Special situations

ź

ź

ź

ź

ź

When 3 consecutive transmissions (after 15 minutes) from the 

AURATON 

200  RTH

  regulator  and/or  the 

T-2

  thermometer  are  lost,  an  error  is 

signalled on the 

RTH

 receiver (LED flashing continuously red and green). 

The 

RTH

 receiver starts executing the ON - OFF cycle memorised during 

the last 24 hours of operation until the problem is removed.

When  both  signals  return  (from  the 

AURATON  200  RTH

  regulator  and 

the

 T-2

 thermometer), the error is cancelled and the receiver enters its 

normal mode of operation.

When only the 

T-2

 thermometer signal returns, the receiver uses the last 

memorised setpoint value and maintains it while signalling the error.

When the 

H-1

 handles, the 

T-2

 thermometer and the 

AURATON 200 RTH

 

regulator (the temperature is measured with the 

T-2

 thermometer) are 

paired with the receiver, then maintaining the work cycle from the last 24 
hours occurs only after losing the signal from the 

T-2

 thermometer. When 

only the signal from the

 AURATON 200 RTH

 is missing, the RTH receiver 

automatically maintains the last memorised setpoint from the 

AURATON 

2025 RTH

 regulator and also signals an error.

When you have only the 

H-1

 handles and the 

T-2

 thermometer paired with 

the 

RTH

  receiver  without  the 

AURATON  200  RTH

  regulator,  the 

RTH

 

receiver maintains a constant, factory-defined temperature of 20 °C. If you 
pivot any window equipped with the 

H-1

 handle paired with the receiver, 

a temperature of 17 °C is maintained. If you open any window equipped 
with the 

H-1

 handle paired with the 

RTH

 receiver, the receiver switches off 

the heating device, but will switch it back on when the temperature falls 
below 7 °C.

 

ź

ź

ź

Switching the relay is synchronised with the wave of the 230 V mains voltage 

in  order  to  ensure  that  closing  and  opening  contacts  of  the  relay  occurs 
around the zero-crossing point. This prevents the occurrence of an electric 
arc, significantly extending the relay service time.

The 

AURATON  RTH

  receiver  is  equipped  with  a  unique  algorithm  for 

analysing the ON - OFF cycles. The entire heating cycle from the last 24 hours 
is  recorded  in  the  memory  of  the 

RTH

  receiver.  In  the  event  of  losing 

communication  with  the 

AURATON  200  RTH

  regulator  and/or  the 

T-2

 

thermometer, the 

RTH

 receiver automatically executes the ON - OFF cycle 

memorised  during  the  last  24  hours.  This  provides  time  for  restoring 
transmission  (removing  interferences)  or  fixing  the 

200  RTH

  regulator 

and/or the 

T-2

 thermometer without a significant deterioration of thermal 

comfort conditions in the controlled spaces.

Cooperation  with  optional  devices  (the 

AURATON  T-2

  thermometer, 

the 

AURATON H-1

 window handle).

Unique features of AURATON 200 RTH

Additional information and notes

ź

ź
ź

ź

ź

ź

The controller can be switched on or off at any time by holding the        key 
pressed for a while.

ź

Pressing  any  function  key  for  the  first  time  always  starts 

the backlight first, and then the key function is performed.

ź

While programming any function, if no key is pressed for 10 seconds, this  

will be interpreted as pressing the         key.

The 

AURATON  200  RTH

  regulator  and/or  the 

T-2

  thermometer  must  be 

installed at least 1 metre from the 

RTH

 receiver (too strong a signal from the 

transmitters can cause interference).

At least 30 seconds must elapse between switching the relay off and on.
Data transmission from the 

AURATON 200 RTH

 regulator to the receiver 

occurs upon each change of 0.2 °C of the surrounding temperature. When 
the  temperature  is  stable,  the  regulator  sends  heart-beat  data  every  5 
minutes  (which  is  signalled  with  the  LED  blinking  orange  on  the 

RTH

 

receiver).

In the event of a power outage, the

 RTH

 receiver will switch off. When power 

is restored, the heating device is switched on automatically, and the 

RTH

 

receiver awaits a signal from the paired transmitters (this signal should be 
received within 5 minutes of restoring power). After receiving the signal, the 

RTH

 receiver enters the normal mode of operation.

The

 RTH

 receiver cannot be placed in metal containers (e.g. an assembly 

box,  a  metal  enclosure  of  a  heater)  in  order  to  not  to  interfere  with  its 
operation.

 

Summary of Contents for 200 RTH

Page 1: ...www auraton pl 200 RTH AURATON RTH OFF ON IN OUT ALARM RESET dla oprogramowania w ver F03 oraz F0A AURATON 200 RTH Instruction Manual ...

Page 2: ...2 ...

Page 3: ... system This way the handle provides information about the state of the window The handle also differentiates between 4 widow positions opened closed pivoted and trickle ventilated micro ventilation The handle transmits information to the RTH receiver that controls the relay e g switching off a heater in the event of opening the window or lowering the temperature down to 3 C to conserve energy One...

Page 4: ...n buttons 4 AURATON 200 LCD display temperature increase key temporary temperature decrease mode keys acknowledge or on off key temperature decrease key ź hold controller on off ź short press acknowledge temperature setting AURATON 200 RTH temperature controller explained ...

Page 5: ...ndicator Indicates the operating status Appears when the controller deviceisstarted 6 Transmissionsymbol Indicatescommunicationwiththereceiver 7 Batteryexhausted Displayed when the battery voltage drops below the allowed limit Replacethebatteryassoonaspossible Display screen 1 Temperature In normal operating mode the controller displays thetemperatureoftheroomitisinstalledin 2 Temperatureunit Indi...

Page 6: ... 200 RTH wireless regulatorandtheRTHreceiver The LED flashes red the RTH receiver awaits the device to be deregistered chapter Deregistering the regulator from the RTHreceiver TheLEDflashesalternatingredandgreen ALARM the RTH receiver has lost connection with one of the paired devices chapter Specialsituations RESET receiver deregisters all previously paired devices chapter Deregisteringalldevices...

Page 7: ...tion wall in a place with free air circulation Avoid locations near sources of heat TV set heater refrigerator or places exposed to direct sunlight Location near doors and the resultant vibration maycausethecontroller tofunction improperly Battery installation replacemen in AURATON 200 RTH Battery sockets are located inside the controller on both sides of the display To install the batteries remov...

Page 8: ...w the back of the controller enclosure to the wall with the two screws provided 5 Installthebatteriesandreplacethecontrollerenclosure NOTE No expansion bolts are needed for wooden walls Just drill holes diameter 2 7 mm insteadof6mm andscrewthescrewsdirectlyintothewood Alternative fixing methods The controller can be mounted to a smooth surface with e g two sidedadhesivetape The controller can also...

Page 9: ... with the cable tie clamps and reinstall protective covers of the AURATON RTH receiver Fastening the RTH receiver 1 Take off protective covers from the lower and upper part of the AURATON RTH receiver 2 Take off cable tie clamps from the lower and upper part of the AURATON RTH receiver protective cover cable tie clamp NOTE When installing the AURATON RTH receiver its power supply must be disconnec...

Page 10: ...er to the wall with screws making sure they hold the receiversecurely Fastening the RTH receiver to the wall NOTE If the wall is wooden there is no need to use wall plugs In such a case drill two holes 2 7 mm in diameter instead of 5 mm and screw thescrewsdirectlyintothewood AURATON RTH hole for fastening the receiver to the wall with a screw NOTE The RTH receiver cannot be placed in metal contain...

Page 11: ...r at least 2 seconds until the LED starts flashing green andthenreleasingthebutton The AURATON RTH receiver waits for pairing for 120 seconds After that time it automatically returnsbacktonormaloperation 2 On the AURATON 200 RTH regulator press and hold the buttons for 6 seconds until the transmission symbol appears on the display but OK OK but radio or Deregistering the regulator from the RTH rec...

Page 12: ...after approx 2 seconds by the LED colour changing to green and then switching it off forashortperiodoftime Signalling operation and reception of data packet Each radio transmission received by the AURATON RTH receiver from the paired device is signalled by a temporary change of LED colour to orange Switching on the relay is signalled by the LED lit red whereas switching it off is signalled by the ...

Page 13: ...odeandstartblinking When pressing any function key for the first time the backlight is turned or 2 With the and keys set the desired temperaturewiththeaccuracyofupto0 2 C 3 Pressthe keytoacknowledgeselection do up do up FrostGuard function AURATON 200 RTH controller features the special FrostGuard function to protecttheroomfrompossiblefreezing Thefunctionisactivatedwhenthecontrollerisswitchedoff W...

Page 14: ...rs the controller will return to the main temperature setting Instead of the moon symbol the sun symbol willbedisplayed NOTE The temporary temperature decrease mode always starts when the function is turned on This means that the possible temporary temperature decrease has to be set at the time you want it to take place Setting the temporary temperature decrease mode Switching off the temporary te...

Page 15: ...r setting the temperature manually and controlling itinthelocationofthefasteningofthe200RTHregulator Cooperation of the AURATON RTH receiver with the AURATON 200 RTH regulator and or the AURATON T 2 thermometer Cooperation of the RTH receiver with a heating device heating device AURATON RTH A simplified schematic of connecting the AURATON RTH receiver with the heating device AURATON 200 RTH Wirele...

Page 16: ... RTH receiver it is not possible to set the temperature manually and the RTH receiver maintains the factory temperature setpointof20 C NOTE 1 The sequence of pairing the AURATON 200 RTH regulator and the T 2 thermometer is very important If you want to maintain the remote setpoint you must first pair the AURATON 200 RTH with the RTH receiver and then the T 2 thermometer Reversing the pairing seque...

Page 17: ... will be maintained until closing This state will last until all windows areclosedortrickle ventilated C Thewindowisopened When you open a window equipped with the H 1 handle paired for longer than 30 seconds the relay in the AURATON RTH receiver is switched off as is the connected heating device If all the assigned windows are again in a state other than opened the RTH receiver returns to normal ...

Page 18: ...TON 200 RTH regulator the temperature is measured with the T 2 thermometer are paired with the receiver then maintaining the work cycle from the last 24 hours occurs only after losing the signal from the T 2 thermometer When only the signal from the AURATON 200 RTH is missing the RTH receiver automatically maintains the last memorised setpoint from the AURATON 2025RTHregulatorandalsosignalsanerror...

Page 19: ...d on or off at any timebyholding the key pressedforawhile ź Pressing any function key for the first time always starts thebacklightfirst andthenthekeyfunctionisperformed ź While programming any function if no key is pressed for 10 seconds this willbeinterpretedaspressingthe key The AURATON 200 RTH regulator and or the T 2 thermometer must be installed at least 1 metre from the RTH receiver too str...

Page 20: ...T ALARM RESET 230V AC L N control 230V power AURATON 200 RTH AURATON RTH OFF ON IN OUT ALARM RESET 230V AC L N L N L N heating device e g a gas furnace electric heating device Max 230V 16 A Max 230V The AURATON RTH receiver connection schematics ...

Page 21: ...e batteries RTH power supply 230V AC 50Hz RTH radio frequency 868MHz RTH Operation range in a typical building with standard construction of walls approx 30 m an open space up to 300 m 0 45 C Disposing of the devices The devices are marked with the crossed waste bin symbol According to European Directive no 2002 96 EU and the Act concerning used up electric and electronic equipment such a marking ...

Page 22: ...A template for drilling holes for fastening the AURATON RTH receiver 1 1 scale 22 ...

Page 23: ...23 ...

Page 24: ...www auraton pl ...

Reviews: