Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 23
equIPmeNt RequIReD
1. Properly installed and powered AutroPath HC800
system (transmitter and receiver). Easy access to
both modules is highly recommended.
2. AutroPath HC800 Alignment Tool. The alignment
tool is recommended for use in commissioning all
AutroPath HC800 systems. The following instructions
cover the use of the Alignment Tool.
3. 9/16 inch wrench.
4. 15/16 inch wrench.
5. For installations with short separation distances
(5-15 meters for the short range model and 30-40
meters for the long range model), the short range
aperture kit (supplied) is typically needed. Refer to
“Aperture Kit for Short Range Applications” section
of this manual for details.
ALIGNmeNt PRoCeDuRe
1. Ensure that the system modules are located within
the specified separation range and securely fixed
to the support structures. Bypass all external gas
alarm devices that are connected to the receiver
outputs.
2. Ensure that the system modules are installed with
their windows at approximately the same height
above grade. Each module should be roughly
aligned to face in the direction of the other module.
3. Loosen the Horizontal and Vertical Adjustment
Bolts on the mounting and alignment bracket using
the 9/16” wrench for the Horizontal Adjustment
Bolts and the 15/16” wrench for the Vertical
Adjustment Bolts. See Figure 23.
4. Loosen the four Horizontal Locking Bolts on top of
the mounting and alignment bracket using a 9/16”
wrench, then retighten until just snug against the
top plate of the Detector Mounting Assembly. The
Detector Mounting Assembly should still be able
to rotate on its axis when adjusting the Horizontal
Adjustment Bolts. If not, slightly loosen the four
Horizontal Locking bolts.
5. Remove the brow by gently working side to side
while pulling forward.
HORIZONTAL LOCKING BOLTS (4)
HORIZONTAL ADJUSTMENT BOLT
WITH LOCK NUT (2)
VERTICAL ADJUSTMENT BOLT
WITH LOCK NUT (2)
DETECTOR MOUNTING ASSEMBLY
Figure 23—autropath Hc800 Mounting and alignment bracket (Receiver Module Shown)