To connect the indicator to the scale using the home run cable, remove the
protective cap from the bottom connector on the junction box. Apply noncon-
ductive silicone grease inside the protective cap and if needed, also on the
cable connector, before connecting. Refer to Figure 6.

Figure 5

Grounding details

Install the T-gap covers, (optional), at each end of the scale to cover the gap
between the edge of the scale deck and the bulkhead.

The scale is now ready for testing, calibration, and inspection (as required).

Figure 6

Interconnecting details

For best grounding we
recommend one grounding
rod for each end of a scale,
one grounding rod for each
junction of scale decks, and
a separate ground for the
power source in accordance
with NEC Code 250. When
possible, this power source
ground should also be tied
to the scale grounds.

Summary of Contents for BridgePort

Page 1: ...profile self contained portable scale suited for a wide variety of applications It is designed and manufactured for simplified temporary installation and relocation when necessary The basic units are...

Page 2: ...6 below the frost line To speed the installation of the scale ensure the proper installation of the piers before receiving the scale For the dimension information refer to the installation drawing Th...

Page 3: ...ock on the frame Adjust the check bolts to a maximum of 3 16 clearance Refer to Figure 3 Figure 3 Checkbolts Install the optional bulkheads on each end of the scale If the bulkheads are from Weigh Tro...

Page 4: ...d level for a minimum of 10 feet at each end of the scale The ground rods must be installed as close as possible to the scale module at each end and same side as the junction box Connect the ground ro...

Page 5: ...ll the T gap covers optional at each end of the scale to cover the gap between the edge of the scale deck and the bulkhead The scale is now ready for testing calibration and inspection as required Fig...

Page 6: ...n Position each module end to end Make sure the junction boxes remain on the same side of the scale To ensure the proper positioning of the second and third module if appli cable the units must be as...

Page 7: ...ulkhead Weigh Tronix will not be responsible for error caused by other bulkheads Once the bulkheads are properly installed prepare the ramps at each end of the scale The ramps must be straight and lev...

Page 8: ...box connectors Remove the tie down bolts and store them in a safe place for future use Install the hold down bolts to secure the scale weigh bridge to the frame To prevent movement of the scale platf...

Page 9: ...gh bar 15 std cable 271 73 0046 Weigh bar 50 std cable 271 73 0053 Weigh bar 15 S S sheathed cable 27173 0061 Weigh bar 50 S S sheathed cable 27173 0079 50 home run std cable 1 7 pin male connector 47...

Page 10: ...ction box cover to access the potentiometers 2 To capture the value of internal zero for your particular indicator refer to your indicator s Service Manual 3 Use test weights equal to 20 25 of full ca...

Page 11: ...A Weigh Tronix 1000 Armstrong Dr Fairmont MN 56031 USA Telephone 507 238 4461 Facsimile 507 238 4195 e mail industrial weigh tronix com www weigh tronix com Weigh Tronix Canada ULC 217 Brunswick Blvd...

Reviews: