Parameter
Display
Default
Setting range
Display
condition
P0-1
HH
comparative
value
PStHH
99999
[
Comparative value output model
01)
]
Operation mode Setting range
F1, F2, F7, F9, F11,
F12, F13, F16
0 to 99999
F3, F4, F5, F6
0.01 to
time setting range
F8, F10, F14, F15
-19999 to 99999
• Varies according to P1-1 Input operation
mode and P2-2 Decimal point position of
display value
• Same parameters at parameter 2 group
are linked.
P1-4 Output
mode:
except F
P0-2 H comparative
value
PSt H
99999
-
P0-3 L comparative
value
PSt L
00000
-
P0-4 LL comparative
value
PStLL
00000
P1-4 Output
mode:
except F
P0-5
Max.
monitoring
value
hPEK
99999
• Reset (PV): [◀] key for over 2 sec
P1-1 Input
operation
mode:
except F13,
F16
P0-6
Min.
monitoring
value
lPEK
`9999
01)
Parameter
Comparative value output model
Q
uintuple
Triple
HH comparative value
○
-
H comparative value
○
○
L comparative value
○
○
LL comparative value
○
-
RUN
[MODE]
→
Parameter 0
group
[MODE]
→
RUN
[MODE] 2 sec
→
Parameter
group
01)
[MODE] 3 sec
→
01) Press [▲], [▼] key or [MODE] key for 1.5 sec after entering parameter: select parameter groups.
Mode Setting
Parameter
Display
Default
Setting range
Display
condition
P1-1
Input
operation
mode
MODE
F1
F1 to F16
-
P1-2 Input A
sensor type
IN-A
NPnhF
NPN.H.F : NPN non-contact input1
NPN.M.F : NPN non-contact input2
NPN.L.F : NPN contact input
PNP.H.F : PNP non-contact input1
PNP.M.F : PNP non-contact input2
PNP.L.F : PNP contact input
-
P1-3 Input B
sensor type
IN-B
NPnhF
P1-1 Input
operation
mode:
F2, F6 to 14,
F16
01)
P1-4 Output mode
OUT-T
STARD
[
Comparative value output model]
STARD : S (Standard)
OUT-H : H (High)
OUT-L : L (Low)
OUT-B : B (Block)
OUT-I : I (One-shot)
OUT-F : F (Deflection) *
P1-1 Input
operation
mode:
except F13
&
* P1-1 Input
operation
mode:
except F16
P1-5 Output
hysteresis
HYS
0001
[
Comparative value output model]
0000 to 9999
• Varies according to P2-2 Decimal point
position of display value
P1-1 Input
operation
mode:
F1, F7 to 10
P1-6 Delay
monitoring
GUARD
fDEFY
[
Comparative value output model]
F.DEFY: LL, L comparative output limit *
STAR.T: Start compensation timer
02)
P1-1 Input
operation
mode:
F1 to 12
*P1-4 Output
mode: S, B, F
P1-7
Start
compensation
timer
STArT
)0
[
Comparative value output model]
0.0 to 99.9 sec
P1-6 Delay
monitoring:
STAR.T
P1-8 Input A auto-
zero time
AUToA
999(9
0.1 to 9999.9 sec
P1-1 Input
operation
mode: F1, F4,
F7 to 10
P1-9 Input B auto-
zero time
AUToB
999(9
P1-1 Input
operation
mode:
F7 to 10
P1-10 Memory
retention
MEMO
OFF
OFF, ON
P1-1 Input
operation
mode:
F13 to 16
01) In case of P1-1 Input operation mode F15, input B sensor type is not displayed and IN-B setting is same as IN-A.
02) [▲] key: Entering compensation time setting
■
Parameter 1
group
Parameter Setting
• Some parameters are activated / deactivated depending on the model or setting of
other parameters. Refer to the description of each parameter.
• The parameter and setting value are cross-displayed on the display part.
• If any key is not entered for 60 sec in each parameter, it returns to RUN mode.
• [MODE] key: Saves current setting value and moves to the next parameter.
[◀] key: Checks fixed value / Changes setting digits.
[▲], [▼] key: Changes setting values.
■
Parameter 0
group
Parameter
Display
Default
Setting range
Display
condition
P2-1 Data bank
pBANK
1
[MP5W model]
1, 2
-
P2-2
Decimal
point
position of
display value
DOT
00000
00000, 0000.0, 000.00, 00.000, 0.0000
P1-1 Input
operation
mode:
F1 to 2,
F7 to 16
P2-3 Time unit
01)
tUNT
tSEC
T.SEC, T.MIN
P1-1 Input
operation
mode:
F3 to 6
P2-4 Time range
(unit: sec)
01)
tSEC
99(99
999.99: 999.99 s
9999.9: 9999.9 s
99.59.9: 99 m 59.9 s
9.59.59: 9 h 59 m 59 s
99999: 99999 s
P2-5 Time range
(unit: min)
01)
tMIN
99(99
999.99: 999.99 m
9999.9: 9999.9 m
99.59.9: 99 h 59.9 m
9.59.59: 999 h 59 m
99999: 99999 m
P2-6
HH
comparative
value
PStHH
99999
[
Comparative value output model]
linked with parameter 0 group parameters
P1-4 Output
mode:
except F
P2-7 H comparative
value
PSt H
99999
-
P2-8 L comparative
value
PSt L
00000
-
P2-9 LL comparative
value
PStLL
00000
P1-4 Output
mode:
except F
P2-10
Input A
prescale
mantissa (x)
PScaH
^0000
0.0001 to 9.9999
P1-1 Input
operation
mode:
F1 to 2,
F4,
F7 to 16
P2-11
Input A
prescale
exponent (y)
PScaY
10 01
10 - 9 (10
-9
) to 10 09 (10
9
)
P2-12
Input B
prescale
mantissa (x)
PScbH
^0000
0.0001 to 9.9999
P1-1 Input
operation
mode:
F7 to 10
P2-13
Input B
prescale
exponent (y)
PScbY
10 01
10 - 9 (10
-9
) to 10 09 (10
9
)
P2-14 Display cycle
dISpT
)05
OFF
02)
or 0.05, 0.5, 1, 2, 4, 8 sec
P1-1 Input
operation
mode:
F1 to 2,
F7 to 10, F16
P2-15
Input B
setting value
(INB)
COUnB
99999
1 to 99999
P1-1 Input
operation
mode: F16
01) To enter P2-4 time range (unit: sec) and P2-5 time range (unit: min) setting, press [▲] key at P2-3 time unit.
02) Only available operation mode F2, F16
■
Parameter 2
group
■
Parameter 3
group
Parameter
Display
Default
Setting range
Display
condition
P3-1
Max. PV
transmission
output value
FS-H
99999
[PV transmission (current) output model]
min. value to max. value (FS-H ≥ FS-L + 1)
Operation mode Setting range
F1, F2, F7, F9, F11,
F12, F13, F16
0 to 99999
F3, F4, F5, F6
0.01 to
time setting range
F8, F10, F14, F15
-19999 to 99999
• Varies according to P1-1 Input operation
mode and P2-2 Decimal point position of
display value
-
P3-2
Min. PV
transmission
output value
FS-L
00000
-
P3-3 current
output
MA
4-20
[PV transmission (current) output model]
4-20, 0-20 mA
-
P3-4 Comm.
address
ADDR
01
[RS485 communication output model]
01 to 99
-
P3-5 Comm.
speed
BPS
9600
[RS485 communication output model]
2400, 4800, 9600, 19200, 38400 bps
-
P3-6 Comm. parity
bit
PRTY
NONE
[RS485 communication output model]
NONE, EVEN, ODD
-
P3-7 Comm. stop
bit
STP
2
[RS485 communication output model]
1, 2
-
P3-8
Comm.
response
waiting time
RSwT
20
[RS485 communication output model]
Comm. speed
Setting range
2400 bps
16 to 99 ms
4800 bps
8 to 99 ms
9600, 19200,
38400 bps
5 to 99 ms
• Setting range varies according to P3-5
Comm. speed
-
P3-9 Comm. write
COmW
DISA
[RS485 communication output model]
ENA: enable, DISA: disable
-
P3-10 Lock
LOC
OFF
OFF : Unlock
LOC.0 : Lock All
LOC.1 : Lock parameter 1 / 2 / 3
LOC.2 : Lock parameter 2 / 3
LOC.3 : Lock parameter 3
-
P3-11 Parameter
reset
mRST
ENA
ENA: enable, DISA: disable
-