SL93x + TBV327-MT-EN
p. 13/40
Type of
cable
Connections
Evacuation
command
(Fire):
If through a dry contact:
connect lower
connectors (Fire link)
with a Normally Closed
switch
AND
put the jumper in the
lower position.
Note
: if there is no
evacuation command,
shunt these connectors.
If through a 24 V DC
command:
connect upper
connectors (0V and
+24")
AND
put the jumper in the
upper position.
Network
cable
Connect the opening
commands and eventual
Inputs/Outputs.
Refer to the electrical diagrams.
0 V
+ 24 V