background image

 
 

 

 

 

 

 

 

 

AUMSHIVAY ENGINEERING PRIVATE LIMITED 

 

 

B-21, Bhan Nagar, Queens Road, Jaipur-302021

 

Website: www.aumshivay.com, www.omengineering.in

 

E-mail:[email protected]

 

 

 

 

 

 

 

 

 

 

PAGE. 11

 

 

REG. OFFICE:VILLA NO. 60,LATA NAGAR, KALWAR ROAD, JHOTWARA, JAIPUR - 302012 

TM 

 

TM 

 

Motor Protection Relay (MM10); 

These Relay is a microprocessor based Motor Protection Relay with 4 digits LED 

Display MM10 is a motor protection relay that combines thermal overload, short circuit, undercurrent, unbalance, phase loss, 

phase sequence, lock/stall rotor and earth fault protections. These incorporates a 4-digit LED indicator which allows direct 

numerical readout of set values, actual measured value and system indication. MM10 has 2 relay outputs (R1 and R2). R1 is On 

under normal operating condition to allow motor running, and off during tripping. R2 is programmable to give signal in various 

conditions. A programmable binary input is provided to perform various operations upon binary input triggering.

 

MOTOR PROTECTION RELAY (MM10) 

ITEM 

Compact Motor Protection Relay  

MAKE 

L&T 

MODEL 

MM10 

SIDE LABELS 

All data pertaining to pick up level and applicable time delays 
are indicated on a label on right hand side of the unit. The 
wiring diagram label is provided on the left hand side of the 
unit. 

Display 

Current and Thermal Capacity Display: 

During power up, 

when the relay is not under tripping condition, the display 
shows current in ampere or thermal capacity %. The Function 
LED indicates which parameter is being displayed. The Data 
LED showing value. 
Press “UP” or “DOWN” to scroll through the parameters.    

Auto Scroll: 

When auto scroll is enabled, the display scrolls 

between currents and thermal reading every 10 seconds. To 
toggle auto scroll mode, press "UP" and "DOWN" 
simultaneously 

*LED Display: i) Run LED -

Run LED shows the motor status. 

Refer to 3.2.1 Motor Starting.                                                                                 

Off - 

Motor stopping,                                                                                   

Blink - 

Motor starting,                                                                                    

On - 

Motor running      

 *

Trip LED: 

Trip LED is normally off. During tripping pickup, 

where tripping delay is counting down, Trip LED blinks. Trip 
LED on during tripping. 

Off

 

Normal                                                                                                   

Blink 

- Pickup                                                                                               

On -

 Tripping            

 *

Thermal LED: 

Thermal LED blinks when motor current is 

more than 105% of IB. Thermal LED on during thermal 
overload tripping, and when thermal capacity is more than 
40% after overload tripping (in which R1 is off, motor not 
allowed to start).                                                                                          

Off - 

Normal                                                                                                     

Blink -

 Thermal overload warning                                                                                              

On -

 Thermal overload tripping, Thermal capacity high, R1 off.

 

Summary of Contents for MC 12A

Page 1: ...b stations The relay has a built in high set facility DIP switches are provided on the front panel for pick up and time delay settings User has a choice of 7 trip time characteristics FEEDER PROTECTIO...

Page 2: ...1987 a Normal Inverse 3s b Normal Inverse 1 3s c Very Inverse d Extremely Inverse Definite time Three curves as follows e Definite Time 1s f Definite time 10s g Definite time 100s Accuracy As per Erro...

Page 3: ...iliary Supply 24 240 V AC DC Wide TMS Range 0 01 1 60 Draw out execution With automatic CT shorting facility Instantaneous Over current and earth fault element Communication Through Modbus Protocol on...

Page 4: ...Stator Ground Fault protection MG30 incorporates 5 output relays expandable up to 16 with the additional module REX 8 Features Voltage controlled over current protection Thermal image element with pr...

Page 5: ...Instantaneous output 30ms 2 Harmonic restraint level 2H 0 1 1 0 Id step 0 01Id First percent bias 0 5 IR In P 1R 2 20 step 1 Second percent bias IR In P 2R 5 50 step 1 Point of slope variation P 1 3 s...

Page 6: ...0 to 40 of In in steps of 5 or 20 to 80 of In in steps of 10 CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel programmable using push buttons Pick up...

Page 7: ...se Cts 1 9999 A step 1A On Rated primary current of earth fault detection Cts 1 9999 A step 1A CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel progr...

Page 8: ...utomatically manage the starting transition Switch over transition current Itr 0 1 1 Ist step 0 1Ist Maximum switch over time delay tTr 0 5 50 s step 0 1s At motor s start counting of tTr begins If du...

Page 9: ...pick up level A DIP switch is provided for selection of thermal overload trip class and enable disable of Locked rotor protection and under current protection Other settings are prefixed in the relay...

Page 10: ...3 sec Both factory set Locked rotor protection Locked rotor current 3 Im Trip time delay 1 sec Both factory set Disable feature Available Under Current protection Under current threshold 50 of Im Tri...

Page 11: ...d applicable time delays are indicated on a label on right hand side of the unit The wiring diagram label is provided on the left hand side of the unit Display Current and Thermal Capacity Display Dur...

Page 12: ...l through various settings Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3 Table 1 gives description of each setting APPLICATIONS MPR 300 offers yo...

Page 13: ...dVB IdVC Maximum Demand and Inrush Recording IdA IdB IdC Ido I1A I1B I1C I2A I2B I2C IdIIA IdIIB IdIIC IdVA IdVB IdVC Programmable Input Quantities Fn System frequency 50 60 Hz 1In Rated primary curre...

Page 14: ...1In Detection time 6ms t 20ms Peak current detection with DC offset restraint Digital Inputs B1 Operation block input B2 Harmonic restraint s reduction B3 Oscillographic record external trigger Approv...

Page 15: ...00 ms can be set Current Input 1A 5A Application These relay can be used for differential protection of generators REF applications of generators and transformers in all low voltage medium voltage sub...

Page 16: ...nt Function enabling Enable Disable Setting range V 0 5 1 50 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV 0 05 60 s step 0 01s F59 V Second OverVoltage Element Function enabling Enable...

Page 17: ...alanced Overvoltage Element Function enabling Enable Disable Setting range V2 0 1 1 5 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV2 0 05 60 s step 0 01s Characteristics Accuracy at ref...

Page 18: ...t Characteristics Normal Inverse 3 5 sec in O V mode Normal Inverse 5 7 sec in U V mode Definite Time 1 10 100 Sec Pick up Voltage Same as set Voltage Vs Reset Voltage 90 to 95 of Set Voltage Vs 105 t...

Reviews: