4-1. Starting Communication
Before starting communication
Confirm the following points before starting communication.
Electrical wiring of the device is completed (see the “Wiring method” below).
There is an input signal from the controller (constant-current supply).
Note) If there is no 4 to 20 mA DC signal from the controller, connect a constant-current supply
(3.85 to 21.5 mA DC) to the input signal terminal. When doing so, be sure to remove the
wires coming from the controller off of the terminals.
4-1-1. Wiring method
Introduction
The wiring method for communicating with this device will now be described.
With HART® communication
AUT
O
MAN.
DOWN
UP
TRAVEL SW
4-20 mA DC
Controller
HART communicator
Fig. 4-1. Wiring of HART® Communication Tool (Model SVX102)
With SFN communication
AU
TO
M
AN.
DOWN
UP
TRAVEL SW
4-20 mA DC
Controller
Check pin
Field Communication Software
(Model CFS100)
Fig. 4-2. Wiring with Field Communication Software (Model SVX100/102)