Chapter 5. APPLICATION OPERATION
■
Function setup item list
Display
Function
Settings description
Factory
s
etti
ng
Remarks
C-1
Key lock
0: Key lock disabled
1: All settings key-locked
0
The key lock can be disabled even
while it is enabled.
C-
Flow rate alarm
detection condition
selection
0: Alarm detection is not performed.
1: Only the upper limit alarm is
detected.
2: Only lower limit alarm 1 is
detected.
3: Upper limit alarm and lower limit
alarm 1 are detected.
4: Only lower limit alarm 2 is
detected.
5: Upper limit alarm and lower limit
alarm 2 are detected.
0
The alarm detection flow rate is set in
the parameter setup mode.
Lower limit alarm 1:
A flow rate less than the lower limit
of the measurement range is not
judged to be an alarm.
Lower limit alarm 2:
A flow rate less than the lower limit
of the measurement range is judged
to be an alarm.
C-
Event output 1
(relay) function
assignment
0: Not used (OFF at all times)
1: ON when upper limit alarm
occurs
2: ON when lower limit alarm
occurs
3: ON when upper limit alarm or
lower limit alarm occurs
4: ON when integration event
occurs
3
C-
Event output 2
(open collector)
function
assignment
0: Not used (OFF at all times)
1: ON when upper limit alarm
occurs
2: ON when lower limit alarm
occurs
3: ON when upper limit alarm or
lower limit alarm occurs
4: ON when integration event
occurs
5: Integrated pulse output
5
C-
Flow rate alarm
reset method
selection
0: Only reset by key switch
1: Reset by key switch or automatic
reset by normal recovery of flow
rate
0
C-
Integrated flow rate
reset method
selection
0: Reset disabled.
1: Reset by key switch only
2: Only automatic reset after the
integration reset delay time when
the integration event occurs
3: Reset by key switch or automatic
reset after the integration reset
delay time when the integration
event occurs
1
C- 7
Total flow rate
reset method
selection
0: Reset disabled.
1: Reset by key switch
0
The integrated flow rate is also reset
when the total flow rate is reset.
C- 8
Reference
temperature
selection
0: 32˚F 1 atmosphere
0
The reference temperature of the flow
rate output can be switched.
1: 41˚F 1 atmosphere
2: 50˚F 1 atmosphere
3: 59˚F 1 atmosphere
4: 68˚F 1 atmosphere
5: 77˚F 1 atmosphere
C-
Pulse rate
selection
CMG152/252
CMG402/502
3
CMG152/252: Do not set except 2
and 3.
CMG402/502: Do not set except 3.
0: Disabled.
1: Disabled.
2: 0.1 CF/1 pulse
3: 1 CF/1 pulse
0: Disabled.
1: Disabled.
2: Disabled.
3: 1 CF/1 pulse
16