APP
MODULE Documentation
62 BAB TECHNOLOGIE GmbH
11
ATTACHMENT
Function
EIS
type
Data point
type
Typical value
Data
Identifier
Switching
EIS 1
DPT 1.yyy
[0] = Off | FALSE; [1] = On | TRUE
1 Bit
1-bit
Relative Dimming
EIS 2
DPT 3.yyy
„Dimming steps“
:
[[0],[2…7]] Darker [2, 4, 8, 16, 32, 64] -Steps and
[[1],[2…7]] Brighter [2, 4, 8, 16, 32, 64]-Steps
„Start/Stop Diming“
:
[0,8] Stop; [1] Darker und [9] Brighter
4 Bit
4-bit
Time
EIS 3
DPT 10.yyy
hh:mm:ss
3 Byte
Time
Date
EIS 4
DPT 11.yyy
dd:mm:yyyy
3 Byte
Date
Floating point number
(short)
EIS 5
DPT 9.yyy
-671 088,64 … 670 433,28
2 Byte
2-byte float value
Percent, Position,
Brightness, …
EIS 6
DPT 5.yyy
0 … 100%
1 Byte
8-bit unsigned value
Blinds
Drive/adjust
EIS 7
DPT 1.yyy
[0] = up; [1] = down
When driving [0,1] = stop
1 Bit
1-bit
Priority
EIS 8
DPT 2.yyy
[0], [1] Switch on, off;
[3] = Forced off;
[4] = Forced on
2 Bit
1-bit controlled
IEEE
Floating point number
(long)
EIS 9
DPT 14.yyy
4-Octet float value;
IEEE 754
32 Bit
4-byte float value
Counter 16 Bit
Unsigned
EIS 10u
DPT 7.yyy
0 … 65.535
16 Bit
2-byte unsigned value
Counter 16 Bit
Signed
EIS 10
DPT 8.yyy
-32.768 … 32.767
16 Bit
2-byte signed value
Counter 32 Bit
Unsigned
EIS 11u
DPT 12.yyy
0 … 4.294.967.295
32 Bit
4-byte unsigned value
Counter 32 Bit
Signed
EIS 11
DPT 13.yyy
-2.147.483.648 … 2.147.483.647
32 Bit
4-byte signed value
Access control
EIS 12
DPT 15.yyy
Access data
4 Byte
Entrance access
ASCII Character
EIS 13
DPT 4.yyy
Char
1 Byte
Character
Counter 8 Bit
Unsigned
EIS 14u
DPT 5.yyy
0 … 255
8 Bit
8-bit unsigned value
Counter 8 Bit
Signed
EIS 14
DPT 6.yyy
-128 … 127
8 Bit
8-bit signed value
String
EIS 15
DPT 16.yyy
14 Characters
14 Byte
Character string
EIB/KNX devices exchange fixed prescribed data formats with each other. These are defined in types.
The old designations of the types are EIS (EIB Interworking Standard). The new designations are DPT (Data Point
Type)