-|Transparent Guide|-
DRW160458AJ
Multi Pulse Meters
MP5S / MP5Y / MP5W Series
PRODUCT MANUAL
For your safety, read and follow the considerations written in the instruction
manual, other manuals and Autonics website.
The specifications, dimensions, etc. are subject to change without notice for product
improvement. Some models may be discontinued without notice.
Features
• 16 operation modes
- Frequency / revolutions / speed, passing speed, cycle, passing time, time interval
- Time differential, absolute ratio, error ratio, density, error, length measurement 1 / 2,
interval
- Accumulation, addition / subtraction (individual input),
addition / subtraction (phase difference input)
• Various output models
- Relay triple / quintuple output, NPN / PNP open collector quintuple output
- BCD Dynamic output, PV transmission output (current output)
- RS485 communication output (Modbus RTU)
• Various function
- Prescale, delay monitoring, hysteresis, auto-zero, parameter lock, data bank (MP5W
only)
• Display range: -19999 to 99999
• Various display units
ᜢ ᜧ ᜫ
Safety Considerations
• Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
• symbol indicates caution due to special circumstances in which hazards may occur.
Warning
Failure to follow instructions may result in serious injury or death.
01. Fail-safe device must be installed when using the unit with machinery that
may cause serious injury or substantial economic loss. (e.g. nuclear power
control, medical equipment, ships, vehicles, railways, aircraft, combustion
apparatus, safety equipment, crime / disaster prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or
fire.
02. Do not use the unit in the place where flammable / explosive / corrosive gas,
high humidity, direct sunlight, radiant heat, vibration, impact, or salinity
may be present.
Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use.
Failure to follow this instruction may result in fire or electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power
source.
Failure to follow this instruction may result in fire or electric shock.
05. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Caution
Failure to follow instructions may result in injury or product damage.
01. When connecting the power / measurement input and relay output, use
AWG 24 (0.20 mm
2
) to AWG 15 (1.65 mm
2
) cable and tighten the terminal
screw with a tightening torque of 0.98 to 1.18 N m.
Use the wiring suitable for the load current capacity.
Failure to follow this instruction may result in fire or malfunction due to contact
failure.
02. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage.
03. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which from
flowing into the unit.
Failure to follow this instruction may result in fire or product damage.
Cautions during Use
• Follow instructions in ‘Cautions during Use’.
Otherwise, it may cause unexpected accidents.
• Power supply should be insulated and limited voltage / current or Class 2, SELV power
supply device.
• Install a power switch or circuit breaker in the easily accessible place for supplying or
disconnecting the power.
• Use twisted pair wire for communication line.
• Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor
at power line and shielded wire at input signal line. Do not use near the equipment
which generates strong magnetic force or high frequency noise.
• This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude max. 2,000 m
- Pollution degree 2
- Installation category II