End position setting via
stroke
Information: To allow the setting of an end position via stroke, the other end
position must be set via the position.
13. Calculate the setting value for stroke setting: For this, multiply the “value per
turn” by the stroke.
Table 15:
Value per turn
Actuator
118.108
TR-M30X/TR-M60X
120.461
TR-M120X
120.041
TR-M250X/TR-M500X
120.461
TR-M1000X
➥
Example: Stroke = 5 turns; value per turn = 120.461
➥
Setting value = 5 x 120.461 = 600
14. Set the value using
:
Figure 56:
15. Save new end position via (Enter).
➥
The signal
End pos. OPEN set!
or
End pos. CLOSED set!
is displayed and the
respective LED is illuminated. Thus, the end position is set via the stroke.
16. If the setting must be corrected: Reset settings with (Enter). The LED goes
out again.
→
Enter the value again using
and save via (Enter).
17. If the end position OPEN has been correctly set: Exit the menu with ESC (Es-
cape).
45
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Commissioning