40429 Brickyard Drive • Madera, CA 93636 • USA
559.438.5800 • FAX 559.438.5900
www.bklighting.com • [email protected]
B-K LIGHTING
PROJECT:
TYPE:
3167387
ETL LISTED
CONFORMS TO ANSI/UL STANDARD 1838,
CERTIFIED TO CSA STD C22.2 NO.250.7
CSA STD C22.2 TIL B-58A
RELEASED
3-30-12
REFERENCE
NUMBER
INS001114
Phase 1 - Rough In
Installation of Back box
1. Install Conduit (by others) to be used with
this product.
2. Install junction box so that front face is flush
with finished wall or ceiling.
3. Connect box to conduit and pull wires for
connections (See wiring diagram).
Additional Info
• Please follow National and Local electrical codes for your area.
• 4” round cast box is provided with Five (5) 1/2” threaded hubs
for conduit entry (4 on sides and one on back of box).
• Suitable for through wire
• Suitable for installation into combustible materials.
• Rated for 90° C.
IMPORTANT SAFETY INFORMATION LISTED ON REVERSE
READ, FOLLOW, AND SAVE ALL SAFETY AND INSTALLATION INSTRUCTIONS
3167387
ETL LISTED
CONFORMS TO ANSI/UL STANDARD 1838,
CERTIFIED TO CSA STD C22.2 NO.250.7
CSA STD C22.2 TIL B-58A
3. Mount fixture using two (2) #10-24 hex screw
to installed back box. Do not over tighten.
Phase 2 - Finish Installation of Fixture with Remote Driver.
1. Install universal mounting ring (supplied with
fixture) using #10-24 screws onto back box.
Align fixture mounting holes to final mounting
position.
2. Make two connections from remote driver to
LED source leads (18 gauge wire) using proper
wire connectors (By Others).
CK™/OL™/SM-DE™
Architectural Surface Installation
LINE
(+)
FIXTURE
COM
POWER
SUPPLY
(-)
Wiring Diagram