-|Transparent Guide|-
Alarm
•
Supported alarms are different depending on the model.
•
When several alarms occur at same time, the highest priority error is displayed based
on priority.
Priority
Type
Display
Operation
Alarm release
Model
Alarm
Output
1
SCR error
SCR
• Error
display
flashes.
• Alarm
indicator
(ALM)
flashes.
• Alarm
output
turns ON
Output
stops.
(SCR OFF)
•
Re-supply
power.
•
RESET input
• Switch to stop
(STOP) mode.
Feedback control
2
Over
current
O-C
Feedback control
4
Heatsink
over heat
TEM
Normal /
Feedback control
5
Over
voltage
O-V
Feedback control
3
Fuse
break
FUS
Automatically
cleared when
returning within
the setting range
Normal /
Feedback control
6
Heater
break
H-B
Normal
operation
Feedback control
• SCR error alarm
Even though output is 0%, if the current of 10% or more of the rated load current flows for
over 3 sec continuously, SCR error alarm occurs.
•
Over current alarm
This function protects the load from over current. If the current flows over the P2-7 over
current alarm value and P2-8 over current alarm delay time, over current alarm occurs.
• Heatsink over heat alarm
When the temperature of a heatsink is over 85 ℃, heatsink over heat alarm occurs.
•
Over voltage alarm
This function protects the load from over voltage. If the current flows over the P2-9 over
voltage alarm value and P2-10 over voltage alarm delay time, over voltage alarm occurs.
• Fuse break alarm
When breaking fuse, not suppling load power, breaking load (single load), fuse brake alarm
occurs. In the case of normal control model, real-time fuse break alarm is not available during
output, and fuse break alarm operates at 0% output such as RESET.
• Heater break alarm
Comparing the full load resistance value and the current load resistance value, if the current
load resistivity is maintained under the P2-12 heater break alarm value for over 3 sec
continuously, heater break alarm occurs. This alarm operates when control output is over
10% and load current is over 10% of the rated current. Output does not stop and operates
normally.
Current load resistance (%) =
Full load resistance value × 100
Current load resistance value
Mode Setting
RUN
[MODE]
→
Monitoring group
[MODE] 3 sec
→
RUN
[MODE] 2 sec
→ Parameter 1 group
[MODE] 3 sec
→
[MODE] 4 sec
→ Parameter 2 group
[MODE] 3 sec
→
[◀ + ▲ + ▼] 5 sec
→
Parameter reset
[MODE]
→
6 - 9 terminal
external contact
→
RUN / STOP
Auto
→
7 - 9 terminal
external contact
→
Auto / Manual
control
Auto
→
[▲ + ▼] 2 sec or
8 - 9 terminal
→
Reset
01)
Auto
→
01) In the event of system anomalies and alarms, RESET input restarts the power controller. (parameters are not
reset.)
Parameter Setting
•
Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
•
If any key is not entered for 30 sec in each parameter, it returns to RUN mode.
•
[MODE] key: Saves current setting value and moves to the next parameter.
[◀] key: Changes setting digits.
[▲], [▼] key: Changes setting values.
■ Monitoring group
Parameter
Display Display range
M1-1
Monitoring value
IN
0 to 100%
M1-2 U-V line load voltage value
U-V
[Feedback control model]
0 to rated voltage range, V
M1-3
V-W line load voltage value
V-W
M1-4 W-U line load voltage value
W-U
M1-5 U-phase load current value
U-A
[Feedback control model]
0 to rated current range, A
M1-6
V-phase load current value
V-A
M1-7 W-phase load current value
W-A
M1-8
Load power value
L-W
[Feedback control model]
0 to rated Power range, kW
M1-9
Resistance value percentage
L-R
[Feedback control model]
0 to 100%
•
Displays the present resistance as percentage
compared to the set resistance of full load auto
recognition.
M1-10
Heatsink temp.
TMP
0 to 100 ℃
M1-11
Power supply frequency
FRQ
50, 60 Hz
Parameter
Display
Default
Setting range
P2-1
Control input
01)
INT
420
420: DC 4 - 20 mA
1-5: 1 - 5 VDCᜡ
512: 5 - 12 VDCᜡ
ONF: ON / OFF contact
COM: RS485 communication
P2-2
Control method
C-M
PA
*[Feedback control model]
Set
Control method
PA
Phase
control
Normal
V-F*
Constant voltage feedback
C-F*
Constant current feedback
W-F*
Constant power feedback
F-C
Cycle
control
Fixed cycle
ONF
ON / OFF control
P2-3
Manual control (MAN)
output limit method
01)
MAN
I_R
I_R: Internal adjuster
E_R: External adjuster
E_I: Internal / external adjuster
P2-4
Input correction
01)
INB
)0
-99 to 99%
P2-5
Input slope correction
01)
SPN
)0
P2-6
Front display
DIS
IN
*[Feedback control model]
IN:
Resistance and input
U-V*: U-V line
load voltage
V-W*: V-W line
load voltage
W-U*: W-U line
load voltage
U-A*: U-phase
load current
V-A*: V-phase
load current
W-A*: W-phase
load current
L-W*:
Load power
P2-7
Over current alarm
value
OCV
120
[Feedback control model]
0 to 120%
P2-8
Over current alarm
delay time
OCT
5
[Feedback control model]
0 to 100 sec
P2-9
Over voltage alarm
value
OVV
120
[Feedback control model]
0 to 120%
P2-10 Over voltage alarm
delay time
OVT
5
[Feedback control model]
0 to 100 sec
P2-11 Load resistance value
auto recognition
F-L
OFF
[Feedback control model]
OFF, ON
•
It executes 100% control output for 3 sec
and the load resistance value recognized
automatically as the initial set when the
function is ON.
P2-12 Heater break alarm
value
HBV
10
[Feedback control model]
10 to 100%, OFF
P2-13 Comm. address
ADR
01
[RS485 communication output model]
01 to 99
P2-14 Comm. speed
BPS
96
[RS485 communication output model]
24, 48, 96, 192, 384 bps (× 100)
P2-15 Comm. parity bit
PRT
NON
[RS485 communication output model]
NON, EVE, ODD
P2-16 Comm. stop bit
STP
2
[RS485 communication output model]
1, 2 bit
P2-17 Comm. response time
RwT
20
[RS485 communication output model]
5 to 99 ms
P2-18 Comm. write
CmW
EnA
[RS485 communication output model]
EN.A: Enable, DS.A: Disable
P2-19 Lock
LOC
OFF
OFF
LC1: Locks parameter 1 group
LC2: Locks parameter 2 group
P2-20
Parameter reset
INI
NO
NO, YES
01) Set the below parameters available depends on the control input.
Type
Control input
Display
Input
correction
Input slope
correction
Output
slope
Monitoring
value
Auto
control
(AUTO)
Current
DC 4 - 20 mA
INT
420
○
○
○
The last
control
input value
0 to 100%
Voltage
1 - 5 VDCᜡ
1-5
○
○
○
Pulse
voltage
5 - 12 VDCᜡ
512
×
×
○
No-voltage ON / OFF contact
ONF ×
×
○
RS485 communication
COM
×
×
×
Manual
control
(MAN)
Output
limit
Internal adjuster
MAN
I_R
×
×
×
External adjuster
E_R
Internal /
external adjuster
E_I
Parameter
Display
Default
Setting range
P1-1
SOFT START time
S-T
3
0 to 100 sec
P1-2
SOFT UP time
U-T
3
P1-3
SOFT DOWN time
D-T
3
P1-4
Output low-limit
value
L-L
0
0 ≤ L-L ≤ H-L ≤ 100 %
P1-5
Output high-limit
value
H-L
100
P1-6
Output slope
01)
SLP
100
0 to 100%
•
In case of auto control (AUTO), set the output
slop limit proportional to control input for limit
load power.
■ Parameter 1 group
■ Parameter 2 group