(2) Operating pressure range 0-0.3 MPa: MVF_ _ _3
●
MVF0503
●
MVF0803
Operating
pressure
(MPa)
Minimum
measurable
flow rate
Q min
Accuracy
Operating
pressure
(MPa)
Minimum
measurable
flow rate
Q min
Accuracy
0.1
7.4
±Q min
±5.4 %RD
±4.1 %RD
0.1
11.0
±Q min
±5.4 %RD
±4.1 %RD
7.4≤Q≤32
32<Q<74
74≤Q≤428
11.0≤Q≤31 31<Q<110 110≤Q≤ 946
0.15
7.4
±Q min
±5.1 %RD
±3.7 %RD
0.15
11.8
±Q min
±5.1 %RD
±3.7 %RD
7.4≤Q≤32
32<Q<74
74≤Q≤535
11.8≤Q≤31 31<Q<110 110≤Q≤1181
0.2
7.4
±Q min
±4.9 %RD
±3.5 %RD
0.2
14.2
±Q min
±4.9 %RD
±3.5 %RD
7.4≤Q≤32
32<Q<74
74≤Q≤641
14.2≤Q≤31 31<Q<110 110≤Q≤1461
0.3
8.5
±Q min
±4.7 %RD
±3.2 %RD
0.3
18.9
±Q min
±4.7 %RD
±3.2 %RD
8.5≤Q≤32
32<Q<74
74≤Q≤854
18.9≤Q≤31 31<Q<110 110≤Q≤1886
●
MVF1003
●
MVF1503
Operating
pressure
(MPa)
Minimum
measurable
flow rate
Q min
Accuracy
Operating
pressure
(MPa)
Minimum
measurable
flow rate
Q min
Accuracy
0.1
14.6
±Q min
±5.4 %RD
±4.1 %RD
0.1
31.3
±Q min
±5.4 %RD
±4.1 %RD
14.6≤Q≤39 39<Q<156 156≤Q≤1457
31.3≤Q≤ 57 57<Q<286 286≤Q≤3135
0.15
18.2
±Q min
±5.1 %RD
±3.7 %RD
0.15
39.1
±Q min
±5.1 %RD
±3.7 %RD
18.2≤Q≤39 39<Q<156 156≤Q≤1819
39.1≤Q≤ 65 65<Q<286 286≤Q≤3913
0.2
21.8
±Q min
±4.9 %RD
±3.5 %RD
0.2
46.9
±Q min
±4.9 %RD
±3.5 %RD
21.8≤Q≤39 39<Q<156 156≤Q≤2180
46.9≤Q≤ 78 78<Q<286 286≤Q≤4692
0.3
29.0
±Q min
±4.7 %RD
±3.2 %RD
0.3
62.5
±Q min
±4.7 %RD
±3.2 %RD
29.0≤Q≤48 48<Q<156 156≤Q≤2904
62.5≤Q≤104 104< Q<286 286≤Q≤6249
25