AB-7350-U
22
Cable Gland with Three Ports
Cable gland with three ports (Model DY7000A1000) is recommended to attach to a wiring port (knockout) of this product when
RS-485 communication line and signal line are passed through the same wiring port. The cable gland with three ports is
applicable to cables for small power. (Small power: 60 V or lower input voltage)
CAUTION
Firmly tighten the terminal screws.
Insufficient tightening of the terminal screws might cause fire or overheating.
IMPORTANT:
Carefully attach the cable gland with three ports so that O-rings do not fall from the cable gland. Without
O-rings, water-proof protection is not assured.
To keep NEMA 4X and IEC IP54 protection
In order to maintain NEMA 4X and IEC IP54 performance, use waterproof connectors etc. when the product is used in high
humidity environment or outdoor.
Close the terminal cover and top cover firmly.
Apply a waterproofing treatment for the knockout holes.
Use waterproof connectors to pull out the cables.
Select suitable connectors from the table below according to diameter of the cables.
If cables are connected by cable glands, use waterproof plica tubes etc.
Item
Model number
Applicable cables
Three-port unit is used
83104346-012
0.24" Dia. to 0.31” Dia. (6 mm Dia. to 8 mm Dia.)
83104346-013
0.28" Dia. to 0.35” Dia. (7 mm Dia. to 9 mm Dia.)
83104346-014
0.35" Dia. to 0.43” Dia. (9 mm Dia. to 11 mm Dia.)
83104346-015
0.43" Dia. to 0.51” Dia. (11 mm Dia. to 13 mm Dia.)
Three-port unit is not used 83104346-003
0.28" Dia. to 0.35” Dia. (7 mm Dia. to 9 mm Dia.)
83104346-004
0.35" Dia. to 0.43” Dia. (9 mm Dia. to 11 mm Dia.)
83104346-005
0.43" Dia. to 0.51” Dia. (11 mm Dia. to 13 mm Dia.)
83104098-001
(Pipe-insertion type temperature
sensor)
0.16" Dia. to 0.24” Dia. (4 mm Dia. to 6 mm Dia.)
Removing the cover from the base
Remove the cover from the base by releasing the 3 latches. Follow the below procedure to release the latches.
IMPORTANT:
When you remove the cover from the base, it is fairly difficult to release the last latch. To easily release all the
latches, start with the one which cannot be visibly checked.
1) Press the upper part of one of the male latches ('1' in the figure below.)
2) Press up the lower part of the one of the male latches ('2' in the figure below) toward the direction '3' while pressing '1' to
release the latch.
Note:
* Do not use a tool such as a screwdriver since a tool may damage a latch.
3) Perform 1) and 2) to release the other 2 latches.