18
CAUTION
Avoid installing cables near noise-making devices such as large capacity transformers and
motors. Do not lay signal/control cables in the same tray or duct with noisy switching power
cables.
Note) To prevent entry of water and damage to electrical wires, the use of metal conduits and
wiring ducts is recommended.
Electrical wiring procedure
Step
Procedure
1
Unscrew 4 screws and remove the cover.
Note) Be careful not to scratch painted surfaces with tools at this time.
2
Remove blind plugs according to how the wiring for the SVX will be performed.
3
Insert cables into the conduit connection. Strip and attach the appropriate wires
to the terminals, checking for polarity. Crimp contacts with insulated sleeves are
recommended.
Note) Be careful not to damage the cable sheath at this time.
4
Tighten the terminal screws fully, to a torque of 1.5 N•m (15 kgf•cm).
5
Apply adequate waterproofing measures to the conduits to prevent the entry of
rainwater or water from any other source.
Note) We recommend the use of silicon resin based non-hardening seal materials.
6
Screw 4 screws onto the SVX until it is hand-tight.
Note) Be careful not to scratch painted surfaces with tools at this time.