IMPORTANT: 

  Install the product to a pipe so that they are electrically connected at the same potential. If the valve and the 

pipe are electrically isolated, noise might be generated, causing incorrect measurement and control of flow. 

  When installing the product with flange gasket, do not use the rubber gasket or the gasket that goes inside the 

pipe. Doing so might cause incorrect measurement and control of flow. 

  This product is applicable only to chilled/hot water control. If the product is used to control any other medium 

such as brine or air, flow rate cannot be measured or controlled. 

  Install the valve so that the flow direction of process fluid agrees with the arrow indicated on the valve body. If 

the flow direction is opposite to the arrow, correct measurement and control of flow is not assured. 

  Do not loosen the yoke fixing screws or the actuator fixing screws. Loose fixing screws lower flow measuring 

accuracy. Note that the actuator mounting position onto the valve cannot be changed. 

  Flow measuring accuracy in the subsection 

Measuring range and accuracy

shown later is for the valve 

sensor measuring 44.6 to 62.6 

F (7 to 17 °C) and 113 to 149 

F (45 to 65 °C) ranges, 29 to 261 psig pipe 

pressure, and 4.35 to 43.5 psig differential pressure. Without these ranges, the flow rate measuring accuracy 

might decrease. 

  To keep flow measuring accuracy, control the quality of process fluid (water), and do not allow rust or foreign 

object inside the valve. Rust or foreign object inside the valve lowers flow measuring accuracy. 

  Thermally insulate the valve, and do not allow the process fluid to freeze. Frozen process fluid around the valve 

sensor might damage the valve sensor and cause error output. 

 

 

 Model  Numbers 

Model FVY5137J is the model for the valve and actuator integrated into a single unit.   
The model number label is attached to the yoke. 

Base 

model 

number 

Actuator/valve Actuator 

Valve 

Fixed

Description 

Ctrl 

signal 

Rating/ 

material 

Type Fixed 

Size/ 

Cv value

FVY51  

 

 

 

 

 

Motorized two-way valve with flanged-end connection 
(Flow measuring and controlling functioned) 

 3 

 

 

 

   

4 to 20 mA DC input, pulse output, RS-485 communication (Modbus 
protocol) 

  

 

 

   

145 psig / Gray cast iron for chilled/hot water 

  

 

 

   

NEMA 4X and IEC IP54 protected and standard torque type actuator 
with terminal block 

  

 

 

00 

   

Fixed 

  

 

 

 

41 

 

1

1

/

2

” / 25 Cv 

  

 

 

 

42 

 

1

1

/

2

” / 40 Cv 

  

 

 

 

51 

 

   2” / 65 Cv 

  

 

 

 

61 

 

2

1

/

2

” / 95 Cv 

  

 

 

 

81 

 

   3” / 125 Cv 

  

 

 

 

  -S03 

 

*  This product was designed and manufactured conforming to the ISO (International Organization for Standardization, PN10/GG-20). 

Summary of Contents for ACTIVAL FVY5137J

Page 1: ...retrieved flow data is effective for energy saving facility operation Features Compact and lightweight Rotary valve actualizes small body and light weight Valve and actuator integrated in a single un...

Page 2: ...ls weigh more than 40 lb 18 1 kg Carefully move the product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product dam...

Page 3: ...ouch the moving parts of the product Doing so might cause injury Do not carelessly touch this product when being used to control hot water The product temperature is hot and you might get burned Do no...

Page 4: ...to 17 C and 113 to 149 F 45 to 65 C ranges 29 to 261 psig pipe pressure and 4 35 to 43 5 psig differential pressure Without these ranges the flow rate measuring accuracy might decrease To keep flow me...

Page 5: ...resistance Between the case and terminal Min 5 M 50 V DC Dielectric strength Between the case and terminal 250 V AC for 1 min leakage current 5 mA or less Position for shipment 100 fully open preset...

Page 6: ...4 pin connector Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 second ON 1 second OFF Major alarm Continuous ON Minor alarm Repetition of 1 second ON 0 25 second...

Page 7: ...4 C at 0 to 80 C ambient temperature 1 08 F at 4 to 32 F 0 6 C at 20 to 0 C ambient temperature Error due to wiring length 0 27 F at 49 2 49 2 ft 0 15 C at 15 15 m in the 32 to 176 F 0 to 80 C measur...

Page 8: ...with the sensor 98 ft 30m 6 pin 3 pin 2 connector Insertion type pipe temperature sensor AWG 22 x 3 core 0 3 mm 2 98 ft 30m RS 485 communication AWG 16 24 x 2 pairs of shielded twist pair cable 1 pair...

Page 9: ...24 190 90 20 140 180 19 16 kg FVY5137J0081 S03 3 in 10 35 4 92 7 99 3 94 0 87 6 00 7 48 0 75 4 45 0 lb DN80 mm 263 125 203 100 22 152 4 190 19 20 4 kg Figure 1 Dimensions Parts Identification 1 to 3 v...

Page 10: ...rature Row T2 Return water temperature Reset switch Connector for Display Panel 24 V AC Power Port for Display Panel cable Port for temperature sensor Pt100 input cable Port for valve sensor cable Por...

Page 11: ...the inflow side of the piping Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product After installation make sure no fluid leaks f...

Page 12: ...tor in water Although the product can be used outdoors be sure not to expose the product to direct sunlight Provide the outdoor cover optional to install outdoors Install the product in a position all...

Page 13: ...alve The valve cannot fully close or the valve seat may get damaged causing fluid leakage due to an object jammed inside the valve When piping do not apply too much sealing material such as solidifyin...

Page 14: ...lly open close the product do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the product slowly turn the joint If shock is sent to the actuator the actuator might ge...

Page 15: ...connector Use crimp terminals with insulation for connections to the product terminals Failure to do so might cause short circuit leading to fire or device failure Firmly tighten the terminal screws...

Page 16: ...sensor Pt100 input Figure 13 6 pin connector for temperature sensor Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red P...

Page 17: ...of the recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 0 31 8 mm...

Page 18: ...es of RS 485 communication cable to the connector unplugged from the actuator socket After connecting the wires to the connector plug the connector into the socket Do not use terminators Do not connec...

Page 19: ...er with multiple 4 to 20 mA input type products See Figs 22 and 23 4 to 20 mA control signal input is not isolated from the power and the 4 to 20 mA input impedance is 250 For connecting a controller...

Page 20: ...Refer to 6 Single transformer with two products in the Precautions for connection section Figure 23 Connection example Two Model FVY5137 with a single controller and a single transformer Notes 1 Prov...

Page 21: ...lizing pulse output open collector output Model FVY5137J This product 3 4 V Protection diode Magnetic counter 0 V Figure 28 Connection example Magnetic counter with relay coil Figure 26 Connection exa...

Page 22: ...ed by cable glands use waterproof plica tubes etc Item Model number Applicable cables Three port unit is used 83104346 012 0 24 Dia to 0 31 Dia 6 mm Dia to 8 mm Dia 83104346 013 0 28 Dia to 0 35 Dia 7...

Page 23: ...the cable gland with three ports Refer to the below table and tighten each part of the cable gland to connect it onto a wiring port knockout of this product Part of cable gland with three ports Fasten...

Page 24: ...erminal connector to facilitate connecting wires 5 Loosen the cap of a seal connector Let the wires through the seal connector so that the end of the sheath comes to inner side of the cover Then tight...

Page 25: ...be re crimped on the wire ends Keep the margins therefore to arrange the cables IMPORTANT Do not put heavy load on the joint of the cable gland with the product Detaching the cable gland with three p...

Page 26: ...If your problem is not solved by the corresponding action please contact our salesperson serviceperson Table 1 Inspection items and details Inspection item Inspection interval Inspection detail Visua...

Page 27: ...AB 7350 U 27 Figure 34 Check of the valve position detecting accuracy Pointer 0 39 1 cm Lower setscrew of the terminal cover 0 39 1 cm...

Page 28: ...AB 7350 U Rev 4 0 Jun 2016 AB 7350 U 28 ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries...

Reviews: