INSTALLATION

 

„

Installation location

Install modules indoors. Minimum clearances are shown in 

figures.

From the front

Wiring duct, etc.

50 mm

W

iring duc

t, et

c.

50 mm

W

iring duc

t, et

c.

Wiring duct, etc.

50 mm

50 mm

Module

50 mm

50 mm

Wiring duct, etc.

Wiring duct, etc.

80 mm

Module

Note.  If used with devices other than this module, check the specifica-

tions of the devices, and choose the larger of the recommended 

space in each direction.

Install the controller in a location that meets the following criteria:

• 

No high/low temperature/humidity.

• 

Free from sulfide gas or corrosive gas.

• 

Not dusty or sooty.

• 

Protected from direct sunlight, wind, and rain.

• 

Little mechanical vibration or shock.

• 

Not close to high voltage line, welding machine or other elec-

trical noise generating source.

• 

At least 15 meters away from the high voltage ignition device 

for a boiler.

• 

No strong magnetic fields.

• 

No flammable liquid or gas.

• 

Indoors

• 

I/O common mode voltages: voltage to ground is 30 V

rms

 max., 

42.4 V peak max., and 60 V DC max.

 

„

Linking modules

The power, LAN, and RS-485 of this device can be connected to 

those of adjacent modules with the left and right side connectors 

on the base.
RS-485 CH2 terminals cannot be connected.
Connection of modules must be done before they are mounted 

on the DIN rail. When connected, modules share the power and 

communication connections, eliminating the need for wiring.

 

„

Mounting procedure

The NX-SVG is used while mounted on a DIN rail.
After mounting the DIN rail and pulling the locking tab com-

pletely off, hook the base onto the DIN rail. Then, push the DIN 

rail locking tab upwards firmly until it clicks into place.

 Handling Precautions

• 

Install the module so that it is vertical, with the DIN rail 

locking tab at the bottom.

 

„

Attaching the main unit to the base

(1)  Fit the hook on the main unit into the base.
(2)  Push the main unit onto the base until the lever clicks.

(2) Lever

(1) Hook

 Handling Precautions

• 

The included base and main unit must be used as a pair.

• 

Be sure to fit the hook on the main unit into the base first. If 

this is not done, the hook might be broken during mounting.

 

„

Removing the main unit from the base

(1)  Grasp the main unit near the front and push it in toward the 

base.

(1)

(2)  While pushing, press the tip of the lever on the top of the 

main unit.

(2)

(3)  While pressing the tip of the lever, rotate the main unit down 

to remove it.

(3)

 Handling Precautions

• 

Press the tip of the lever. Do not press it down excessively 

(2 mm or more). Doing so may break the lever.

 

Press here.

Do not press in this area.

Summary of Contents for NX-SVG

Page 1: ...J1 CP UM 5928JE NX NX SVG URL https www azbil com jp product factory order html DIN 2 NX SVG NX SVG 1 CP UM 5928JE...

Page 2: ...ROR ID F1 F2 RUN MOD COM NST FAIL 1 0 ID USB LAN1 RS 485 CH1 DA DB SG LAN2 LAN RS 485 RS 485 CH2 1 DC24 V 2 DC24 V RS 485 CH2 4 DA 5 DB 6 SG LED PWR ON OFF RUN MOD COM LAN2 LAN2 NST LAN2 LAN2 LAN2 LAN...

Page 3: ...J3 15 m 30 Vrms 42 4 V DC60 V LAN RS 485 RS 485 CH2 DIN DIN DIN DIN DIN DIN 2 mm...

Page 4: ...uit 1 25 mm2 16AWG 30 m M3 5 8 mm 0 6 N m 1 70 W LAN1 LAN2 LAN1 RJ 45 LAN2 RS 485 CH1 RS 485 CH2 RS 485 CH1 DA SG DB RS 485 CH1 RS 485 CH2 1 2 4 5 6 DA DB SG 150 5 1 2 W SG USB USB USB USB 1 LED USB R...

Page 5: ...V 0 3 2 m s2 10 150 Hz XYZ 2h 0 9 8 m s2 3 0 3 mg m3 2000 m Pollution degree 2 20 70 5 95 RH 0 9 8 m s2 10 150 Hz XYZ 2h 0 300 m s2 DIN 3 60 cm 1 3 6 DC500 V 20 M I O AC500 V 1 min I O 6 W 10 A 30 s...

Page 6: ...il com jp 0466 20 2143 2018 2 F 2019 4 5 V LAN 2 LAN1 LAN2 IEEE802 3 10BASE T 100BASE TX AutoMDI MDI X RJ 45 100BASE TX UTP 4P Cat 5e ANSI TIA EIA 568B 100 m RS 485 2 RS 485 CH1 RS 485 CH2 1 31 RS 485...

Page 7: ...ing tab using a tool such as a screwdriver Otherwise you might be injured Do not disassemble this device Doing so might cause device failure Do not block ventilation holes Doing so might cause fire or...

Page 8: ...power LAN and RS 485 of adjacent modules Does not connect RS 485 CH2 terminals Power supply terminal 1 24 V DC 2 24 V DC RS 485 CH2 terminals 4 DA 5 DB 6 SG These terminals cannot be connected with th...

Page 9: ...S 485 CH2 terminals cannot be connected Connection of modules must be done before they are mounted on the DIN rail When connected modules share the power and communication connections eliminating the...

Page 10: ...the LAN1 and LAN2 connectors Insert an RJ 45 connector into the LAN1 connector on the de vice The side connectors on the base are LAN2 connectors Connecting to RS 485 CH1 and CH2 Connect wires to the...

Page 11: ...stance 0 m s2 Mounting angle Reference plane 3 z z Operating conditions Ambient temperature 0 to 50 C below the installed module Ambient humidity 10 to 90 RH without condensation Allowable power suppl...

Page 12: ...500 m No of wires 3 Terminating resistor External 150 0 5 W min Transmission speed Selectable from 4800 9600 19200 38400 57600 and 115200 bps Data bits 7 bits 8 bits Stop bits 1 bit 2 bits Parity bit...

Page 13: ...Sie vor dem Einschalten des Ger ts unbedingt ob es sachgerecht verdrah tet wurde ACHTUNG Die folgenden Vorsichtshinweise sind zu beachten um elektrische Schl ge Feuer und andere Gefahrenzust nde zu ve...

Page 14: ...ssere osservati al fine di prevenire scosse elettri che incendi e altre condizioni pericolose Prima di rimuovere montare o cablare questo dispositivo accertarsi di disatti vare l alimentazione di ques...

Page 15: ...sor el rango y los par me tros seg n corresponda para el objetivo de control Aseg rese de que el terminal de tierra del bastidor est correctamente puesto a tierra 100 m x antes de conectar el controla...

Page 16: ...X4 MEMO...

Reviews: