-|Transparent Guide|-
Output Mode
Output mode is available to set. (Indicator does not support output mode.)
OFF:
ON:
H:
hysteresis
■ S (Standard) output
mode
■ H (High) output
mode
• Comparative value setting condition:
individual o
ut
put operation regardless of
size or order of set comparative values
• Comparative value setting condition:
individual o
ut
put operation regardless of
size or order of set comparative values
HH output: Display value
≥ Comparative value HH
H output:
Display value
≥ Comparative value H
L output:
Display value
≤ Comparative value L
LL output: Display value
≤ Comparative value LL
GO output: No HH, H, L, LL output
Comp
ar
ative
value
HH
H
L
LL
HH
H
GO
L
LL
Output
H
H
H
H
HH output: Display value
≥ Comparative value HH
H output:
Display value
≥ Comparative value H
L output:
Display value
≥ Comparative value L
LL output: Display value
≥ Comparative value LL
GO output: No HH, H, L, LL output
Comp
ar
ative
value
Output
HH
H
L
LL
HH
H
L
LL
GO
H
H
H
H
■ L (Low) output
mode
■ B (Block) output
mode
• Comparative value setting condition:
individual o
ut
put operation regardless of
size or order of set comparative values
• Comparative value setting condition:
LL<L<H<HH
HH output: Display value
≤ Comparative value HH
H output:
Display value
≤ Comparative value H
L output:
Display value
≤ Comparative value L
LL output: Display value
≤ Comparative value LL
GO output: No HH, H, L, LL output
Comp
ar
ative
value
Output
HH
H
L
LL
HH
H
L
LL
GO
H
H
H
H
HH output: Display value
≥ Comparative value HH
H output: Comparative value HH > Display value ≥
Comparative value H
L output: Comparative value LL < Display value ≤
Comparative value L
LL output: Display value
≤ Comparative value LL
GO output: No HH, H, L, LL output
Comp
ar
ative
value
Output
HH
H
L
LL
HH
H
GO
L
LL
H
H
H
H
■ I (One-shot) output
mode
■ F (Deflection) output
mode
• Comparative value setting condition:
individual o
ut
put operation regardless of
size or order of set comparative values
• One-shot output time: 0.3 sec (fixed)
• No GO output.
• No hysteresis.
HH output: Display value
≥ Comparative value HH
H output: Comparative value HH > Display value ≥
Comparative value H
L output: Comparative value H > Display value ≥
Comparative value L
LL output: Comparative value L > Display value ≥
Comparative value LL
0.3s
0.3s
0.3s
0.3s
HH
H
L
LL
HH
H
GO
L
LL
Comp
ar
ative
value
Output
• Transmits outputs when the saved
setting value exceeds H deviation or L
deviation.
• Comparative value setting
: Based on the set value, set the H / L
deviation in the P0-2, P2-7 H
comparative value and P0-3, P2-8 L
comparative value parameters.
( The set deviation value is saved during
Power OFF until it is re-set.)
• Comparative value setting range
: 0.0001 to 99999
The setting range is different according
to the P2-2 Decimal point position of
display value setting.
E.g.)
In case of P2-2 Decimal point
position of display value = 0000.0,
setting range = 0.1 to 9999.9
• Saving setting value: [MODE] + [▲]
• Checking setting value: [▲]
• No HH, GO, LL output.
• The deviation can be set to “0” but the
actual operation will be the same as “1”.
01)
02)
(Max.)H deviation
SV
(Min.) L deviation
Power
Save SV
L deviation
output
H deviation
output
Save SV
01) When P1-6 Delay monitoring = F.DEFY is set, there is
no output.
02) The graph is assuming that there is a saved setting
value prior to the setting value save point. The actual
output position may be different.
Operation Mode
■ F1: frequency / revolutions / speed
Measures the frequency of input A and displays the calculated frequency, revolutions,
and speed.
Frequency (Hz)
= f × α
(α = 1 [sec])
Revolutions (rpm) = f × α
(α = 60 [sec])
Speed (m / min)
= f × α
(α = 60 L [sec])
• L: travel distance of conveyor belt of 1
cycle [m]
• α: prescale value
(For multiple objects, α = 60L / N)
Display value Display
unit
α
Frequency
Hz
1
kHz
0.001
Revolutions
rps
1
rpm (default)
60
Speed
mm / sec
1,000 L
cm / sec
100 L
m / sec
1 L
m / min
60 L
km / hour
3.6 L
MP5
MP5
Encoder
t1
t2
t3
t4
t5
t6
Input A
Hold
Display
1 × α
t1
1 × α
t2
1 × α
t5
1 × α
t3
1 × α
t6
■
F2:
passing speed
Displays the passing speed between input A ON and input B ON.
Passing speed (V) = f × α
(α = L [m])
• f : reciprocal of time [sec] between input A
(sensor) ON and input B( sensor) ON.
• L: distance between input A (sensor) and
input B (sensor) [m]
• α: prescale value
Display value Display
unit
α
Passing speed
mm / sec
1,000 L
cm / sec
100 L
m / sec (default) 1 L
m / min
60 L
km / hour
3.6 L
Sensor A
Sensor B
MP5
• ta: Return time (≥ 20 ms)
Input A
Input B
Hold
Display
t1
ta
t2
t3
t4
t5
t6
t7
1 × α
t1
1 × α
t2
1 × α
t3
1 × α
t6
1 × α
t4
1 × α
t7
■
F3: cycle
Displays the measured time from input A ON to the next ON.
Cycle (T)
= t
• t: measurement time [sec]
Display value Display
unit
Cycle
SEC
MIN
999.99 s
(default)
999.99 m
9999.9 s
9999.9 m
99 m 59.9 s
99 h 59.9 m
9 h 59 m 59 s
999 h 59 m
99999 s
99999 m
Photoelectric
sensor
MP5
Input A
t1
t1
t2
t2
t3
t5
t6
t3
t4
t5
t6
Hold
Display
■
F4:
passing time
Measure the time from input A ON to the next ON, and displays the passing time of the
arbitrary distance.
Passing time [sec] = t × α
(α=
L [m]
Distance advanced in 1 pulse cycle [m] )
• t: measurement time [sec]
• L: arb
i
trary distance [m]
• α: prescale value
Display value Display
unit
Passing time
SEC
MIN
999.99 s
(default)
999.99 m
9999.9 s
9999.9 m
99 m 59.9 s
99 h 59.9 m
9 h 59 m 59 s
999 h 59 m
99999 s
99999 m
MP5
L : Dis
tanc
e [m]
Input A
t1
t1 × α t2 × α
t5 × α
t2
t3 × α
t6 × α
t3
t4
t5
t6
Hold
Display