23
Zero and span adjustment using the switch
Zero and span adjustments can be made pressing the “UP” or “DOWN” button switch. Once
adjustments have been completed, press the button switch a second time to record the new
position.
Since the zero and span adjustments do not interfere with each other, they can be adjusted
independently.
Adjustment direction
The feedback lever moves up when the “UP” adjustment switch is pressed.
Fig. 3-2. Adjusting the lever in the upward direction
The feedback lever moves down when the “DOWN” adjustment switch is pressed.
Fig. 3-3. Adjusting the lever in the downward direction
Note)
The zero and span adjustment function uses the input signal to identify whether a valve fully
open position (span) adjustment or a valve fully closed position (zero) adjustment is to be
performed. If the input signal is not within the range of ±1 mA of the set current values that
correspond to the valve open and closed position, this function will not operate.
Use the adjustment switches only if the supply air pressure is stable and only if the valve can
move freely.
Summary of Contents for SVX100
Page 1: ...CM2 SVX100 2001 Smart Valve Positioner for Rotary Valve Model SVX100 102 User s Manual...
Page 6: ...iv...
Page 9: ...vii...
Page 10: ...viii...
Page 16: ...6...
Page 40: ...30 4 2 1 Menu Tree...
Page 79: ......
Page 82: ......
Page 84: ......