background image

2

GENERAL INFORMATION

BAC cooling equipment is factory assembled to assure uniform
quality and minimum field assembly.
The VL models are shipped in one single section.
For the dimensions and weights of a specific unit or section, refer to
the certified drawing.

When the unit is delivered to the jobsite, it should be checked
thoroughly to ensure all required items have been received and are
free of any shipping damage prior to signing the bill of lading.
The following parts should be inspected:

- Sheaves and belts
- Bearings
- Bearing supports
- Fan  motors
- Fan wheels and shafts
- Wet deck surface (VTL)
- Coils  (VFL,  VCL)
- Water distribution system
- Strainers
- Float valve assembly
- Spray Pump (VFL, VCL)
- Eliminators
- Interior surfaces
- Exterior surfaces
- Miscellaneous items

An envelope with checklist is stored in a wooden crate or a plastic
container which is placed in the lower section. For safety reasons,
access doors / panels may be sealed with bolts. 

The wooden crate / plastic container also contains miscellaneous
parts such as gasket, hardware and accessory items. 

!

Be sure to remove all miscellaneous items from the pan before 

the unit is assembled.

Before rigging any BAC cooling equipment, the weight of each
section should be verified on the unit certified drawing.

Note: These weights are approximate only and should be confirmed by
weighing before lifting when available hoisting capacity provides little margin
for safety.

!

Before an actual lift is undertaken, ensure no water or debris has 

collected in the sump or elsewhere in the unit. Such 

accumulations will add substantially to the equipment's lifting 

weight.

The unit must be properly anchored in place before operation
begins.
Refer to the suggested support details on the certified drawing for
locations of the mounting holes. Anchor bolts must be provided by
others.
Holes suitable for 20 mm bolts are provided in the bottom flange of
the lower section for bolting the unit to the support beams.

The unit must be level for proper operation and ease of piping.
Support beams must also be level as shims should not be used
between pan and support beams to level to unit.

All piping external to BAC cooling equipment must be supported
separately. In case the equipment is installed on vibration rails or
springs, the piping must contain compensators to eliminate
vibrations carried through the external pipework.

The installer of BAC condensers must ensure proper system purging
of air prior to operation. Entrained air can obstruct free drainage of
refrigerant and reduce condensing capacity, resulting in higher
operating pressures than design.  To  verify  absence  of  non
condensables in the system, follow the instructions of the BAC
Evaporative Condenser Manual E115.
Refrigerant connections on site :
All connections in the external refrigerant pipework (installed by
others) must be leak free and tested accordingly.

All electrical, mechanical and rotating machinery constitute a
potential hazard, particularly for those not familiar with its design,
construction and operation. Accordingly adequate safeguards
(including use of protective enclosures where necessary) should be
taken with this equipment both to safeguard the public (including
minors) from injury and to prevent damage to the equipment, its
associated system and the premises.
If there is doubt about safe and proper rigging, installation,
operation or maintenance procedures, contact the equipment
manufacturer or his representative for advise.

Shipping

Inspection before Rigging

Unit Weights

Anchoring

Leveling

Connecting Pipework

Purge Requirements

Safety Precautions

Summary of Contents for VCL

Page 1: ...nd to assure that all necessary equipment will be available at the jobsite Be sure to have a copy of the unit certified drawing available for reference If you do not have a copy of this drawing or if you need additional information about this unit contact the local BAC representative The model number and serial number of the unit are located on a label on the sinde of the unit Table of Contents Pa...

Page 2: ... suggested support details on the certified drawing for locations of the mounting holes Anchor bolts must be provided by others Holes suitable for 20 mm bolts are provided in the bottom flange of the lower section for bolting the unit to the support beams The unit must be level for proper operation and ease of piping Support beams must also be level as shims should not be used between pan and supp...

Page 3: ...ens access panels and access doors in place When the equipment is operated with a variable fan speed control device steps must be taken to avoid operating at or near to the fan s critical speed For more information consult your local BAC Balticare representative ELECTRICAL SAFETY Each fan and pump motor associated with this equipment should be installed with a lockable disconnect switch located wi...

Page 4: ...ng shorten the slings at one end so the casing is approximately horizontal General Notes COOLING TOWERS VTL Model N Minimum H mm Spreader Bar Length mm Discharge Accessory1 Minimum H VTL 039 to VTL 079 3100 1250 3100 VTL 076 to VTL 095 4300 1250 4300 VTL 089 to VTL 137 5000 1250 5000 VTL 139 to VTL 227 4300 2450 4300 VTL 225 to VTL 272 5000 2450 5000 Table 1 Rigging method VTL and discharge access...

Page 5: ...ges of the upper section are about 50 mm above the lower section Dot not let the upper section swing and damage the sealer Using at least four drift pins see figure in the fastening holes located on the long sides of the sections to align the top section to the bottom section To avoid incorrect alignment refer to the below drawing for the position of the fastening holes to be used Use additional d...

Page 6: ...es of the clean out port are mounted with flanges towards the inside 1 On site the cover can be placed with flanges to the outside for easy access to hardware 2 Clean out port Figure 5 Clean out port cover mounted for transport Figure 6 Final installation of clean out port cover ...

Page 7: ...he Operating and Maintenance Manual see Table Recommended Maintenance and Monitoring Schedule Start up must be performed Proper start up procedures and scheduled periodic maintenance will prolong the life of the equipment and ensure trouble free performance for which the unit is designed Start up Inspection ...

Page 8: ...eration and monthly thereafter Schedule Type of Action Action Start Up Weekly Monthly Quarterly Every Six Months Annually Shutdown Checks and Adjustments Cold Water Basin and Strainers X X Operating level and make up X X Blow down X X Sump heater package X X Belt tension X X Drive alignment X X Locking Collar X X Rotation of fan s and pump s X Motor voltage and current X X Unusual noise and or vib...

Reviews: