No-Load Running 

Under current level:  I< = (0.15-1)Im, step 0.01Im                                                                              
Trip time delay: tI< = (0.1-90)s, step 0.1s                                                                                                    
When current is below 0.1 Im the function is disabled 

Earth Fault 

Current setting range:  O> = (0.02 - 2)On, step 0,01On                                                                      
Istantaneous output : £ 0.03s (Reset time of instantaneous output : tO> + tBO)                                                                                        
Independent time delay :  tO> = (0.05 - 5)s, step 0.01s                                   

Over-current 

Current setting range:  I> = (1 - 5)Ist, step 0.1Ist (limited to 20 In)                                                                                                                                    
Istantaneous output:  £ 0.03s (Reset time of instantaneous output : tI> + tBO)                                                                                                               
Independent time delay: tI> = (0.05 - 1)s, step 0.01s                                                                                   
Reset time delay of the blocking output relay :  tBO = (0.05 - 0,5)s, step 0,01s 

 Limitation of N° of Starting 

Numbers of startings: StNo = (1 - 60), step 1                                                                                                   
Time interval for counting of StNo : tStNo = (1 - 60)min, step 1min If during the set 
interval the StNo is attained, a new start is inhibited for the time tBst.                                                                                                                              
Reset time after trip :  tBst = (1 - 60)min, step 1min. 

Starting Sequence Control 

During start-up of the motor, the unit can control an output contact used to operate the 
switch-over of Reduced Voltage 
motor starter (star-delta, resistance or impedance, autotransformers, etc.) to 
automatically manage the starting transition:                                                                                                                                 
Switch-over (transition) current: : Itr = (0.1-1)Ist, step 0.1Ist.                                                                                                
Maximum switch-over time delay: tTr = (0.5-50)s, step 0.1s.                                                                   
At motor's start, counting of tTr begins. If during tTr the motor current drops below ITr, 
switching-over is operated; if motor 
current stays over ITr longer than tTr, the Locked Rotor element is activated. 

Auto-setting 

The complexity of properly set a motor protection, frequently produces undesired 
tripping or non-operation of some of the data functions.                                                                                            
The relay MM30 automatically selects the best setting of the according to motor and 
system basic data. 
These parameters are: System frequency, Rated primary current of phase CTs, Rated 
primary current of earth fault CT, 
Motor rated current, Motor starting current, Starting time, Transition current level, 
Transition time. Once these settings have been programmed the AUTOSET function can 
be activated and all the variables are computed and automatically set at values suitable 
for a normal duty of the motor. Variables can be anyhow manually modified if different 
setting is needed. 

Features: 

 

Auto setting of parameters. 

 

Draw out enclosure. 

 

8 digit alpha numeric display. 

 

Real Time Measurements. 

 

Measurement and display of actual & trip data recordings. 

 

8 LED’s for fault indication. 

 

Control on number of starts of motor and Starting sequence control. 

During start-up of the motor, the unit can control an output contact to automatically manage the starting transition. 

 

RS485 port for communication with Modbus Protocol. 

Summary of Contents for MC 12A

Page 1: ...b stations The relay has a built in high set facility DIP switches are provided on the front panel for pick up and time delay settings User has a choice of 7 trip time characteristics FEEDER PROTECTIO...

Page 2: ...1987 a Normal Inverse 3s b Normal Inverse 1 3s c Very Inverse d Extremely Inverse Definite time Three curves as follows e Definite Time 1s f Definite time 10s g Definite time 100s Accuracy As per Erro...

Page 3: ...iliary Supply 24 240 V AC DC Wide TMS Range 0 01 1 60 Draw out execution With automatic CT shorting facility Instantaneous Over current and earth fault element Communication Through Modbus Protocol on...

Page 4: ...Stator Ground Fault protection MG30 incorporates 5 output relays expandable up to 16 with the additional module REX 8 Features Voltage controlled over current protection Thermal image element with pr...

Page 5: ...Instantaneous output 30ms 2 Harmonic restraint level 2H 0 1 1 0 Id step 0 01Id First percent bias 0 5 IR In P 1R 2 20 step 1 Second percent bias IR In P 2R 5 50 step 1 Point of slope variation P 1 3 s...

Page 6: ...0 to 40 of In in steps of 5 or 20 to 80 of In in steps of 10 CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel programmable using push buttons Pick up...

Page 7: ...se Cts 1 9999 A step 1A On Rated primary current of earth fault detection Cts 1 9999 A step 1A CT Burden Less than 1 0 VA at Is min Less than 6 VA at Is max Operating Characteristics Front panel progr...

Page 8: ...utomatically manage the starting transition Switch over transition current Itr 0 1 1 Ist step 0 1Ist Maximum switch over time delay tTr 0 5 50 s step 0 1s At motor s start counting of tTr begins If du...

Page 9: ...pick up level A DIP switch is provided for selection of thermal overload trip class and enable disable of Locked rotor protection and under current protection Other settings are prefixed in the relay...

Page 10: ...3 sec Both factory set Locked rotor protection Locked rotor current 3 Im Trip time delay 1 sec Both factory set Disable feature Available Under Current protection Under current threshold 50 of Im Tri...

Page 11: ...d applicable time delays are indicated on a label on right hand side of the unit The wiring diagram label is provided on the left hand side of the unit Display Current and Thermal Capacity Display Dur...

Page 12: ...l through various settings Function LED showing number or alphabet to indicate which setting is being view as shown in Figure 3 Table 1 gives description of each setting APPLICATIONS MPR 300 offers yo...

Page 13: ...dVB IdVC Maximum Demand and Inrush Recording IdA IdB IdC Ido I1A I1B I1C I2A I2B I2C IdIIA IdIIB IdIIC IdVA IdVB IdVC Programmable Input Quantities Fn System frequency 50 60 Hz 1In Rated primary curre...

Page 14: ...1In Detection time 6ms t 20ms Peak current detection with DC offset restraint Digital Inputs B1 Operation block input B2 Harmonic restraint s reduction B3 Oscillographic record external trigger Approv...

Page 15: ...00 ms can be set Current Input 1A 5A Application These relay can be used for differential protection of generators REF applications of generators and transformers in all low voltage medium voltage sub...

Page 16: ...nt Function enabling Enable Disable Setting range V 0 5 1 50 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV 0 05 60 s step 0 01s F59 V Second OverVoltage Element Function enabling Enable...

Page 17: ...alanced Overvoltage Element Function enabling Enable Disable Setting range V2 0 1 1 5 Vn step 0 01Vn Instantaneous output 0 03s Trip time delay tV2 0 05 60 s step 0 01s Characteristics Accuracy at ref...

Page 18: ...t Characteristics Normal Inverse 3 5 sec in O V mode Normal Inverse 5 7 sec in U V mode Definite Time 1 10 100 Sec Pick up Voltage Same as set Voltage Vs Reset Voltage 90 to 95 of Set Voltage Vs 105 t...

Reviews: