8

Assembly Instruction

 FTA 600 

N

OTE

Post warning signs!

Other persons must be kept away from 
the casement when a hold-to-run switch  
(pushbutton) is operated or when a 
window, which has been opened by a 
smoke and heat exhaust system, is clo-
sing! 

The operating element of hold-to-run
switches must be installed within di-
rect view from the window, but apart 
from moving elements. If the switch is 
not a key-operated switch it must be
installed at a minimum height of 1,5 m 
and inaccessible to the public!

Do not allow children to play with
permanently mounted control devices 
and keep remote controls out of reach 
for children!

!

C

AUTION

!

C

AUTION

!

C

AUTION

During cleaning, maintenance work and while 
exchanging parts the drive must be comple-
tely disconnected from the power supply and 
secured against unintentional reactivation. 

During the proper assembly of drives with mounting
elements at a window, and the connection to an external 
control unit, the interfaces resulting from mechanical and 
electrical performance characteristics of single elements 
shall be observed.

!

W

ARNING

Do not use drive or casement when repair 
or re-setting work has to be performed! 

Replacement parts, fasteners and controls

The drive shall only be operated with control devices from 
the same manufacturer. There is no liability, warranty or 
customer service if third-party parts are used. Exclusively 
original replacement parts of the manufacturer shall be 
used for mounting elements or expansions.

Ambient conditions

The product may not be subjected to impacts or falls, or 
to vibrations, moisture, aggressive vapors or other harmful 
environments, unless the manufacturer released it for one 
or more of these environmental conditions.
• 

Operation:

 

 

Ambient temperature:   -5 °C … +75°C

 

Relative humidity:    

< 90% less 20°C;

        < 

50% 

less 

40°C;

        no 

formation 

of 

condensation

• 

Transport / Storage:

 

Storage temperature:   -5°C … +40°C

 

Relative humidity:    

< 60%

Accident prevention regulations and workmen’s
compensation insurance guidelines

For work on or in a building or building part the provisi-
ons and instructions of the respective accident prevention 
regulations (UVV and workmen’s compensation insurance 
guidelines (BGR /ASR) shall be observed and adhered to.

Declaration of Conformity

The drive is manufactured and inspected in accordance with 
European guidelines. The respective Declaration of Con-
formity is on hand. 

In case the operation of the drive differs from the
intended use, a risk evaluation for the complete
power-operated window system shall be performed 
and a Declaration of Conformity according Machinery 
Directive 2006 / 42 / EG issued.

S

AFETY

 

INSTRUCTIONS

01

Summary of Contents for FTA600 DF

Page 1: ...FTA600 R FTA600 DF FTA600 GF FOLDING ARM DRIVES according to Machinery Directive 2006 42 EC annex VI Assembly and Commissioning Instructions...

Page 2: ...ON STEP 4B FTA600 R Hinge side mounting inward opening door INSTALLATION STEP 4C FTA600 DF Hinge side mounting inward opening side hung window INSTALLATION STEP 4D FTA600 GF Opposite hinge side mounti...

Page 3: ...G AND SAFETY SYMBOLS IN THESE IN STRUCTIONS The symbols used in the instructions shall be strictly observed and have the following meaning Caution Warning Danger due to electric current Caution Warnin...

Page 4: ...0 mm by a simultaneous speed of 15 mm s at the HSK in closing direction Application as NSHEV natural smoke and heat exhaust ventilators for ventilation without dual function for ventilation in accorda...

Page 5: ...oor ZAA 20 1 Opening at HSK 200 mm and Speed at HSK CLOSE 15 mm s OPEN 50 mm s 20 ZAA 2 Yes Yes No No Risk covered by Declaration of Conformity for window drives Observe danger at NSK 2 5 m above floo...

Page 6: ...connection assignment the electrical supply data see machine plate and performance limits see technical data as well as the mounting and installation instructions of the drive must be strictly observe...

Page 7: ...h a trial run It shall be ensured that drive and casement are set correctly and that security systems if available are functioning properly After the installation of the system is completed the end us...

Page 8: ...ive shall only be operated with control devices from the same manufacturer There is no liability warranty or customer service if third party parts are used Exclusively original replacement parts of th...

Page 9: ...ir intlets Internal intelligent cut off switch S12 Programmable contact for door opener Unitary plug solution for all AUM LLER chain drives and AUM LLER folding arm drives Options Programmable special...

Page 10: ...temperature range 5 C 75 C MA Torque OPEN 215 Nm 600 N MZ Torque CLOSE 215 Nm 600 N FH Pullout force 3000 N fastening depended Lever arm aluminium RAL9006 Connecting cable with plug non halogen grey...

Page 11: ...gent cut off switch S12 Programmable contact for door opener Unitary plug solution for all AUM LLER chain drives and AUM LLER folding arm drives Options Programmable special functions M COM for automa...

Page 12: ...losing edges Space on the frame above min 56 max 106 mm Space on the frame above min 40 mm Space on the frame above min 48 mm Space on the frame min 60 mm on the casement min 40 mm door width 1200 mm...

Page 13: ...ins spind les of the drives must be extendable or retractable easily The casement must run smoothly and the weight must be in balance The test procedure of drives may only be performed on a non slip a...

Page 14: ...llowing conditions must be fulfilled for the instal lation of the drives so they can be properly assembled with other parts and constructed to a complete machine at the window without impairing the sa...

Page 15: ...profile depth PT and door hinge dimension B 05 MOUNTING FTA600 R DRILL HOLES ACCORDING TO MOUNTING VARIANTS FTA600 R OPPOSITE HINGE SIDE MOUNTING OUTWARD OPENING DOOR INSTALLATION STEP 3 INSTALLATION...

Page 16: ...IDE MOUNTING INWARD OPENING DOOR 05 INSTALLATION STEP 4B MOUNTING FTA600 R 260 400 422 5 5 x8 408 M5 x4 50 20 5 24 40 4 11 22 33 4 1x Angle L 422 50 x 40 x 4 1x Angle L 100 50 x 75 x 5 with slots 1x A...

Page 17: ...R FTA600 R Ensure that the role of the folding arm drive FTA600 R when opening and closing is based on the angle K88 K88 K88 K88 door leaf door frame 1 2 3 Space A A View from inside FTA600 R M5 105 5...

Page 18: ...5 6 8 35 30 6 6 20 6 5 6 9 70 130 130 408 70 24 22 11 33 M4 M5 RA 1 FTA600 DF 9 05 MOUNTING FTA600 DF 1x Angle L 422 50 x 40 x 4 1x Bolt 14 x 57 x M10 1x Lever arm 14 x 12 x 30 1x Eyebolt M8 1x Caseme...

Page 19: ...mm 81 15 mm 81 10 mm 79 0 mm 77 10 mm 76 20 mm 75 30 mm 05 MOUNTING FTA600 DF 36 47 10 40 20 35 25 X B X X 4 400 356 24 35 13 6 4 40 2 20 17 35 X X 13 5 10 X 4 X X 400 386 24 35 13 6 13 5 1 40 0 2 20...

Page 20: ...e angle of frame bracket K104 at the frame M5 Fasten folding arm drive FTA600 GF on the angle with the screws Fit slide rail with screws M5 at the casement Using the screws and lock washers and mount...

Page 21: ...F 10 10 11 11 Insert the circlip for stabilization in the drill hole Push bolt in the connector Insert this module in slide rail Using the screw and mount the drive arm of the folding arm drive FTA600...

Page 22: ...A FL BD BD AK FL Cable crossover without protective cable hose Cable crossover with protective cable hose Connection cable routing on the hinge side Make sure that during opening or closing procedure...

Page 23: ...grey GY WH is used for communication in systems with synchronized multi drive operation Standard CLOSE Optional OPEN contact max 24 V 500 mA min 10mA ELECTRIC CONNECTION ELECTRIC CONNECTION from contr...

Page 24: ...the housing cover with the both screws Locking hooks at the housing cover prevent withdrawal of the plug under tensile load Five terminals to 1 5 mm2 The performances especially the fire be havior of...

Page 25: ...acket 0 C 70 C 45 x 17 x 6 mm 3 wires 0 5 mm x 50 mm Feature Equipment printed circuit board with connecting wires for in tegration in site supplied junction box Cable junction box for renewal Order n...

Page 26: ...accessibility Ensure expansion possibilities of the drive and the drive cable Consider the cable length of drives Operation of the power operated window When operating the power operated window safety...

Page 27: ...diness must be checked regularly Frequent inspection of the system for imbalance and signs of wear or damages of cables and fastening elements must be performed During maintenance contaminations must...

Page 28: ...s to the country in which the product has been acquired The warranty includes material and manufacturing defects incurred during normal use The warranty period for delivered material is twelve months...

Page 29: ...29 Assembly Instruction FTA600 CERTIFICATES 08...

Page 30: ...30 Assembly Instruction FTA600 CERTIFICATES 08...

Page 31: ...ensure that the data and information are as correct and up to date as possible we still cannot guarantee that they are free from mistakes and errors All information and data contained in this document...

Page 32: ...n Tel 49 8271 8185 0 Fax 49 8271 8185 250 info aumueller gmbh de 9000017000_V0 1_KW05 14 www aumueller gmbh de AUM LLER AUMATIC GMBH Gemeindewald 11 86672 Thierhaupten Tel 49 8271 8185 0 Fax 49 8271 8...

Reviews: