Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 22
StaRtup
When the AutroPath HC800 is installed and wired as
described in the “Installation” section, it is ready for
commissioning. If the application requires that specific
changes be made to the factory settings, HART
communication will be required.
NoTe
ensure that alarm devices are bypassed during
commissioning.
NoTe
The safety function (gas input-to-actuation/
notification) must always be verified upon
completion of installation and/or modification.
aliGnMEnt
oVeRVIew
The AutroPath HC800 modules must be properly
aligned before normal operation will be attained.
NoTe
Refer to the ATeX or IeCex Appendix for
information regarding the effect of misalignment
on system accuracy.
Important
Upon completion of system alignment, ensure
that
all
bolts on the AutroPath HC800 mounting
and alignment bracket are properly tightened.
24 VDC
+
–
B2653
250 TO 500
OHMS
+mA
INTR GND
RS-485 A
INTR A
SHIELD
SHIELD
+24 VDC
SPARE
+24 VDC
11
12
13
14
15
16
17
18
19
–mA
CAL
RS-485 B
INTR B
SHIELD
SHIELD
0V COM
0V COM
0V COM
1
2
3
4
5
6
7
8
9
HART
NOTE: THE HART HANDHELD DEVICE CAN BE CONNECTED EITHER TO THE
HART TERMINALS OR ACROSS THE LOAD RESISTOR.
Figure 20—Wiring the autropath Hc800 Receiver for benchtop
testing/programming using HaRt protocol
HART CONNECTORS
A2672
Figure 22—location of HaRt connector pins
(Receiver Module Shown)
C2667
+mA
INTR GND
RS-485 A
INTR A
SHIELD
SHIELD
+24 VDC
SPARE
+24 VDC
11
12
13
14
15
16
17
18
19
–mA
CAL
RS-485 B
INTR B
SHIELD
SHIELD
0V COM
0V COM
0V COM
1
2
3
4
5
6
7
8
9
HART
NOTE 1:
TOTAL LOOP RESISTANCE OF 4-20 MA CIRCUIT =
250 OHMS MINIMUM, 600 OHMS MAXIMUM.
NOTE 2: NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX).
CAUTION: DO NOT CONNECT THE COMMUNICATION LINK “INTR GND”
TERMINAL TO POWER SUPPLY COMMON OR ANY OTHER
GROUND CONNECTION.
INTR GND
RS-485 A
INTR A
SHIELD
SHIELD
+24 VDC
+24 VDC
17
16
15
14
13
12
18
SPARE
RS-485 B
INTR B
SHIELD
SHIELD
0V COM
0V COM
8
7
6
5
4
3
2
HART
TRANSMITTER
RECEIVER
24 VDC
+
–
+
–
4 to 20 MA
Figure 21— typical System Wiring including optional communication
link Wiring — Receiver Wired for non-isolated 4–20 ma current output
(Sinking)