Assemble on the base plate and connect
the pneumatics
The base plate is available in various designs as an
accessory part. The illustration shows an example with a
single base plate
1.
Insert the three base plate seals (
15
) in the thread
connections (
3
,
4
,
5
) and
press in.
The seals are formed so they engage in the thread
connections and cannot fall out during assembly.
2.
Place the ED05 pressure regulator on the base plate.
3.
Insert both of the M6x75 screws (
16
) in the two through
holes in the housing
(see Figure
) and tighten.
Tightening torque: 6 Nm
Connecting the supply voltage and set
point
To operate the ED05 pressure regulator, you must supply
the device with compressed air, connect the 24 V DC
supply voltage, and control the device with
a set point.
The electrical set point is connected to pin 2 (set point (+))
and pin 3 (0 V).
The actual electrical value can be measured between pin
4 (actual value (+)) and pin 3 (0V).
Observe the following table containing the plug
assignment of the integrated XPC plug, M12, for this.
3
3
1
Installation conditions
Mounting orientation
See Fig
.
Assemble on a mounting plate and
connect the pneumatics
1.
Insert both the screws (
14
) (e.g. M6 x 75 in accordance
with DIN EN ISO 4762, formerly DIN 912) in the two
through holes in the housing as shown in the
illustration and
tighten.
Tightening torque: 6 Nm
2.
Connect the supply line at inlet connection1 (
4
).
3.
Connect the outlet line at the outlet connection 2 (
3
).
4.
Always connect a silencer or a line for restricted
exhaust at the exhaust air connection 3 (
5
).
NOTICE
Malfunction due to atmosphere containing oil
Oil may clog the housing ventilation port. This will
change the characteristic curve.
O
Never operate the device in an atmosphere
containing oil.
Malfunction caused by closed housing ventilation port
If the housing ventilation port is closed, there is no
atmospheric equalization and the characteristics curve
will change.
O
Ensure that the air can circulate freely through the
housing ventilation
port
(
6
).
The inside diameter of the supply line must be at
least 6 mm to attain the air flow rate stipulated in
the specifications.
1
1
5
2
2