RIGGING

1. Never assemble the unit before lifting, as the lifting devices

provided are not designed to support the weight of the entire
assembled unit.

2. Spreader bars of the full width of the section must be used

between the lifting cables to prevent damage to the section. 
For extended lifts or where hazards exist, it is recommended to
use the lifting devices in conjunction with safety slings placed
under the unit.

3. Lifting devices have been provided on all sections. The tables

below give the preferred method for rigging each section of a
unit.

1. Spreader Bar; 2. Lifting Device; 3. Safety Slings; 4. Spreader Bar Length.

1

 Discharge accessories can be: positive closure damper, tapered 

discharge hood, sound attenuation.

1

 Discharge accessories can be: positive closure damper, tapered 

discharge hood, sound attenuation. 

2

 For asymmetrical load distribution (with external piping) shorten the 

slings at one end so the casing is approximately horizontal. 

1

 Discharge accessories can be: positive closure damper, tapered 

discharge hood, sound attenuation. 

2

 For asymmetrical load distribution (with external piping) shorten the 

slings at one end so the casing is approximately horizontal. 

General Notes

COOLING TOWERS VTL

Model N°

Minimum

"H 

(mm)

Spreader 

Bar 

Length 

(mm)

Discharge 

Accessory

1

Minimum “H”

VTL-039 to VTL-079

3100

1250

3100

VTL-076 to VTL-095

4300

1250

4300

VTL-089 to VTL-137

5000

1250

5000

VTL-139 to VTL-227

4300

2450

4300

VTL-225 to VTL-272

5000

2450

5000

Table 1: Rigging method VTL and discharge accessory

CLOSED CIRCUIT COOLING TOWERS VFL

Model N°

Minimum

"H 

(mm)

Spreader 

Bar 

Length 

(mm)

Discharge 

Accessory

1

Minimum “H”

2

VFL-241 to VFL-243

3100

1250

3100

VFL-361 to VFL-383

3100

1250

3100

Table 2: Rigging method VFL and discharge accessory

Figure 1: Rigging method VL units

VFL-481 to VFL-484

3700

1250

3700

VFL-721 to VFL-724

3100

2450

3100

VFL-961 to VFL-964

3700

2450

3700

EVAPORATIVE CONDENSERS VCL

Model N°

Minimum

"H 

(mm)

Spreader 

Bar 

Length 

(mm)

Discharge 

Accessory

1

Minimum 

“H”

2

VCL-042 to VCL-079

3100

1250

3100

VCL-084 to VCL-133

3100

1250

3100

VCL-131 to VCL-159

3700

1250

3700

VCL-167 to VCL-258

3100

2450

3100

VCL-239 to VCL-321

3700

2450

3700

Table 3: Rigging method VCL and discharge accessory

Rigging Method Discharge Accessories

CLOSED CIRCUIT COOLING TOWERS VFL

Model N°

Minimum

"H 

(mm)

Spreader 

Bar 

Length 

(mm)

Discharge 

Accessory

1

Minimum “H”

2

Table 2: Rigging method VFL and discharge accessory

Summary of Contents for VCL

Page 1: ...nd to assure that all necessary equipment will be available at the jobsite Be sure to have a copy of the unit certified drawing available for reference If you do not have a copy of this drawing or if you need additional information about this unit contact the local BAC representative The model number and serial number of the unit are located on a label on the sinde of the unit Table of Contents Pa...

Page 2: ... suggested support details on the certified drawing for locations of the mounting holes Anchor bolts must be provided by others Holes suitable for 20 mm bolts are provided in the bottom flange of the lower section for bolting the unit to the support beams The unit must be level for proper operation and ease of piping Support beams must also be level as shims should not be used between pan and supp...

Page 3: ...ens access panels and access doors in place When the equipment is operated with a variable fan speed control device steps must be taken to avoid operating at or near to the fan s critical speed For more information consult your local BAC Balticare representative ELECTRICAL SAFETY Each fan and pump motor associated with this equipment should be installed with a lockable disconnect switch located wi...

Page 4: ...ng shorten the slings at one end so the casing is approximately horizontal General Notes COOLING TOWERS VTL Model N Minimum H mm Spreader Bar Length mm Discharge Accessory1 Minimum H VTL 039 to VTL 079 3100 1250 3100 VTL 076 to VTL 095 4300 1250 4300 VTL 089 to VTL 137 5000 1250 5000 VTL 139 to VTL 227 4300 2450 4300 VTL 225 to VTL 272 5000 2450 5000 Table 1 Rigging method VTL and discharge access...

Page 5: ...ges of the upper section are about 50 mm above the lower section Dot not let the upper section swing and damage the sealer Using at least four drift pins see figure in the fastening holes located on the long sides of the sections to align the top section to the bottom section To avoid incorrect alignment refer to the below drawing for the position of the fastening holes to be used Use additional d...

Page 6: ...es of the clean out port are mounted with flanges towards the inside 1 On site the cover can be placed with flanges to the outside for easy access to hardware 2 Clean out port Figure 5 Clean out port cover mounted for transport Figure 6 Final installation of clean out port cover ...

Page 7: ...he Operating and Maintenance Manual see Table Recommended Maintenance and Monitoring Schedule Start up must be performed Proper start up procedures and scheduled periodic maintenance will prolong the life of the equipment and ensure trouble free performance for which the unit is designed Start up Inspection ...

Page 8: ...eration and monthly thereafter Schedule Type of Action Action Start Up Weekly Monthly Quarterly Every Six Months Annually Shutdown Checks and Adjustments Cold Water Basin and Strainers X X Operating level and make up X X Blow down X X Sump heater package X X Belt tension X X Drive alignment X X Locking Collar X X Rotation of fan s and pump s X Motor voltage and current X X Unusual noise and or vib...

Reviews: