Chapter 5.  SPECIFICATIONS

 

Specifications

Item

Specifications

MVF050

MVF080

MVF100

MVF150

Pipe size

50A (2B)

80A (3B)

100A (4B)

150A (6B)

Flowrate mea-

surement range 

(for air)*

2

  

[ m

3

/h (normal)]*

3

at a pressure of 0.05 MPa

7.4 to 322

11.0 to 711

13.7 to 1095

23.6 to 2356

at a pressure of 0.15 MPa

7.4 to 535

11.8 to 1181

18.2 to 1819

39.1 to 3913

at a pressure of 0.5 MPa

12.8 to 1280

28.3 to 2825

43.5 to 4351

93.6 to 9364

Applicable gas

Air, Nitrogen, Argon, Oxygen*

1

, Carbon dioxide, natural gas (LNG base), Methane, Propane, 

Butane, and other inert gases and mixed gases outside the explosion limit range.

Volumetric flowrate accuracy (for air)*

4

*

5

±2 %RD at 73 m

3

/h 

(actual) or more

±2 %RD at 109 m

3

/h 

(actual) or more

±2 %RD at 154 m

3

/h 

(actual) or more

±2 %RD at 282 m

3

/h 

(actual) or more

Accuracy after temperature and pressure cor-

rection (at a pressure of 0.5 MPa)*

6

±3.3 %RD at 74 m

3

/h 

(normal) or more

±3.3 %RD at 110 m

3

/h 

(normal) or more

±3.3 %RD at 156 m

3

/h 

(normal) or more

±3.5 %RD at 286 m

3

/h 

(normal) or more

Operating pressure range 

(Accuracy of pressure sensor)

0.0 to 0.1 MPa (±2 %FS at 23 °C) for MVF_ _ _1
0.0 to 0.3 MPa (±2 %FS at 23 °C) for MVF_ _ _3
0.0 to 1.0 MPa (±1 %FS at 23 °C) for MVF_ _ _0

Pressure resistance

0.15 MPa for MVF_ _ _1
0.45 MPa for MVF_ _ _3
1.5 MPa for MVF_ _ _0

Operating temperature range 

(Accuracy of temperature sensor)

−15 to +60 °C (±2 %RD (absolute temperature base))

Operating humidity range

10 to 90 %RH (No condensation allowed)

Flow rate calculation/output updating cycle

100 ms

Rated power supply

24 Vdc

Current consumption

100 mA max.

Output signal (1 point)

Instantaneous flowrate output:  4 to 20 mAdc (Allowable load resistance 600 Ω max.)

Maximum Current value: 23.2 mA

Integrated pulse output (1 point)

Open collector output Absolute maximum rating: 30 Vdc, 20 mA max.

Pulse weight  MVF050: 0.01, 0.1, 1, 10 

(The unit depends on the instantaneous flow rate display unit.) 

MVF080/100/150: 0.1, 1, 10, 100 

(The unit depends on the instantaneous flow rate display unit.)

Pulse width  Output intervals of 1s or more: 0.5 s 

Output intervals of less than 1s: duty ratio 50 %

Communication function 1

RS-485 interface, Transmission line: 3-wire system

Communication distance: 300 m max. Compatible with Azbil Corporation's products 

(CMC15G, etc.)

Transmission speed: 2400, 4800, 9600, 19200 bps

Integrated value, instantaneous, value/warning, and settings can be recorded.

Communication function 2

Mini-plug jack for PC Smart Loader connection, used in servicing by the manufacturer.

Display

Flowrate display

6-digit LCD for instantaneous flow rate, 8-digit LCD for totalized flow rate

Instantaneous flow rate 

_ _ _ _ _._ m

3

/h

(“1” is the max. value for the first digit)

_ _ _ _ _  m

3

/h  

(no decimal point)

(“1” is the max. value 

for the first digit)

Totalized flow rate*

7

_ _ _ _ _ _ _._ m

(up to 1 digit after 

the decimal point)

_ _ _ _ _ _ _ _ m

3

 (no decimal point)

Status display

OVER: Flowrate range over, setting: For maintenance

Gas contacting parts material

Flow passage: SUS304 (SCS13A) μF sensor: Silicon, Gold etc., O-ring: Type 4D (Viton)

Convertor material

Aluminum alloy (ADC12)

Convertor coating

Acrylic resin corrosion resistant coating Coating color: Light beige

Display glass parts material

Tempered glass: Thickness 10 mm

Mounting direction

(flow direction) Horizontal/Vertical mounting

Connection type

MVF_ _ _ _ _U: JIS 10K wafer connection

MVF_ _ _ _CD: DIN PN10 wafer connection

MVF_ _ _ _CA: ANSI 150 wafer connection

18

Summary of Contents for MVF Series

Page 1: ...product This manual contains information for ensuring the correct use of this prod uct It also provides necessary informa tion for installation maintenance and troubleshooting This manual should be re...

Page 2: ...hout notice Considerable effort has been made to ensure that this manual is free from inaccuracies and omissions If you should find an error or omission please contact the azbil Group In no event is A...

Page 3: ...manual uses the icons and conventions listed below Use caution when handling the product The indicated action is prohibited Always follow the indicated instructions Handling precautions Handling Preca...

Page 4: ...or use a throttle valve or the like to control the flowrate If the velocity exceeds the maximum measurable velocity both the flowrate display and the output voltage current may indicate considerably...

Page 5: ...nce Doing so might damage this device The Role of This Manual A total of 2 different manuals are available for the MVF Series Read them as necessary for your specific require ments If a manual you req...

Page 6: ...TS on this device Chapter 3 INSTALLATION MOUNTING WIRING This chapter describes installation mounting and wiring on this device Chapter 4 TROUBLESHOOTING This chapter describes how to investigate and...

Page 7: ...n 7 Behavior when the flowrate greatly exceeds the upper limit of flowrate 7 Precautions for piping installation 7 Piping work 10 Wiring 12 Chapter 4 TROUBLESHOOTING Nothing on display 16 Error messag...

Page 8: ......

Page 9: ...m square and 0 5 mm thick made possible by silicon micro machining and thin film technolo gies By using this high sensitivity high speed sensor to detect vortex frequency measurement rangeability of 1...

Page 10: ...to 20 mAdc output Integration pulse output 1 Power 24 Vdc 1 RS 485 communications 0 Horizontal Flow direction left to right Converter on top 2 1 Horizodntal Flow direction left to right Converter on b...

Page 11: ...dc output Integration pulse output 1 Power 24 Vdc 1 RS 485 communications 0 Horizontal Flow direction left to right Converter on top 2 1 Horizodntal Flow direction left to right Converter on bottom 2...

Page 12: ...es model number range and pulse rate Check that they are the same as the specifications ordered Converter Calculates temperature and pressure correction etc Wiring port There are 2 wiring ports Used f...

Page 13: ...more Upper 7 segment display Displays instantaneous flow rate Example 10000 0 m3 h Lower 7 segment display Displays integrated flow rate Example MVF050 1000000 0 m3 MVF080 100 150 10000000 m3 Station...

Page 14: ...ne could be injured by flying parts Caution Be sure to use this device for a flow not exceeding 36m s the maximum measurable velocity To pre vent excessive flow use a suitable means to control the sup...

Page 15: ...splay will stop increasing in proportion to the flowrate Be sure to use this device within the maximum measurable velocity If the velocity exceeds 50 m s the flowrate display will begin to decrease gi...

Page 16: ...ngle plane double 90 bend 10D min 5D min Flow direction Pipe with threedimen sional double 90 bend 20D min 5D min Flow direction If the oil water or dust is contained in a fluid install a device to re...

Page 17: ...ation damp ing device muffler between the pump or roots blower and this device to suppress the influence of pulsation as much as possible If the device is installed downstream of branched piping it ma...

Page 18: ...cause leak age or measurement error Be sure to flush cleaning the inside of pipe before installation this device to eliminate any foreign matter which might exist inside the pipe When installing pay...

Page 19: ...more a little at a time Tighten bolts within the specified tightening torque Otherwise the bolts may be damaged Do not forcibly insert into the narrow space between the flange faces Doing so might ca...

Page 20: ...the same electrical conduit There are two wiring methods direct cable lead out and use of an electrical wiring conduit When installing the device outdoors be sure to use a conduit Tools required Phill...

Page 21: ...diameter 6 Connect the wiring to the terminal block 7 Put the terminal cover back in place Procedure for using an electrical wiring conduit The wiring port thread is G1 2 1 Specify the wiring port Han...

Page 22: ...ax Input Load Load Power for load Handling precautions Connect COM of 4 20 mA output directly from the terminal block Do not use the COM of power supply terminal 4 20 mA and the COM of pulse output te...

Page 23: ...rm contact area Use crimp type terminal lugs applicable to M4 screw Be sure that the tightening torque of terminal screw is less than 0 8 N m Use the JIS C 3401 cables for control CVV etc of less than...

Page 24: ...dhered to the sensor Er04 Pressure sensor The cause may be an error or burnout of the pressure compensating sensor Er05 Flow sensor Pressure sensor The cause may be an error or burnout of the flow sen...

Page 25: ...mit alarm Pressure lower limit alarm AL 13 Flowrate upper limit alarm Temperature upper limit alarm Pressure lower limit alarm AL 16 Pressure upper limit alarm AL 17 Flowrate upper limit alarm Pressur...

Page 26: ...20 mAdc Allowable load resistance 600 max Maximum Current value 23 2 mA Integrated pulse output 1 point Open collector output Absolute maximum rating 30 Vdc 20 mA max Pulse weight MVF050 0 01 0 1 1 1...

Page 27: ...display becomes 00000000 after counting up to 99999999 For details about setup refer to MVF050 080 100 150 Micro Flow Vortex Gas Flowmeter User s Manual for Communications manual No CP SP 1183E 8 The...

Page 28: ...easured down to 5 2 m3 h Next we can calculate the minimum mass flow rate Qnormal m3 h normal at 0 C and pressure of 101 3 kPa with temperature and pressure correction Qnormal m3 h normal 5 2 273 0 27...

Page 29: ...low rate volumetric flow rate calculation Qactual m3 h 100 273 23 273 0 101 3 101 3 700 13 7 Volumetric flow rate Velocity calculation Velocity V m s Qactual m3 h S 3600 13 7 78 10 3 2 4 3600 0 8 S fl...

Page 30: ...umber is 15000 or less 4 RD when velocity is 0 5 m s or more and the Reynolds number is from 15000 to 35000 2 RD when the Reynolds number is 35000 or more MVF80 pipe size 80A Qmin minimum measurable f...

Page 31: ...13 Q 516 0 90 2 3 2 3 Q 4 4 Q 8 8 Q 234 0 90 5 2 5 2 Q 9 9 Q 12 12 Q 516 0 98 2 3 2 3 Q 4 4 Q 8 8 Q 234 0 98 5 2 5 2 Q 9 9 Q 11 11 Q 516 MVF100 Pipe size 100A MVF150 Pipe size 150A Operating pressure...

Page 32: ...min 4 7 RD 3 1 RD 0 05 11 0 Q min 4 7 RD 3 1 RD 7 4 Q 32 32 Q 74 74 Q 322 11 0 Q 31 31 Q 110 110 Q 711 0 1 7 4 Q min 4 6 RD 3 0 RD 0 1 11 0 Q min 4 6 RD 3 0 RD 7 4 Q 32 32 Q 74 74 Q 428 11 0 Q 31 31 Q...

Page 33: ...4 7 RD 3 2 RD 0 3 18 9 Q min 4 7 RD 3 2 RD 8 5 Q 32 32 Q 74 74 Q 854 18 9 Q 31 31 Q 110 110 Q 1886 MVF1003 MVF1503 Operating pressure MPa Minimum measurable flow rate Q min Accuracy Operating pressure...

Page 34: ...51 0 Q min 4 6 RD 3 0 RD 23 0 Q 38 38 Q 74 74 Q 2302 51 0 Q 85 85 Q 110 110 Q 5081 MVF1000 MVF1500 Operating pressure MPa Minimum measurable flow rate Q min Accuracy Operating pressure MPa Minimum mea...

Page 35: ...00 16000 18000 16 0 14 0 12 0 10 0 8 0 6 0 4 0 2 0 0 0 Pressure loss kPa Flow rate m h normal 3 When the MVF is used for a gas other than air multiply by the appropriate specific gravity below Specifi...

Page 36: ...External dimensions MVF050_S Pipe size 50A Unit mm 117 50 127 61 96 52 5 44 351 130 208 59 70 MVF080_S Pipe size 80A 117 50 127 61 126 60 367 130 208 59 70 78 28 Chapter 5 SPECIFICATIONS...

Page 37: ...A L I V E C O V E R MUST BE KE PT T I G H T 117 50 127 61 96 44 351 130 208 59 70 52 5 MVF080_C Pipe size 80A ADE IN JAPAN W H I L E C I R C U I T S A R E A L I V E C O V E R MUST BE KEPT T I G H T 1...

Page 38: ...MVF100_S Pipe size 100A 117 50 127 61 151 71 5 400 130 208 59 80 96 8 MVF150_S Pipe size 150A 117 50 127 61 212 142 100 428 130 208 59 120 Eyebolt 30 Chapter 5 SPECIFICATIONS...

Page 39: ...MVF100_C Pipe size 100A 399 70 5 40 100 117 50 127 61 59 130 208 151 96 8 MVF150_C Pipe size 150A 212 142 Eyebolt 127 61 99 427 117 50 130 208 59 140 60 31 Chapter 5 SPECIFICATIONS...

Page 40: ......

Page 41: ...Old pages are 11 to 13 Old pages are 14 and 15 Contact rating changed to Absolute maximum rating Pulse width added to pulse output Old page is 16 One atmospheric pressure changed to 101 3kPa Old page...

Page 42: ...he following matters into consideration 1 Regulations and standards or laws that your Equipment is to comply with 2 Examples of application described in any documents provided by Azbil Corporation are...

Page 43: ...cations or instruction manuals System products field instru ments sensors such as pressure flow level sensors regulating valves etc will reach the end of their life due to aged deterioration of parts...

Page 44: ...09 Specifications are subject to change without notice 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan URL http www azbil com 1st edition Sep 2005 W 6th edition Dec 2013 F...

Reviews: