Transistory fault Er
2
If transistory faults Er
1
are detected in work of heating system, energy calculation do not stop and these
errors are displayed via 5 character error code:
Detailed description of transistory faults codes Er
2
Display
Description
Er2: 00000
No error. Normal mode
Er2: 00001
Flow q1 flow in reverse direction
Er2: 00002
Flow value q1< q1
i
(the minimum allowable value of flow rate)
Er2: 00004
Flow value q1
q1
s
(the maximum allowable value of flow rate)
Er2: 00008
Flow sensor V1 is not filled by a liquid
Er2: 00010
Flow q2 flow in reverse direction *
Er2: 00020
Flow value q2< q2
i
(the minimum allowable value of flow rate)
Er2: 00040
Flow value q2
q2
s
(the maximum allowable value of flow rate)
Er2: 00080
Flow sensor V2 is not filled by a liquid
Er2: 00100
On input V3 more than 24 hours do not arrive pulses **
Er2: 00200
Flow value q3< q3i (the minimum allowable value of flow rate)
Er2: 00400
Flow value q3
q3s (the maximum allowable value of flow rate)
Er2: 00800
Short circuit V3 ***
Er2: 01000
On input V4 more than 24 hours do not arrive pulses **
Er2: 02000
Flow value q4< q4i (the minimum allowable value of flow rate)
Er2: 04000
Flow value q4
q4s (the maximum allowable value of flow rate)
Er2: 08000
Short circuit V4***
Er2:10000
Temperature difference
1-
2 < d
min
Er2:20000
Temperature difference
1-
2 < 0
o
C
Er2:40000
Temperature
3 <- 40
o
C or sensor has short circuit ****
Er2:80000
Temperature
3 > 180
o
C or sensor has open circuit ****
Er2:50000
At the same time there are two error: “10000” and “40000”
Er2:60000
At the same time there are two error: “20000” and “40000”
Er2:90000
At the same time there are two error: “10000” and “80000”
Er2:A0000
At the same time there are two error: “20000” and “80000”
Note:
* - Are not shown, when the algorithm 'winter / summer' is applied
** - only when flow input type “L”is on (“24 hours pulse control”)
*** - only when flow input type “E”is on (“short circuit control”)
**** - only when temperature measurement chanell T3 is on
Active error codes are added and simultaneously displayed
Status of temperature sensor
Status of flow sensor V1
Status of flow sensor V2
Status of flow sensor V3
Status of flow sensor V4