background image

 
 

 

 

 

 

 

 

 

AUMSHIVAY ENGINEERING PRIVATE LIMITED 

 

 

B-21, Bhan Nagar, Queens Road, Jaipur-302021

 

Website: www.aumshivay.com, www.omengineering.in

 

E-mail:[email protected]

 

 

 

 

 

 

 

 

 

 

PAGE. 14

 

 

REG. OFFICE:VILLA NO. 60,LATA NAGAR, KALWAR ROAD, JHOTWARA, JAIPUR - 302012 

TM 

 

TM 

 

 

 

Features; 

 

Automatic correction of CTs’ mismatch and Transformer Vector Group. 

 

Two differential current levels. 

 

2nd and 5th harmonic adjustable restraint levels. 

 

Programmable percentage bias curve. 

 

Oscillographic recording. 

 

Modbus Communication Protocol. 

 

Maximum Demand & Inrush Recording. 

 

 

 

 

F87T : High-set Phase 
Differential 

Current setting range : 

d>> = (2 - 20)In

, step 0.01In                                                                                       

Detection time: 

6ms < t < 20ms 

                                                                

Peak current detection with DC offset restraint. 

Digital Inputs 

B1 

= Operation block input                                                                          

B2

 = Harmonic restraint's reduction                                                             

B3

 = Oscillographic record external trigger 

Approval: CE 
Reference Standards  

Dielectric test voltage- IEC 60255-5                                                    
Impulse test voltage - IEC 60255-5                                                       
Insulation resistance - >100 M 

Characteristics 

Accuracy at reference value of influencing factors 

:                                                                               

2% In for measurement and 2% +/- 10ms for times.                                                                                     

Rated Current: 

In = 1 or 5A 

Current overload : 

200 A for 1 sec; 10A continuos                                                                                    

Burden on current inputs : 

Phase : 0.01VA at In = 1A; 0.2VA 

at In = 5A and Neutral : 0.015VA at In = 1A ; 0.35VA at In = 5A.                                                  

Average power supply consumption: 

8.5 VA                                           

Output relays :

 Rating 5 A; Vn = 380 V 

A.C. resistive switching = 1100W (380V max) 
make = 30 A (peak) 0.5 sec. 
break = 0.3 A, 110 Vcc, 
L/R = 40 ms (100.000 op.) 

Summary of Contents for MC 12A

Page 1: ...b stations The relay has a built in high set facility DIP switches are provided on the front panel for pick up and time delay settings User has a choice of 7 trip time characteristics FEEDER PROTECTIO...

Page 2: ...1987 a Normal Inverse 3s b Normal Inverse 1 3s c Very Inverse d Extremely Inverse Definite time Three curves as follows e Definite Time 1s f Definite time 10s g Definite time 100s Accuracy As per Erro...

Page 3: ...iliary Supply 24 240 V AC DC Wide TMS Range 0 01 1 60 Draw out execution With automatic CT shorting facility Instantaneous Over current and earth fault element Communication Through Modbus Protocol on...

Page 4: ...Stator Ground Fault protection MG30 incorporates 5 output relays expandable up to 16 with the additional module REX 8 Features Voltage controlled over current protection Thermal image element with pr...

Page 5: ...Instantaneous output 30ms 2 Harmonic restraint level 2H 0 1 1 0 Id step 0 01Id First percent bias 0 5 IR In P 1R 2 20 step 1 Second percent bias IR In P 2R 5 50 step 1 Point of slope variation P 1 3 s...

Page 6: ...0 to 40 of In in steps of 5 or 20 to 80 of In in steps of 10 CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel programmable using push buttons Pick up...

Page 7: ...se Cts 1 9999 A step 1A On Rated primary current of earth fault detection Cts 1 9999 A step 1A CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel progr...

Page 8: ...utomatically manage the starting transition Switch over transition current Itr 0 1 1 Ist step 0 1Ist Maximum switch over time delay tTr 0 5 50 s step 0 1s At motor s start counting of tTr begins If du...

Page 9: ...pick up level A DIP switch is provided for selection of thermal overload trip class and enable disable of Locked rotor protection and under current protection Other settings are prefixed in the relay...

Page 10: ...3 sec Both factory set Locked rotor protection Locked rotor current 3 Im Trip time delay 1 sec Both factory set Disable feature Available Under Current protection Under current threshold 50 of Im Tri...

Page 11: ...d applicable time delays are indicated on a label on right hand side of the unit The wiring diagram label is provided on the left hand side of the unit Display Current and Thermal Capacity Display Dur...

Page 12: ...l through various settings Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3 Table 1 gives description of each setting APPLICATIONS MPR 300 offers yo...

Page 13: ...dVB IdVC Maximum Demand and Inrush Recording IdA IdB IdC Ido I1A I1B I1C I2A I2B I2C IdIIA IdIIB IdIIC IdVA IdVB IdVC Programmable Input Quantities Fn System frequency 50 60 Hz 1In Rated primary curre...

Page 14: ...1In Detection time 6ms t 20ms Peak current detection with DC offset restraint Digital Inputs B1 Operation block input B2 Harmonic restraint s reduction B3 Oscillographic record external trigger Approv...

Page 15: ...00 ms can be set Current Input 1A 5A Application These relay can be used for differential protection of generators REF applications of generators and transformers in all low voltage medium voltage sub...

Page 16: ...nt Function enabling Enable Disable Setting range V 0 5 1 50 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV 0 05 60 s step 0 01s F59 V Second OverVoltage Element Function enabling Enable...

Page 17: ...alanced Overvoltage Element Function enabling Enable Disable Setting range V2 0 1 1 5 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV2 0 05 60 s step 0 01s Characteristics Accuracy at ref...

Page 18: ...t Characteristics Normal Inverse 3 5 sec in O V mode Normal Inverse 5 7 sec in U V mode Definite Time 1 10 100 Sec Pick up Voltage Same as set Voltage Vs Reset Voltage 90 to 95 of Set Voltage Vs 105 t...

Reviews: