Commissioning
6.1
Factory default settings
The following configuration is set by factory default:
Individual device address:
15.15.0
Number of configured KNXnet/IP tunneling connections:
1
Individual address of tunneling connection:
15.15.240
IP address assignment:
DHCP
Initial key (FDSK):
active
Security mode:
not active
6.1.1
Reset to factory default settings
It is possible to reset the device to its factory settings:
➜
Separate the KNX bus connector (1) from device
➜
Press the KNX programming button (3) and keep it pressed down
➜
Reconnect the KNX bus connector (1) to the device
➜
Keep the KNX programming button (3) pressed for at least another 6 seconds
➜
A short flashing of all LEDs (2, 4, 5, 6) visualizes the successful reset of the
device to factory default settings.
6.2
KNX programming mode
The KNX programming mode is activated/deactivated either by pressing the flushed KNX program
-
ming button (3) or by simultaneously pressing the buttons (7) and (8).
CAUTION
Factory default settings!
The individually made settings are lost.