23
Instructions for the installer
Note:
Modulex 660 - 770 - 900 need 2 security
valve.
17
SAFETY VALVE
VISIBLE
DRAIN
FUNNEL
3.12-
PRESSURE RELIEF VALVE DRAIN
PIPE
A pressure relief valve must be fitted on the flow
pipe, within 0,5 m from the boiler. It must be
dimensioned for the capacity of the boiler and
must comply to the regulations in force,
WARNING!
Please remember that it is forbidden to
interpose, between the boiler and the
pressure relief valve, any type of cutting-off
device. Moreover it is recommended to use
cutting-off valves which do not exceed the
maximum allowable operating pressure.
WARNING!
In correspondence to the heating pressure
relief valve foresee the installation of a
discharge pipe with a funnel and a siphon
which lead to an adequate drainage. The
drainage has to be controllable by sight.
If this precaution is not made, an eventual
intervention of the pressure relief valve could
cause injury to persons, animals or damage
to property. The manufacturer shall not be
held liable for any injury and/or damage.
3.14 - BALLSTOP VALVES
The installation of ballstop gate valves, on the C.H. flow and
return connection, is recommended.
Doing so, in case of normal or extraordinary service, the boi-
ler can be drained without emptying the whole C.H. sistem.
WARNING!
IT IS NOT ALLOWED TO ISOLATE THE SAFETY
DEVICES, as the safety valve and the expan-
sion vessel, FROM THE BOILER.
3.13 -
MIXING HEADER FILTER
UNICAL suggests the installation of a Y filter
on the return pipe so that it can be cleaned if
necessary.
This filter will protect the boiler from the heating
system dirt.
Secondary
circuit