background image

-|Transparent Guide|-

Alarm

• 

Supported alarms are different depending on the model.

• 

When several alarms occur at same time, the highest priority error is displayed based 
on priority.

Priority

Type

Display

Operation

Alarm release

Model

Alarm

Output

1

SCR error

SCR

•  Error 

display 

flashes.

•  Alarm 

indicator 

(ALM) 

flashes.

•  Alarm 

output 

turns ON

Output 

stops.

 

(SCR OFF)

• 

Re-supply 

power. 

• 

RESET input

•  Switch to stop 

(STOP) mode.

Feedback control

2

Over 

current

O-C 

Feedback control

4

Heatsink 

over heat

TEM

Normal / 

Feedback control

5

Over 

voltage

O-V

Feedback control

3

Fuse 

break

FUS

Automatically 

cleared when 

returning within 

the setting range

Normal / 

Feedback control

6

Heater 

break

H-B

Normal 

operation

Feedback control

•  SCR error alarm

 

Even though output is 0%, if the current of 10% or more of the rated load current flows for 

over 3 sec continuously, SCR error alarm occurs.

• 

Over current alarm 

 

This function protects the load from over current. If the current flows over the P2-7 over 

current alarm value and P2-8 over current alarm delay time, over current alarm occurs.

• Heatsink over heat alarm 

When the temperature of a heatsink is over 85 ℃, heatsink over heat alarm occurs.

• 

Over voltage alarm

  

This function protects the load from over voltage. If the current flows over the P2-9 over 

voltage alarm value and P2-10 over voltage alarm delay time, over voltage alarm occurs. 

• Fuse break alarm

 

When breaking fuse, not suppling load power, breaking load (single load), fuse brake alarm 

occurs. In the case of normal control model, real-time fuse break alarm is not available during 

output, and fuse break alarm operates at 0% output such as RESET.

• Heater break alarm

 

Comparing the full load resistance value and the current load resistance value, if the current 

load resistivity is maintained under the P2-12 heater break alarm value for over 3 sec 

continuously, heater break alarm occurs. This alarm operates when control output is over 

10% and load current is over 10% of the rated current. Output does not stop and operates 

normally.

 

Current load resistance (%) =  

Full load resistance value × 100

Current load resistance value

Mode Setting

RUN

[MODE] 

Monitoring group

[MODE] 3 sec

RUN

[MODE] 2 sec

→ Parameter 1 group

[MODE] 3 sec

[MODE] 4 sec

→ Parameter 2 group

[MODE] 3 sec

[◀ + ▲ + ▼] 5 sec

Parameter reset

[MODE]

6 - 9 terminal 

external contact

RUN / STOP

Auto

7 - 9 terminal 

external contact

Auto / Manual 

control

Auto

[▲ + ▼] 2 sec or

8 - 9 terminal

Reset 

 01)

Auto

 01)  In the event of system anomalies and alarms, RESET input restarts the power controller. (parameters are not 

reset.)

Parameter Setting

• 

Some parameters are activated / deactivated depending on the model or setting of 

other parameters. Refer to the description of each parameter.

• 

If any key is not entered for 30 sec in each parameter, it returns to RUN mode.

• 

[MODE] key: Saves current setting value and moves to the next parameter.

 

[◀] key: Changes setting digits.

 

[▲], [▼] key: Changes setting values.

  

■ Monitoring group

Parameter

Display Display range

M1-1

Monitoring value

IN

0 to 100%

M1-2 U-V line load voltage value

U-V

[Feedback control model]

0 to rated voltage range, V

M1-3

V-W line load voltage value

V-W

M1-4 W-U line load voltage value

W-U

M1-5 U-phase load current value

U-A

[Feedback control model]

0 to rated current range, A

M1-6

V-phase load current value

V-A

M1-7 W-phase load current value

W-A

M1-8

Load power value

L-W

[Feedback control model]

0 to rated Power range, kW

M1-9

Resistance value percentage

L-R

[Feedback control model]

0 to 100%

• 

Displays the present resistance as percentage 

compared to the set resistance of full load auto 

recognition.

M1-10

Heatsink temp.

TMP

0 to 100 ℃

M1-11

Power supply frequency

FRQ

50, 60 Hz

Parameter

Display

Default

Setting range

P2-1

Control input

 01)

INT

420

420: DC 4 - 20 mA

1-5: 1 - 5 VDCᜡ

512: 5 - 12 VDCᜡ

ONF: ON / OFF contact

COM: RS485 communication

P2-2

Control method

C-M

PA

*[Feedback control model]

Set

Control method

PA

Phase 

control

Normal

V-F*

Constant voltage feedback

C-F*

Constant current feedback

W-F*

Constant power feedback

F-C

Cycle 

control

Fixed cycle

ONF

ON / OFF control

P2-3

Manual control (MAN) 

output limit method

 

01)

MAN

I_R

I_R: Internal adjuster

E_R: External adjuster

E_I: Internal / external adjuster

P2-4

Input correction

 

01)

INB

)0

-99 to 99%

P2-5

Input slope correction

 

01)

SPN

)0

P2-6

Front display

DIS

IN

*[Feedback control model]

IN: 

Resistance and input

U-V*: U-V line 

load voltage

V-W*: V-W line 

load voltage

W-U*: W-U line 

load voltage

U-A*: U-phase

 load current

V-A*: V-phase

 load current

W-A*: W-phase

 load current

L-W*: 

Load power

P2-7

Over current alarm 

value

OCV

120

[Feedback control model]

0 to 120%

P2-8

Over current alarm 

delay time

OCT

5

[Feedback control model]

0 to 100 sec

P2-9

Over voltage alarm 

value

OVV

120

[Feedback control model]

0 to 120%

P2-10 Over voltage alarm 

delay time

OVT

5

[Feedback control model]

0 to 100 sec

P2-11 Load resistance value 

auto recognition

F-L

OFF

[Feedback control model]

OFF, ON

• 

It executes 100% control output for 3 sec 

and the load resistance value recognized 

automatically as the initial set when the 

function is ON. 

P2-12 Heater break alarm 

value

HBV

10

[Feedback control model]

10 to 100%, OFF

P2-13 Comm. address

ADR

01

[RS485 communication output model]

01 to 99

P2-14 Comm. speed 

BPS

96

[RS485 communication output model]

24, 48, 96, 192, 384 bps (× 100)

P2-15 Comm. parity bit

PRT

NON

[RS485 communication output model]

NON, EVE, ODD

P2-16 Comm. stop bit

STP

2

[RS485 communication output model]

1, 2 bit

P2-17 Comm. response time

RwT

20

[RS485 communication output model]

5 to 99 ms

P2-18 Comm. write

CmW

EnA

[RS485 communication output model]

EN.A: Enable, DS.A: Disable

P2-19 Lock

LOC

OFF

OFF 

LC1: Locks parameter 1 group 

LC2: Locks parameter 2 group

P2-20

Parameter reset

INI

NO

NO, YES

 01)  Set the below parameters available depends on the control input.

 

Type

Control input

Display

Input 

correction

Input slope 

correction

Output 

slope 

Monitoring 

value

Auto 

control

(AUTO)

Current

DC 4 - 20 mA

INT

420

The last 

control 

input value

0 to 100%

Voltage

1 - 5 VDCᜡ

1-5

Pulse 

voltage

5 - 12 VDCᜡ

512

×

×

No-voltage ON / OFF contact

ONF ×

×

RS485 communication

COM

×

×

×

Manual 

control

(MAN)

Output 

limit

Internal adjuster

MAN

I_R

×

×

×

External adjuster

E_R

Internal / 

external adjuster

E_I

Parameter

Display

Default

Setting range

P1-1

SOFT START time

S-T

3

0 to 100 sec

P1-2

SOFT UP time

U-T

3

P1-3

SOFT DOWN time

D-T

3

P1-4

Output low-limit 

value

L-L

0

0 ≤ L-L ≤ H-L ≤ 100 %

P1-5

Output high-limit 

value

H-L

100

P1-6

Output slope

 

01)

SLP

100

0 to 100%

• 

In case of auto control (AUTO), set the output 

slop limit proportional to control input for limit 

load power.

  

■ Parameter 1 group 

  

■ Parameter 2 group 

Summary of Contents for SPR3 Series

Page 1: ...k Connections before wiring Failure to follow this instruction may result in fire 06 Do not disassemble or modify the unit Failure to follow this instruction may result in fire or electric shock Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or product damage 02 Use ...

Page 2: ...multiple power controllers keep space between power controllers for heat radiation Horizontal 50 mm vertical 100 mm UnitDescriptions U V W R S T 01 08 09 09 07 05 03 02 12 13 13 10 11 06 04 14 15 01 Bracket except rated load current 100 150 A model 02 Indicator Indicator Function RUN Operation indicator green Turns on in the RUN mode MAN Manual control indicator green Turns on when adjusting load ...

Page 3: ...rrent feedback control within 3 F S of rated load current Constant voltage feedback control within 3 F S of rated load voltage Constant power feedback control within 3 F S of rated load power Power supply 100 240 VACᜠ 10 50 60 Hz Min load current 1 A Power consumption Rated load current 25 35 50 A 14 VA Rated load current 70 A 22 VA Rated load current 100 150 A 32 VA Insulation resistance 200 MΩ 5...

Page 4: ... value U A Feedback control model 0 to rated current range A M1 6 V phase load current value V A M1 7 W phase load current value W A M1 8 Load power value L W Feedback control model 0 to rated Power range kW M1 9 Resistance value percentage L R Feedback control model 0 to 100 Displays the present resistance as percentage compared to the set resistance of full load auto recognition M1 10 Heatsink t...

Page 5: ... G Y Y G G Y Y G G Y Y H H Z Z H H Z Z H H Z Z H H Z Z Function Output limit OUT ADJ Control input output limit setting output It controls the power supplied into the load Although control input is 100 the output is the 50 which is proportioned with OUT ADJ It is not available at ON OFF control method SV 50 SV 100 Output Control input Output high low limit value This function is to limit output ra...

Reviews: