48
Instructions for the installer
SWEEPER MODE
C
BCM
For the adjustment of each individual module it is
necessary to put the switch ‘’ C ‘’, in position I, as
shown in the figure. In this way all the modules
are switched OFF and the first module is ignited.
To pass to the following modules (after the previous
one has been switched OFF) repeat the step 0 - 1
of the switch ‘’ C’ as shown in figure.
The function is active for a time of 15 min,
after that the planned parameters are
restored.
SW NO XXXX
CASCATA MANU
BOILER 01 - 00%
CHANGE PER CENT
VALUE
TO 10 %.
BOILER 01 - 10%
VARY THE VALUE
FROM 10 % TO 100%.
PER CENT
BOILER 01 - 100%
RELAY TEST
Turn
anticlok-wise
O
displayed
pen the operating flap,
DISPLAY
GENERAL
After
2 sec
is displayed
level
DATA/TIME
SERVICE
Press
to open
the level
Before open the operating flap
turn clock-wise Shaft encoder,
to symbol
Turn
anticlok-wise
Turn
clok-wise
Press
to open
the level
Turn
clok-wise
Press
to open
the level
All modules of the
boiler running and
working at MINIMUM
power
All modules of the
boiler running and
working at MAXIMUM
power