Azbil NX-SVG Installation Manual Download Page 10

E4

WIRING

 

„

Wiring precautions

• 

All wiring must comply with applicable codes and ordinances.

• 

Do not run wires outside. The equipment could be damaged in 

the event of lightning.

• 

When connecting wires to the power terminals, use crimp ter-

minals with insulating sleeves.

• 

Use M3 crimp terminal lugs for wiring to the power terminals 

and the RS-485 CH2 terminals.

• 

Be careful not to allow any crimp-type terminal lugs to touch 

adjacent terminals.

• 

The signal wires and power wires of the module should be at 

least 60 cm away from other power wires or power sources. 

Also, do not pass these wires through the same conduit or wir-

ing duct.

• 

Before connecting the NX-SVG to other devices in parallel, 

check their connection conditions carefully.

• 

To ensure stable operation, the NX-SVG is designed not to op-

erate for 30 seconds after the power is turned ON. 

• 

After wiring, check that there are no mistakes before turning 

the power ON.

 

„

Connecting the power supply

Connect the power terminals as shown below.

1

2

Instrument power supply 24 V DC

4

5

6

+

The power supply unit must be a Class 2 circuit or limited energy 

circuit that has double or reinforced insulation from the main 

power.
• Recommended power cable:

Cross-sectional area:  1.25 mm

2

 (16 AWG)

Length:  

30 m max.

• Terminal lug specifications:

Type:  

M3 crimp terminal lug

Width:  

5.8 mm max.

Tightening torque:  0.6 N·m

 Handling Precautions

• 

Since linked modules supply power to each other, supply 

power to only one of a group of linked modules.

• 

Use a power supply that can supply the total power 

requirement of the linked modules. The total power 

consumption of all connected modules should be no more 

than 70 W.

• 

If there are multiple wires to the power supply and wiring is 

difficult, add a relay terminal or the like. 

 

„

Connecting to the LAN1 and LAN2 connectors

Insert an RJ-45 connector into the LAN1 connector on the de-

vice. The side connectors on the base are LAN2 connectors.

 

„

Connecting to RS-485 CH1 and CH2

Connect wires to the RS-485 CH1 connector as shown below.

DA(+)

SG

DB(−)

RS-485 CH1

Connect wires to the RS-485 CH2 terminals as shown below.

1

2

4

5

6

DA(+) DB(−)

SG

 Handling Precautions

• 

Terminating resistors are not built into the NX-SVG.

• 

0.5 W or greater terminating resistor of 150 Ω ±5 % at each 

end of the communications lines. However, if any device that 

does not allow a terminating resistor is connected to the 

same communications line, follow the instructions on that 

device.

• 

Be sure to connect the SG terminals to each other. Failure to 

do so might cause unstable communications.

• 

For communications wiring, use twisted pair cables.

 

„

USB host connector

Insert a USB flash drive to save or load data. Do not insert a 

device other than a USB flash drive. Attach the USB dust cover 

when the USB port is not in use.

 

„

I/O isolation

The solid line indicates isolation from other circuits.

Power supply (including side connector)*

1

Logic circuit

Indicators (LED, switch, etc)

USB host communication

RS-485 CH2 communication*

2

LAN2 Ethernet communication*

1

RS-485 CH1 communication

LAN1 Ethernet communication

 Isolated

 Functionally isolated*

3

*1.  The power and LAN2 Ethernet communication circuits connected 

to the side connector are isolated from each other.

*2.  The RS-485 CH2 communication circuit is not connected to the 

side connector.

*3.  Dielectric strength is not specified for functionally isolated circuits. 

The main purpose of this type of isolation is to improve noise 

protection. 

SETTING

 

„

Smart Loader Package

To set up this device, the SLP-SVG Smart Loader Package (sold 

separately) is needed.

 

„

Connecting to a PC

This device can be connected to a PC (running the Smart Loader 

Package) via Ethernet. Operating environment setup, such as 

changing the IP address of the PC, is necessary for connection.

Summary of Contents for NX-SVG

Page 1: ...J1 CP UM 5928JE NX NX SVG URL https www azbil com jp product factory order html DIN 2 NX SVG NX SVG 1 CP UM 5928JE...

Page 2: ...ROR ID F1 F2 RUN MOD COM NST FAIL 1 0 ID USB LAN1 RS 485 CH1 DA DB SG LAN2 LAN RS 485 RS 485 CH2 1 DC24 V 2 DC24 V RS 485 CH2 4 DA 5 DB 6 SG LED PWR ON OFF RUN MOD COM LAN2 LAN2 NST LAN2 LAN2 LAN2 LAN...

Page 3: ...J3 15 m 30 Vrms 42 4 V DC60 V LAN RS 485 RS 485 CH2 DIN DIN DIN DIN DIN DIN 2 mm...

Page 4: ...uit 1 25 mm2 16AWG 30 m M3 5 8 mm 0 6 N m 1 70 W LAN1 LAN2 LAN1 RJ 45 LAN2 RS 485 CH1 RS 485 CH2 RS 485 CH1 DA SG DB RS 485 CH1 RS 485 CH2 1 2 4 5 6 DA DB SG 150 5 1 2 W SG USB USB USB USB 1 LED USB R...

Page 5: ...V 0 3 2 m s2 10 150 Hz XYZ 2h 0 9 8 m s2 3 0 3 mg m3 2000 m Pollution degree 2 20 70 5 95 RH 0 9 8 m s2 10 150 Hz XYZ 2h 0 300 m s2 DIN 3 60 cm 1 3 6 DC500 V 20 M I O AC500 V 1 min I O 6 W 10 A 30 s...

Page 6: ...il com jp 0466 20 2143 2018 2 F 2019 4 5 V LAN 2 LAN1 LAN2 IEEE802 3 10BASE T 100BASE TX AutoMDI MDI X RJ 45 100BASE TX UTP 4P Cat 5e ANSI TIA EIA 568B 100 m RS 485 2 RS 485 CH1 RS 485 CH2 1 31 RS 485...

Page 7: ...ing tab using a tool such as a screwdriver Otherwise you might be injured Do not disassemble this device Doing so might cause device failure Do not block ventilation holes Doing so might cause fire or...

Page 8: ...power LAN and RS 485 of adjacent modules Does not connect RS 485 CH2 terminals Power supply terminal 1 24 V DC 2 24 V DC RS 485 CH2 terminals 4 DA 5 DB 6 SG These terminals cannot be connected with th...

Page 9: ...S 485 CH2 terminals cannot be connected Connection of modules must be done before they are mounted on the DIN rail When connected modules share the power and communication connections eliminating the...

Page 10: ...the LAN1 and LAN2 connectors Insert an RJ 45 connector into the LAN1 connector on the de vice The side connectors on the base are LAN2 connectors Connecting to RS 485 CH1 and CH2 Connect wires to the...

Page 11: ...stance 0 m s2 Mounting angle Reference plane 3 z z Operating conditions Ambient temperature 0 to 50 C below the installed module Ambient humidity 10 to 90 RH without condensation Allowable power suppl...

Page 12: ...500 m No of wires 3 Terminating resistor External 150 0 5 W min Transmission speed Selectable from 4800 9600 19200 38400 57600 and 115200 bps Data bits 7 bits 8 bits Stop bits 1 bit 2 bits Parity bit...

Page 13: ...Sie vor dem Einschalten des Ger ts unbedingt ob es sachgerecht verdrah tet wurde ACHTUNG Die folgenden Vorsichtshinweise sind zu beachten um elektrische Schl ge Feuer und andere Gefahrenzust nde zu ve...

Page 14: ...ssere osservati al fine di prevenire scosse elettri che incendi e altre condizioni pericolose Prima di rimuovere montare o cablare questo dispositivo accertarsi di disatti vare l alimentazione di ques...

Page 15: ...sor el rango y los par me tros seg n corresponda para el objetivo de control Aseg rese de que el terminal de tierra del bastidor est correctamente puesto a tierra 100 m x antes de conectar el controla...

Page 16: ...X4 MEMO...

Reviews: