Starting the AURATON 200 RTH controller 
for the first time

After  correct  installation  on  batteries,  the  LCD 
will display, for a second, all segments (display 
test) followed by the firmware version number.

After  a  while,  the  current  temperature  in  the 
room will be displayed. The controller is ready to 
use.

Temperature setting

NOTE: 

on and then the key function is activated.

To set the desired temperature in normal operating mode:

1.

Press  the

key.  The  segment  displaying 

temperature will switch to edit mode and start blinking. 

When pressing any function key for the first time, the backlight is turned 

 

or

 

2.

With  the 

and

  keys,  set  the  desired 

temperature with the accuracy of up to 0.2°C. 

3.

Press the          key to acknowledge selection. 

<do> <up>

<do>

<up>

FrostGuard function

AURATON  200  RTH  controller  features  the  special  FrostGuard  function  to 
protect the room from possible freezing.

The function is activated when the controller is

 switched off

.

With the controller switched off, when the room temperature drops to 2°C, 
the 

Fr

 (      ) and flame (       ) symbols will appear and signal will be sent to the 

receiver to start heating. When the temperature raises to 2.2°C, the display 
will turn off again and signal will be sent to the receiver to turn the heating off.

3

. A  properly  completed  deregistering  process  is  signalled  by  the  LED  on  the 

AURATON RTH

 receiver no longer flashing red and the receiver reverting back 

to normal operation.

In the event of an error during the deregistering process, repeat steps 1 and 2. 
Should more errors occur, deregister all paired devices (see “RESET - Deregistering 
all devices paired with the RTH receiver”) and attempt to pair the device again

.

RESET - Deregistering all devices paired 
with the RTH receiver

In order to deregister all devices paired with 
the RTH receiver, simultaneously press both 
the  pairing  and  the  deregistering  button 
(

and  )  and  hold  them  for  at  least 

5 seconds until the LED flashes alternating 
red and green. Then release both buttons. 

A  properly  completed  process  of

 

deregistering  all  devices  is  signalled  after 
approx.  2  seconds  by  the  LED  colour 
changing to green and then switching it off 
for a short period of time.

.. 

..

Signalling operation and reception 
of data packet

Each radio transmission received by the 

AURATON RTH

 receiver from the paired 

device is signalled by a temporary change of LED colour to orange. Switching on 
the relay is signalled by the LED lit red, whereas switching it off is signalled by the 
LED lit green.

LED

NOTE

: If after executing the RESET function the RTH receiver is disconnected 

from power supply and then connected again, the receiver will automatically 
enter “pairing” mode for 120 seconds. A newly purchased RTH receiver without 
any factory-paired devices (i.e. not the one bundled with the regulator) will 
behave the same way.

2

. On the 

AURATON 200 RTH

 regulator, press and hold the buttons 

 6 seconds until the transmission symbol ( 

) appears on the 

display. Release the button  -  the regulator  transmits  the pairing signal for  5 
seconds. 

   

 

radio

or 

for

Summary of Contents for 200 RTH

Page 1: ...www auraton pl 200 RTH AURATON RTH OFF ON IN OUT ALARM RESET dla oprogramowania w ver F03 oraz F0A AURATON 200 RTH Instruction Manual ...

Page 2: ...2 ...

Page 3: ... system This way the handle provides information about the state of the window The handle also differentiates between 4 widow positions opened closed pivoted and trickle ventilated micro ventilation The handle transmits information to the RTH receiver that controls the relay e g switching off a heater in the event of opening the window or lowering the temperature down to 3 C to conserve energy One...

Page 4: ...n buttons 4 AURATON 200 LCD display temperature increase key temporary temperature decrease mode keys acknowledge or on off key temperature decrease key ź hold controller on off ź short press acknowledge temperature setting AURATON 200 RTH temperature controller explained ...

Page 5: ...ndicator Indicates the operating status Appears when the controller deviceisstarted 6 Transmissionsymbol Indicatescommunicationwiththereceiver 7 Batteryexhausted Displayed when the battery voltage drops below the allowed limit Replacethebatteryassoonaspossible Display screen 1 Temperature In normal operating mode the controller displays thetemperatureoftheroomitisinstalledin 2 Temperatureunit Indi...

Page 6: ... 200 RTH wireless regulatorandtheRTHreceiver The LED flashes red the RTH receiver awaits the device to be deregistered chapter Deregistering the regulator from the RTHreceiver TheLEDflashesalternatingredandgreen ALARM the RTH receiver has lost connection with one of the paired devices chapter Specialsituations RESET receiver deregisters all previously paired devices chapter Deregisteringalldevices...

Page 7: ...tion wall in a place with free air circulation Avoid locations near sources of heat TV set heater refrigerator or places exposed to direct sunlight Location near doors and the resultant vibration maycausethecontroller tofunction improperly Battery installation replacemen in AURATON 200 RTH Battery sockets are located inside the controller on both sides of the display To install the batteries remov...

Page 8: ...w the back of the controller enclosure to the wall with the two screws provided 5 Installthebatteriesandreplacethecontrollerenclosure NOTE No expansion bolts are needed for wooden walls Just drill holes diameter 2 7 mm insteadof6mm andscrewthescrewsdirectlyintothewood Alternative fixing methods The controller can be mounted to a smooth surface with e g two sidedadhesivetape The controller can also...

Page 9: ... with the cable tie clamps and reinstall protective covers of the AURATON RTH receiver Fastening the RTH receiver 1 Take off protective covers from the lower and upper part of the AURATON RTH receiver 2 Take off cable tie clamps from the lower and upper part of the AURATON RTH receiver protective cover cable tie clamp NOTE When installing the AURATON RTH receiver its power supply must be disconnec...

Page 10: ...er to the wall with screws making sure they hold the receiversecurely Fastening the RTH receiver to the wall NOTE If the wall is wooden there is no need to use wall plugs In such a case drill two holes 2 7 mm in diameter instead of 5 mm and screw thescrewsdirectlyintothewood AURATON RTH hole for fastening the receiver to the wall with a screw NOTE The RTH receiver cannot be placed in metal contain...

Page 11: ...r at least 2 seconds until the LED starts flashing green andthenreleasingthebutton The AURATON RTH receiver waits for pairing for 120 seconds After that time it automatically returnsbacktonormaloperation 2 On the AURATON 200 RTH regulator press and hold the buttons for 6 seconds until the transmission symbol appears on the display but OK OK but radio or Deregistering the regulator from the RTH rec...

Page 12: ...after approx 2 seconds by the LED colour changing to green and then switching it off forashortperiodoftime Signalling operation and reception of data packet Each radio transmission received by the AURATON RTH receiver from the paired device is signalled by a temporary change of LED colour to orange Switching on the relay is signalled by the LED lit red whereas switching it off is signalled by the ...

Page 13: ...odeandstartblinking When pressing any function key for the first time the backlight is turned or 2 With the and keys set the desired temperaturewiththeaccuracyofupto0 2 C 3 Pressthe keytoacknowledgeselection do up do up FrostGuard function AURATON 200 RTH controller features the special FrostGuard function to protecttheroomfrompossiblefreezing Thefunctionisactivatedwhenthecontrollerisswitchedoff W...

Page 14: ...rs the controller will return to the main temperature setting Instead of the moon symbol the sun symbol willbedisplayed NOTE The temporary temperature decrease mode always starts when the function is turned on This means that the possible temporary temperature decrease has to be set at the time you want it to take place Setting the temporary temperature decrease mode Switching off the temporary te...

Page 15: ...r setting the temperature manually and controlling itinthelocationofthefasteningofthe200RTHregulator Cooperation of the AURATON RTH receiver with the AURATON 200 RTH regulator and or the AURATON T 2 thermometer Cooperation of the RTH receiver with a heating device heating device AURATON RTH A simplified schematic of connecting the AURATON RTH receiver with the heating device AURATON 200 RTH Wirele...

Page 16: ... RTH receiver it is not possible to set the temperature manually and the RTH receiver maintains the factory temperature setpointof20 C NOTE 1 The sequence of pairing the AURATON 200 RTH regulator and the T 2 thermometer is very important If you want to maintain the remote setpoint you must first pair the AURATON 200 RTH with the RTH receiver and then the T 2 thermometer Reversing the pairing seque...

Page 17: ... will be maintained until closing This state will last until all windows areclosedortrickle ventilated C Thewindowisopened When you open a window equipped with the H 1 handle paired for longer than 30 seconds the relay in the AURATON RTH receiver is switched off as is the connected heating device If all the assigned windows are again in a state other than opened the RTH receiver returns to normal ...

Page 18: ...TON 200 RTH regulator the temperature is measured with the T 2 thermometer are paired with the receiver then maintaining the work cycle from the last 24 hours occurs only after losing the signal from the T 2 thermometer When only the signal from the AURATON 200 RTH is missing the RTH receiver automatically maintains the last memorised setpoint from the AURATON 2025RTHregulatorandalsosignalsanerror...

Page 19: ...d on or off at any timebyholding the key pressedforawhile ź Pressing any function key for the first time always starts thebacklightfirst andthenthekeyfunctionisperformed ź While programming any function if no key is pressed for 10 seconds this willbeinterpretedaspressingthe key The AURATON 200 RTH regulator and or the T 2 thermometer must be installed at least 1 metre from the RTH receiver too str...

Page 20: ...T ALARM RESET 230V AC L N control 230V power AURATON 200 RTH AURATON RTH OFF ON IN OUT ALARM RESET 230V AC L N L N L N heating device e g a gas furnace electric heating device Max 230V 16 A Max 230V The AURATON RTH receiver connection schematics ...

Page 21: ...e batteries RTH power supply 230V AC 50Hz RTH radio frequency 868MHz RTH Operation range in a typical building with standard construction of walls approx 30 m an open space up to 300 m 0 45 C Disposing of the devices The devices are marked with the crossed waste bin symbol According to European Directive no 2002 96 EU and the Act concerning used up electric and electronic equipment such a marking ...

Page 22: ...A template for drilling holes for fastening the AURATON RTH receiver 1 1 scale 22 ...

Page 23: ...23 ...

Page 24: ...www auraton pl ...

Reviews: