-|Transparent Guide|-

Manual

For the detailed information about communication, etc., please refer to the manuals,

and be sure to follow cautions written in the technical descriptions.

Visit Autonics website to download manuals.

Product Components

• Product ×1

• Insulating barrier ×4

• 11-pin connector

 ×1

DAQMaster

• 

DAQMaster is comprehensive device management program. It is available for 

parameter setting, monitoring.

• 

Visit Autonics website to download the manual and the program.

Dimensions

• 

Unit: mm, For the detailed drawings, follow the Autonics website.

  

■ Rated load current 25 / 35 / 50 A

227

203.1

261

4 - Ø 6

6.8

243.6

200

21.8

68

92.2

105

80

80

  

Rated load current 70 A

250

203.1

261

4 - Ø 6

6.8

266.6

200

21.8

25

68

92.2

105

80

80

  

■ Rated load current 100 / 150 A

233.2

326.5

4 - Ø 6.5

270

210

30

140

158

170

80

80

25

Ordering Information

This is only for reference.
For selecting the specified model, follow the Autonics website.  

SPR 3

-

❶ ❷ ❸ ❹ ❺

❶ Rated load voltage

1: 110 VACᜠ

2: 220 VACᜠ

3: 380 VACᜠ

4: 440 VACᜠ

❹ Feedback control

N: Normal control

F:  Normal, feedback control (constant 

current / constant voltage / constant 

power) 

❷ Rated load current

Number: Rated load current (unit: A)

❺ Fuse

N: None

F: Supports fuse

❸ Option output

N: Alarm output

T:  Alarm RS485 comm. output

Cautions during Installation

While supplying power to the load or right after turning off the power of the load, 

do not touch the body and heatsink. 

Failure to follow this instruction may result in a burn due to the high temperature.

High Temperature Caution

  

■ Mount space

100

100

4 - Ø 6

50

Panel

• 

When installing multiple power controllers, 
keep space between power controllers for heat 
radiation.

 

Horizontal: ≥ 50 mm, vertical:  ≥ 100 mm

Unit Descriptions

U

V

W

R

S

T

01

08

09

09

07

05

03

02

12

13

13

10

11

06

04

14

15

01. Bracket 

[except rated load current 100 / 150 A model]

02. Indicator

Indicator

Function

RUN

Operation indicator (green)

Turns on in the RUN mode.

MAN

Manual control indicator (green) Turns on when adjusting load output in 

the manual control mode.

ALM

Alarm indicator (red)

Flashes in alarming status.

OUT

Output indicator (red)

Turns on when load control outputs.

03. Display part

RUN mode: Displays depending the front display setting

Setting mode: Displays parameter and setting value

04.   Unit indicator (V, A)

Dependent on the display setting.

Display setting

V

A

Resistance and input  OFF

OFF

Voltage 

ON

OFF

Current

OFF

ON

Power

ON

ON

05.  [MODE] key

Enters parameter group, returns to RUN 

mode, moves parameters, and saves the 

setting value. 

06. [◀], [▼], [▲] key

Enters SV setting mode and move digits.

07. Output limit adjuster (OUT ADJ)

Limits output from 0 to 100%.

08.  Control input / 

 

comm. output terminal 

 

(11-pin connector terminal)  

09. Terminal  protection cover 

10. R, S, T load input terminal

11. Alarm output / power input terminal

12. U, V, W load output terminal

13. Cooling fan 

 

[Rated load current 70 / 100 / 150 A model]

 

14. Heatsink

Rated load current 100 / 150 A models have 

left / right  mounting holes. 

15. Bolt for grounding (M4)

Insulating Barrier

It is recommended to use the included interphase barriers for insulation between 
phases and reduce influence from conductive material. 

• 

Unit: mm, For the detailed drawings, 
follow the Autonics website.

55

40

2.5

3.8

1.5

42.5

• 

With the insulating barrier

A

B

C

Rated load current A

B

C

25 / 35 / 50 A 

30

28.2

300

70 A

30

28.2

300

100 / 150 A

40.5 50

370

Summary of Contents for SPR3 Series

Page 1: ...k Connections before wiring Failure to follow this instruction may result in fire 06 Do not disassemble or modify the unit Failure to follow this instruction may result in fire or electric shock Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or product damage 02 Use ...

Page 2: ...multiple power controllers keep space between power controllers for heat radiation Horizontal 50 mm vertical 100 mm UnitDescriptions U V W R S T 01 08 09 09 07 05 03 02 12 13 13 10 11 06 04 14 15 01 Bracket except rated load current 100 150 A model 02 Indicator Indicator Function RUN Operation indicator green Turns on in the RUN mode MAN Manual control indicator green Turns on when adjusting load ...

Page 3: ...rrent feedback control within 3 F S of rated load current Constant voltage feedback control within 3 F S of rated load voltage Constant power feedback control within 3 F S of rated load power Power supply 100 240 VACᜠ 10 50 60 Hz Min load current 1 A Power consumption Rated load current 25 35 50 A 14 VA Rated load current 70 A 22 VA Rated load current 100 150 A 32 VA Insulation resistance 200 MΩ 5...

Page 4: ... value U A Feedback control model 0 to rated current range A M1 6 V phase load current value V A M1 7 W phase load current value W A M1 8 Load power value L W Feedback control model 0 to rated Power range kW M1 9 Resistance value percentage L R Feedback control model 0 to 100 Displays the present resistance as percentage compared to the set resistance of full load auto recognition M1 10 Heatsink t...

Page 5: ... G Y Y G G Y Y G G Y Y H H Z Z H H Z Z H H Z Z H H Z Z Function Output limit OUT ADJ Control input output limit setting output It controls the power supplied into the load Although control input is 100 the output is the 50 which is proportioned with OUT ADJ It is not available at ON OFF control method SV 50 SV 100 Output Control input Output high low limit value This function is to limit output ra...