5. Disposal
Do not dispose this product as unsorted municipal waste. Collection of such waste
separately for special treatment is necessary.
It is prohibited to dispose of this appliance in domestic household waste.
For disposal, there are several possibilities:
A) The municipality has established collection systems, where electronic waste can be disposed of at
least free of charge to the user.
B) When buying a new product, the retailer will take back the old product at least free of charge.
C) The manufacture will take back the old appliance for disposal at least free of charge to the user.
D) As old products contain valuable resources, they can be sold to scrap metal dealers.
Wild disposal of waste in forests and landscapes endangers your health when hazardous substances
leak into the ground-water and find their way into the food chain.
When using this air conditioner in the European countries, the follow information must be
followed:
Disposal:
51
Error code list:
TROUBLESHOOTING AND DISPOSAL
Error code
TIMER indicator
Description
E1
1 blink
Indoor room temperature sensor fault (Ta)
E2
2 blinks
Outdoor coil temperature sensor fault (Tcm or Tdef)
E3
3 blinks
Indoor coil temperature sensor fault (Tem)
E4
4 blinks
Indoor fan motor or DC motor feedback fault
E5/5E
5 blinks
Indoor & outdoor communication fault
F0
10 blinks
Outdoor DC Fan motor fault
F1
11 blinks
IPM module fault
F2
12 blinks
PFC module fault
F3
13 blinks
Compressor start fault
F4
14 blinks
Exhaust temperature sensor fault (Td)
F6
16 blinks
Outdoor room temperature sensor fault (Tao)
F7
17 blinks
Over / under voltage protection
F8
18 blinks
Main PCB & Inverter communication fault
F9
19 blinks
Outdoor EEPROM fault
J3/P3
20 blinks
Refrigerant leakage detection
FA
21 blinks
Suction temperature sensor fault (Ts)
J8/P8
22 blinks
Outdoor over current protection
J5/P5
23 blinks
Compressor high exhaust temperature protection
J4/P4
24 blinks
High pressure protection failure
H8
25 blinks
Four way valve fault
H1
26 blinks
Dranaige failure
H2
27 blinks
Remote control communication fault
H5
28 blinks
Compressor exhaust temperature is too low protection
H6
29 blinks
Low voltage swithc fault
H7
30 blinks
Low pressure protection
H3
31 blinks
Evaporator inlet temperature sensor fault (Tiq)
H3
31 blinks
Evaporator inlet temperature sensor fault (Tiq)
H4
32 blinks
Evaporator outlet temperature sensor fault (Tas)
H9
33 blinks
Indoor & outdoor communication line fault dislocation
Summary of Contents for AM Series
Page 1: ...Manual de usuario e instalación MULTI INVERTER SERIE AM CL80100 CL80112 ...
Page 2: ... ES EN 3 32 2 ...
Page 27: ...CONTROL REMOTO 27 ...
Page 28: ...CONTROL REMOTO Este botón no tiene función en este equipo 28 ...
Page 29: ...CONTROL REMOTO 29 ...
Page 30: ...CONTROL REMOTO 30 ...
Page 31: ...CONTROL REMOTO 31 ...
Page 56: ...REMOTE CONTROLLER 56 ...
Page 57: ...REMOTE CONTROLLER This button has no function 57 ...
Page 58: ...REMOTE CONTROLLER 58 ...
Page 59: ...REMOTE CONTROLLER 59 ...
Page 61: ...61 ...
Page 62: ...C PROVENZA 392 P2 08025 BARCELONA SPAIN 34 93 446 27 80 ...