TECHNICAL SPECIFICATIONS (FEEDER PROTECTION RELAY-MC12A) 

Rated Current (In) 

1A or 5A 

Rated Frequency 

50Hz ± 2.5 Hz 

Auxiliary Power 

Supply 

24V to 110V AC/DC ± 10% 
95V to 240V AC/DC ± 10% 

Relay Settings 

Current (IS)

: One of the three ranges (User selectable) 

10% to 40% of In in steps of 2% or 20% to 80% of In in steps of 4 %                                               

or 50% to 200% of  in steps of 10%.                                                                                                                                   

 

High-set Current (Ihs): 

2 Is to 16 Is in steps of 2 Is and disable.                                                                                           

Time Multiplier TMS: 

0.1 to 1.6 in steps of 0.1. 

Operating 

Characteristics 

Front panel programmable, using push buttons.                                                                         

Time /Current characteristics;  

                                                                                                      

Pick up current; 

Same as set current 

Is

.                                                                                        

Reset Current:

 95% to 90% of set current 

Is.

 

Operating time : 

Inverse time;

                                                                                                                                                  

Four curves, As per IS 3231:1987.                                                                                                                

a) Normal Inverse 3s 

b) Normal Inverse 1.3s 
c) Very Inverse 

d) Extremely Inverse 

Definite time;

                                                                                                                                                 

Three curves as follows: 

e) Definite Time 1s 

f) Definite time 10s 

g) Definite time 100s 

Accuracy:

 As per Error class 5 of IS3231: 1987 

Reset time:

 Less than 50 milli sec 

High-set (Instantaneous trip):                                                                                                        

Accuracy:

 As per Error class 5 of IS3231: 1987.                                                                    

Operating time: 

Less than 50 ms for Iin < 1.5 Ihs 

Less than 35 ms for Iin > 1.5 His (Iin = input current) 

Burden 

Less than 0.25 VA on all settings.                                                                                                            

Less than 5.5 VA at Auxiliary Power supply 

Operation Indicators 

Separate LED indications for:                                                                                                                       

• Power on 

• Trip status (LED blinks when input crosses set point and becomes steady on when relay 

has tripped. LED has to be manually reset) 

• Time current characteristics selected 

Output Relay Contacts 

• 2 c/o contacts for trip signal (self reset) 

Output contact rating 

Rated voltage: 

250 V AC / 30 V DC, 

Max. S/W voltage: 

440 V AC / 300 V DC                                                                                       

Rated current: 

8A , 

Max. Current: 

14A                                                                                                                                   

Rated Breaking Capacity: 

2000VA / 240 W (Resistive) 

Over Load capacity 

2 In continuously, 20 times In for 1 sec. 

Case 

Front Bezel: 158 x 71 mm,  Panel Cutout: 142 x 62 mm , Depth:224 mm 

Weight 

0.9 kg approx. 

Summary of Contents for MC 12A

Page 1: ...b stations The relay has a built in high set facility DIP switches are provided on the front panel for pick up and time delay settings User has a choice of 7 trip time characteristics FEEDER PROTECTIO...

Page 2: ...1987 a Normal Inverse 3s b Normal Inverse 1 3s c Very Inverse d Extremely Inverse Definite time Three curves as follows e Definite Time 1s f Definite time 10s g Definite time 100s Accuracy As per Erro...

Page 3: ...iliary Supply 24 240 V AC DC Wide TMS Range 0 01 1 60 Draw out execution With automatic CT shorting facility Instantaneous Over current and earth fault element Communication Through Modbus Protocol on...

Page 4: ...Stator Ground Fault protection MG30 incorporates 5 output relays expandable up to 16 with the additional module REX 8 Features Voltage controlled over current protection Thermal image element with pr...

Page 5: ...Instantaneous output 30ms 2 Harmonic restraint level 2H 0 1 1 0 Id step 0 01Id First percent bias 0 5 IR In P 1R 2 20 step 1 Second percent bias IR In P 2R 5 50 step 1 Point of slope variation P 1 3 s...

Page 6: ...0 to 40 of In in steps of 5 or 20 to 80 of In in steps of 10 CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel programmable using push buttons Pick up...

Page 7: ...se Cts 1 9999 A step 1A On Rated primary current of earth fault detection Cts 1 9999 A step 1A CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel progr...

Page 8: ...utomatically manage the starting transition Switch over transition current Itr 0 1 1 Ist step 0 1Ist Maximum switch over time delay tTr 0 5 50 s step 0 1s At motor s start counting of tTr begins If du...

Page 9: ...pick up level A DIP switch is provided for selection of thermal overload trip class and enable disable of Locked rotor protection and under current protection Other settings are prefixed in the relay...

Page 10: ...3 sec Both factory set Locked rotor protection Locked rotor current 3 Im Trip time delay 1 sec Both factory set Disable feature Available Under Current protection Under current threshold 50 of Im Tri...

Page 11: ...d applicable time delays are indicated on a label on right hand side of the unit The wiring diagram label is provided on the left hand side of the unit Display Current and Thermal Capacity Display Dur...

Page 12: ...l through various settings Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3 Table 1 gives description of each setting APPLICATIONS MPR 300 offers yo...

Page 13: ...dVB IdVC Maximum Demand and Inrush Recording IdA IdB IdC Ido I1A I1B I1C I2A I2B I2C IdIIA IdIIB IdIIC IdVA IdVB IdVC Programmable Input Quantities Fn System frequency 50 60 Hz 1In Rated primary curre...

Page 14: ...1In Detection time 6ms t 20ms Peak current detection with DC offset restraint Digital Inputs B1 Operation block input B2 Harmonic restraint s reduction B3 Oscillographic record external trigger Approv...

Page 15: ...00 ms can be set Current Input 1A 5A Application These relay can be used for differential protection of generators REF applications of generators and transformers in all low voltage medium voltage sub...

Page 16: ...nt Function enabling Enable Disable Setting range V 0 5 1 50 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV 0 05 60 s step 0 01s F59 V Second OverVoltage Element Function enabling Enable...

Page 17: ...alanced Overvoltage Element Function enabling Enable Disable Setting range V2 0 1 1 5 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV2 0 05 60 s step 0 01s Characteristics Accuracy at ref...

Page 18: ...t Characteristics Normal Inverse 3 5 sec in O V mode Normal Inverse 5 7 sec in U V mode Definite Time 1 10 100 Sec Pick up Voltage Same as set Voltage Vs Reset Voltage 90 to 95 of Set Voltage Vs 105 t...

Reviews: