![AUMA TIGRON TR-M1000X Operation Instructions Manual Download Page 67](http://html1.mh-extra.com/html/auma/tigron-tr-m1000x/tigron-tr-m1000x_operation-instructions-manual_3016515067.webp)
Features and functions
AUMA Ex plug/socket connector (KT, KM), screw-type motor terminals, push-in type
control terminals
Standard:
Electrical connection
AUMA Ex plug/socket connector (KT, KM), with additional support terminals in
plug/socket connector
Option:
Metric threads
Standard:
Threads for cable entries
NPT threads, G threads
Options:
B1 according to EN ISO 5210
Standard:
Valve attachment
A, B2, B3, B4, C, D according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Options:
Special valve attachments: AF, AK, AG, B3D, ED, DD, IB1, IB3, A prepared for permanent lubrication
of stem
Absolute encoder, magnetic for position sensing (MWG)
Turns per stroke: 2 to 500 (standard) or 20 to 5,000 (option)
Position sensing
AUMA torque sensor; resolution
± 2 %
, referring to maximum adjustable torque.
Torque sensing
24 V DC: +20 %/–15 %
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
External supply of the electronics
(option)
The rated power is the nominal motor power, refer to Electrical data.
Rated power
Reversing contactors (mechanically and electrically interlocked) for AUMA power classes
A1 and A2
Standard:
Switchgear
Thyristor unit for mains voltage up to 500 V AC for AUMA power classes B1, B2 and B3
Options:
For the assignment of AUMA power classes, please refer to Electrical data.
4 digital inputs: OPEN, STOP, CLOSE, EMERGENCY (via opto-coupler with one common).
Standard:
Digital input
6 digital inputs, e.g. OPEN, STOP, CLOSE, EMERGENCY, MODE, Enable LOCAL
Option:
With positioner option: Input of actuator position setpoint as continuous value from 0/4 – 20 mA
Analogue input
24 V DC, current consumption: approx. 10 mA per input
Standard:
Control voltage/current consumption
for digital control inputs
All input signals must be supplied with the same potential.
●
6 programmable output contacts:
-
5 potential-free NO contacts with one common, max. 250 V AC, 1 A (resistive
load)
-
1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
●
Analogue output signal for position feedback
-
Galvanically isolated position feedback 0/4 – 20 mA (load max. 500 Ohm)
Standard:
Status signals
(output signals)
●
6 programmable output contacts:
-
5 change-over contacts with separate common, max. 250 V AC, 1 A (resistive
load), 1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load)
●
1 further analogue output, e.g. torque output as continuous value from 0/4 – 20 mA
Options:
Auxiliary voltage 24 V DC: max. 100 mA for supply of control inputs, galvanically isolated
from internal voltage supply.
Standard:
Voltage output
Auxiliary voltage 115 V AC: max. 30 mA for supply of control inputs, galvanically isolated
from internal voltage supply
Option:
●
Combi-Switch with the following functions:
- Selector switch: LOCAL-OFF-REMOTE, ESC, ENTER, (RESET)
- Shuttle dial: OPEN, CLOSE, (STOP)
●
Selector switch: lockable in all three positions
●
6 indication lights:
-
End position and running indication OPEN (green), torque fault OPEN (red), motor
protection tripped (red), torque fault CLOSE (red), end position and running indic-
ation CLOSE (yellow), Bluetooth communication (blue)
●
Graphic LC display: illuminated
For display of all essential actuator data like travel position, torque, type of seating,
etc.
Standard:
Local controls
●
Colours and functions of indication lights to be selected via the menu according to
operation instructions
Option:
67
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Technical data