Chapter 6: Power Management
109
To upgrade IPDU firmware:
1.
From http://www.avocent.com, click
Resources-Updates and Documentation.
2.
From the Updates section, click
Cyclades PM Intelligent Power Distribution Unit for Cyclades
PM IPDU
or click
PM2000 PM3000 Rack PDUs for Avocent PM PDU
. The web page will
show a firmware list.
3.
Click the
firmware
link. It is recommended that you download the new firmware to a /tmp
directory since files in this directory are deleted during the boot process.
NOTE:
It is recommended that you run md5sum on the file after you download it and compare the md5sum
output with the contents of the firmware md5 file on the avocent web site, to ensure that the firmware file you
downloaded was not corrupted.
CAUTION:
It is possible that all outlets get turned off during the upgrade process. Make sure to shut down all
connected devices before starting the firmware upgrade process.
4.
Execute the pmfwupgrade application from the shell prompt. Table 6.3 describe
the parameters.
#
pmfwupgrade [<options>] {all | -s <serial device name> | <IPDU id>}
[<filename>]
SNMP Proxy
The SNMP proxy for power management feature allows the console server to proxy SNMP
requests to the IPDU. This allows SNMP clients to query and control the remote IPDU using
standard set and get commands.
The following parameters and features are controlled in the remote IPDU:
•
The number of IPDU units connected to the console server.
•
The number of outlets connected to a serial port.
Table 6.3: pmfwupgrade Application Parameters
Parameter
Description
-h
Show the help message and exit.
-f
Upgrade the firmware without asking any questions.
-v
Show messages about the status of the upgrade.
-s
<serial device name>: Serial port name where the PM IPDU is connected.
This option upgrades all IPDU appliances in daisy-chained IPDUs connected
to the serial port.
<IPDU id>
IPDU identification name.
<filename>
The new firmware to upload to the PM unit. Default:/tmp/pmfirmware.
Summary of Contents for Cyclades ACS 5000 SERIES
Page 1: ...CYCLADES ACS 5000 Command Reference Guide ...
Page 8: ...vi Cyclades ACS 5000 Advanced Console Server Command Reference Guide ...
Page 16: ...8 Cyclades ACS 5000 Advanced Console Server Command Reference Guide ...
Page 40: ...32 Cyclades ACS 5000 Advanced Console Server Command Reference Guide ...
Page 62: ...54 Cyclades ACS 5000 Advanced Console Server Command Reference Guide ...
Page 76: ...68 Cyclades ACS 5000 Advanced Console Server Command Reference Guide ...
Page 151: ......
Page 152: ...590 814 501B For Technical Support www avocent com support ...