normal operating screen press the 
MENU key. 
 
  To enter the Self Test screen press the ENTER key and 
the following screen will appear: 
 
 

- SELF TEST - 

PRESS UP TO ACTIVATE 

 
 
  If you decide not to enter into the Self Test section, 
press the MENU key and you will return to the normal 
display screen. 
 
  To enter into the Self Test section press the UP arrow 
key and the following screen will appear: 
 
 

- SELF TEST - 

EEPROM TEST=> PASSED 

 
 
 
  This tests the EEPROM and indicates if it passed or 
failed. This takes a few seconds and then the following 
screen will appear: 
 
 

- SELF TEST - 

VREF TEST=> PASSED 

 
 
  This tests the reference voltage and indicates if it 
passed or failed. The following screen will appear: 
 
 

- SELF TEST - 

SERVO TEST=> PASSED 

 
 
 
  This tests the servo drive system and indicates if it 
passed or failed. 
 
  Should any of the screens indicate a failure, contact the 
factory for the appropriate action to be taken. 
 
  Upon completion of the Self Test the unit will return to 
the normal operating display screen. This completes the 
Status Mode Section. 

8

 

Summary of Contents for 3000+

Page 1: ...ng Diagram 20 UNPACKING INSPECTION To avoid damage in transit Eastech Badger products are shipped to the customer in special shipping containers Upon receipt of the product perform the following unpac...

Page 2: ...or pressure or temperature totalization alarm indication and is used to program the recorder through menu driven prompts RECORDING 12 inch circular chart with 24 hour 7 day or 31 day selectable chart...

Page 3: ...a window The door is provided with two lockable latches Caution should be used when mounting the enclosure so that it is not exposed to direct sunlight A sun shield is recommended to prevent the temp...

Page 4: ...e dimensions If the outdoor enclosure has the window option do not mount facing the sun or install a sun shade to prevent overheatingoftheelectronicsinsidetheenclosure WIRING CONNECTIONS 4 20 MA OUTPU...

Page 5: ...en the screws on the connectors Strip off about 1 4 inch of insulation from the wires Insert the wire into the proper connector and tighten the screw securely After connecting all of the wires to the...

Page 6: ...ow not differential DC power must be connected in series with the load as shown above DRY CONTACT RELAYS MAX LOAD 250 MA 4 20 MA OUTPUT NO C SW 1 NC NO C SW 2 NC 1 2 3 4 5 6 7 8 TB5 RELAY OUTPUTS Rela...

Page 7: ...reen informs the user of the Model of the recorder This screen will be displayed for a few seconds The next screen to be displayed is the following SOFTWARE REVISION X XX SERIAL NUMBER 12345678 This s...

Page 8: ...tion of this manual CHT This indicates that the chart has made a complete rotation and the chart needs to be changed INT Indicates a contact integrator pulse output has occurred EE EEPROM read write e...

Page 9: ...t the following screen will appear MEASUREMENTS UNITS UNIT INITIALS GPM This screen allows the user to select the engineering unit of measure for the flow rate To change the units press the UP or DOWN...

Page 10: ...1 55 POWER 1 58 POWER 1 95 POWER 1 2 POWER 3 2 POWER 5 2 POWER OPTION The linear function is used where the transmitter output is proportional to flow The 1 55 power is used with 1 2 3 24 Parshall flu...

Page 11: ...to be at the span value if the UP or DOWN arrow keys are not pressed When pressing the UP or DOWN arrow keys the display will indicate the direction of the pen movement Once the pen is positioned to s...

Page 12: ...the channels to be summed must be input to the recorder when making this adjustment For example if the input signal is 4 20 mA for 0 to 100 then 4 mA must be input to all channels to be summed to mak...

Page 13: ...t points If the High alarm is set for 60 percent and the hysteresis is 3 percent then the High alarm will trip closed at 63 percent and open at 57 percent Press the UP or DOWN arrow keys to the desire...

Page 14: ...or DOWN arrow keys to select YES or NO and press the ENTER key The following screen will appear UNIT MULTIPLIER AAA X 1 000 This screen allows the selection of the desired flow rate multiplier Press...

Page 15: ...reens appear during the chart pen adjusting procedure one of the following problems probably occurred 1 There was not a 4 20 mADC analog signal to the recorder analog channel you selected while adjust...

Page 16: ...N OF DECIMAL WHOLE NUMBER TO HEXADECIMAL NUMBER 1 Divide the decimal number by 16 Example 57420 16 3588 75 2 Multiply only the fractional part of the product by 16 to arrive at the first character in...

Page 17: ...lue of the next character Example 224 0 224 3 Multiply the previously found product by 16 Example 224 X 16 3584 4 Repeat steps 2 and 3 in a cyclical fashion until you have added the last hexadecimal c...

Page 18: ...18 INSERT DWG 600662 9999 3000 RECORDER ASSY DWG...

Page 19: ...15 SPACER 6 EA 2 0 34 400006 0025 SET SCREW 4 40 X 3 16 EA 1 0 35 524720 CHART CLAMP BODY EA 1 0 36 400006 0071 SET SCREW 5 40 X 5 16 EA 1 0 37 512610 COVER W LOGO EA 1 0 38 524743 CHART KNOB EA 1 0 3...

Page 20: ...that pen arm transport tie down is removed from unit Increase damping See IOM page 10 Ok Now CONTACT FACTORY Will pen arm move with input now CONTACT FACTORY YES GO TO NEXT PAGE Do pen arm display ag...

Page 21: ...Loop Check chart rotation speed chart knob tightness power outages motor backlash Chart turn ok CONTACT FACTORY Chart turn ok YES NO Fast Slow Not at all NO YES YES 3000 should be operating properly...

Page 22: ...CULAR PURPOSE Eastech Badger shall not be liable for any defects attributable to acts or omissions of others after shipment nor any consequential incidental or contingent damage whatsoever NUCLEAR DIS...

Reviews: