6 Parameter Settings and Functions
78
© Copyright Reserved Autonics Co., Ltd.
Setting
Description
OFF
Auto-tuning complete.
ON
Auto-tuning in progress.
Setting
group
Parameter Setting range
Factory
default
Unit
PAR2
AT
OFF
/
ON
OFF
-
Auto-tuning continues to run even if the temperature reading exceeds or falls below the input
range.
When auto-turning is in progress, parameters can only be referenced and not altered.
Auto-tuning is not available in manual control.
6.3.4.2
Auto-tuning mode settings [
PAR3
→
AtT
]
Auto-tuning is available in [
TUN1
] mode (based on SV) or [
TUN2
] mode (based on 70% of SV),
depending on the baseline value used.
Setting
Description
TUN1
Auto-tunes and derives a PID time constant based on set value(SV).
TUN2
Auto-tunes and derives a PID time constant based on 70% of set value(SV).
Setting
group
Parameter Setting range
Factory
default
Unit
PAR3
AtT
TUN1
/
TUN2
TUN1
-
In cooling control mode, [
TUN2
] mode calculates 70% based at 0.
When SV=-100, [
TUN2
] is performed at -70.
Summary of Contents for TK Series
Page 1: ...1 Product Introduction Copyright Reserved Autonics Co Ltd 1 USER MANUAL ...
Page 2: ...1 Product Introduction 2 Copyright Reserved Autonics Co Ltd ...
Page 8: ...1 Product Introduction 8 Copyright Reserved Autonics Co Ltd ...
Page 12: ...1 Product Introduction 12 Copyright Reserved Autonics Co Ltd ...
Page 24: ...1 Product Introduction 24 Copyright Reserved Autonics Co Ltd ...
Page 28: ...3 Dimensions 28 Copyright Reserved Autonics Co Ltd 5 TK4H Series 6 TK4W Series 7 TK4L Series ...
Page 32: ...3 Dimensions 32 Copyright Reserved Autonics Co Ltd ...
Page 36: ...4 Connections 36 Copyright Reserved Autonics Co Ltd ...
Page 41: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 41 5 3 Parameter group ...
Page 42: ...5 Preparation and Startup 42 Copyright Reserved Autonics Co Ltd ...
Page 45: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 45 5 4 2 Parameter 2 group PAR2 ...
Page 46: ...5 Preparation and Startup 46 Copyright Reserved Autonics Co Ltd ...
Page 47: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 47 5 4 3 Parameter 3 group PAR3 ...
Page 49: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 49 5 4 4 Parameter 4 group PAR4 ...
Page 50: ...5 Preparation and Startup 50 Copyright Reserved Autonics Co Ltd ...
Page 51: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 51 ...
Page 52: ...5 Preparation and Startup 52 Copyright Reserved Autonics Co Ltd 5 4 5 Parameter 5 group PAR5 ...
Page 53: ...5 Preparation and Startup Copyright Reserved Autonics Co Ltd 53 ...
Page 54: ...5 Preparation and Startup 54 Copyright Reserved Autonics Co Ltd ...
Page 63: ...6 Parameter Settings and Functions Copyright Reserved Autonics Co Ltd 63 1 Using a Deadband ...
Page 124: ...8 DAQMaster 124 Copyright Reserved Autonics Co Ltd MCT TKU1 V2 3 1703EN ...