8.2.3.
Limit switching setting via the device menu
Valve damage at valve/gearbox due to incorrect setting!
→
When setting with motor operation: Interrupt operation in time prior to reaching
the end stop (swing shuttle dial in the direction of operation).
→
For limit seating, provide for sufficient backlash between end position and
mechanical end stop due to potential overrun.
Information
Local actuator settings are made using the Combi-Switch.
●
Operate the yellow shuttle dial
of the Combi-Switch to scroll within the menu
.
●
Operate the black selector switch
(outer ring), either to confirm the selected
menu or to go one step back (ESC).
How to proceed
1.
Open device menu.
Information: If the ID of the indicated page starts with
M, PRM, ...
, you have
already entered the device menu. For further information, refer to:
➭
2.
Select menu
M0084
or
M0085
:
Customer settings M0041
Limit switches M0010
Set end pos.CLOSED? M0084
Set end pos. OPEN? M0085
Figure 52:
Information
If required, change user level. For performing settings, at least user level 4 is re-
quired. For further information, refer to:
➭
➥
The display now indicates the command prompt
CMD0009
or
CMD0010
.
Figure 53:
3.
If the valve is already in the end position:
→
For end position CLOSED, continue with step 7 (set end position
CLOSED).
→
For end position OPEN, continue with step 10 (set end position OPEN).
4.
If the valve is NOT already in the selected end position:
→
Continue with steps 5 + 6 (approach end position).
→
If the valve CANNOT be operated, continue with step 13 (set end pos-
ition via stroke).
Information: For all applications not allowing to operate the valve during
commissioning, the second end position can only be set via the stroke.
43
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Commissioning