Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 36
Additional Safety Notes:
• For ambient temperatures below –10°C, use field wiring suitable for the expected conditions, and for ambient
temperatures above +60°C, use field wiring and cable glands suitable for 15°C above the maximum expected
conditions.
ATEX Standards:
EN 60079-29-4: 2010
Performance Approved for Methane, Butane, and Propane
EN 60079-0: 2012 +A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-28: 2007
EN 60529:1991+A1: 2000
EN 50270: 2015
EN 50271: 2010
ACCurACy (per en 60079-29-4)
±5% of full scale gas concentration or ±10% of applied gas concentration, whichever is greater.
ReSPoNSe tIme
T90: 2 seconds (2.5 LFL-meters applied).
ALIGNmeNt
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of EN
60079-29-4.
Accessories with the following part numbers are approved for use with the AutroPath HC800:
116-011773-001
Short Range Aperture Kit
116-012287-XXX
AutroPath HC800 Alignment Tool
116-009246-002
Gas Test Cell
116-012673-001
System Test Film
116-012312-001
Transmitter Brow
116-012300-001
Receiver Brow
116-012660-001
Mounting Bracket
116-103922-001
HART Handheld Communicator
116-011824-001
Modbus Program
116-102740-002
Calibration Magnet