Chapter 5. APPLICATION OPERATION
■
Parameter setup item list
No.
Item displayed
Item Description
Factory Setting
Setting Range
Remarks
1
(*1)
Instantaneous flow rate
upper limit alarm
(Upper limit of
measurement range)
CFH (normal)
(0 to 150% of
measurement
upper limit)
CFH (normal)
Selection of an alarm
detection condition is
required in function setup
C-
.
2
. H. Hy
Hysteresis for
instantaneous flow rate
upper limit alarm
(Within 2% of
measurement upper
limit) CFH (normal)
(0 to 100% of
measurement
upper limit)
CFH (normal)
3
.
*2
Instantaneous flow rate
lower limit alarm
(Lower limit of
measure range)
CFH (normal)
(0 to 100% of
measurement
upper limit)
CFH (normal)
4
. L. Hy
Hysteresis for
instantaneous flow rate
lower limit alarm
(Within 2% of
measurement upper
limit) CFH (normal)
(0 to 100% of
measurement
upper limit)
CFH (normal)
5
. Ly
Delay timing for
instantaneous flow rate
alarm judgment
60.0s
0.0 to 999.9s
6
. P. L
Integration event setup
(lower four digits)
0 CF
0 to 99,999,999
CF
Value set is valid only when
selecting integration event
output in either
C-
or
C-
of function setup.
7
. P. H
Integration event setup
(upper four digits)
8
. C. L
Integration reset delay
time
10.0s
0.0 to 999.9s
Value set is valid only when
selecting automatic reset by
integration reset delay in
C-
of function setup.
9
Instantaneous flow rate
bias (PV bias)
0 CFH
(-20 to +20% of
measurement
upper limit)
CFH (normal)
10
t. H
Instantaneous flow rate
output 20mA scaling
(Upper limit of
measurement range)
CFH (normal)
(0 to 150% of
measurement
upper limit)
CFH (normal)
11
t. L
Instantaneous flow rate
output 4mA scaling
0 CFH
(0 to 100% of
measurement
upper limit)
CFH (normal)
12
. C
Gas composition
compensation
coefficient
1.000
0.100 to 4.000
Note)
"Normal" refers to the volumetric flow rate (CFH) after converting to 32˚F,
1 atmosphere.
Handling Precautions
*1 Be certain to set a flow rate that is less than the display upper limit.
Alarm detection will not operate if flow rate is set above the display
upper limit.
*2 If "lower limit alarm1" has been selected in function setup
C-
, alarm
detection will not operate when the flow rate is less than the lower limit
of the measurement range, even if the flow rate is below the lower limit
alarm value.
18