H-62
TC Series
※
Mount the product on the panel, fasten bracket by pushing with tools as shown above.
(In case of TC4Y, fasten bolts for bracket.)
TC4S/SP (48×48mm) Series
TC4Y (72×36mm) Series
Other Series
Mounting
※
AC/DC power type has no SSR drive output method [
SSrM
] and supports only ON/OFF
output when selecting
SSR
in control output [
OUT
].
Factory Default
SV setting
Parameter group 1
Parameter group 2
Parameter
Factory default
-
0
Parameter
Factory default
AL1
1250
AL2
AT
OFF
P
01)0
I
0000
D
REST
05)0
HYS
002
Parameter
Factory default
Parameter
Factory default
IN-T
KCA
T
02)0
UNIT
?C
AL-1
AMiA
IN-B
0000
MAvF
00)1
AL-2
AM@A
L-SV
-050
AHYS
0001
H-SV
1200
LBaT
0000
O-FT
HEAT
LBaB
002
C-MD
PID
DI-K
STOP
OUT
RLY
ErMV
00)0
SSrM
STND
LOC
OFF
Input Sensor And Temperature Range [
IN-T
]
Input sensor
Display
Input range (
℃
)
Input range (
℉
)
Thermocouple
K (CA)
KCA
-50 to 1200
-58 to 2192
J (IC)
JIC
-30 to 500
-22 to 932
L (IC)
LIC
-40 to 800
-40 to 1472
RTD
DPt100Ω
DPtH
-100 to 400
-148 to 752
DPtL
-100.0 to 400.0
-148.0 to 752.0
Cu50Ω
CUsH
-50 to 200
-58 to 392
CUsL
-50.0 to 200.0
-58.0 to 392.0