8.2.2.
Torque seating setting via the device menu
If the set tripping torque is specified for the indicated operation direction, the actuator
switches off (overload protection of the valve).
Information
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Information
Local actuator settings are made using the Combi-Switch.
●
Operate the yellow shuttle dial
of the Combi-Switch to scroll within the menu
.
●
Operate the black selector switch
(outer ring), either to confirm the selected
menu or to go one step back (ESC).
How to proceed
1.
Open device menu.
Information: If the ID of the indicated page starts with
M, PRM, ...
, you have
already entered the device menu. For further information, refer to:
➭
2.
Select menu
M0088
or
M0089
:
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Information: If required, change user level. For performing settings, at least
user level 4 is required. For further information, refer to:
➭
➥
The display indicates the command prompt
CMD0018
or
CMD0019
.
Figure 51:
Change settings
3.
Enter the new value for the tripping torque in direction CLOSE or OPEN with
.
Information: The adjustable torque range is shown in round brackets.
4.
Save new value via (Enter).
➥
The display shortly indicates
Value saved!
. The tripping torque for the operation
direction is set.
5.
Press ESC (Escape) to return for further parameter setting.
Information
If the set torque is reached prior to reaching the end position, a fault signal is issued:
Torque fault OPEN
or
Torque fault CLOSE
The fault can be eliminated by an operation command in the opposite direction (for
Torque fault OPEN
: operation command in direction CLOSE; for
Torque fault CLOSE
:
operation command in direction OPEN) or via the selector switch in LOCAL with
ESC (Escape).
Further information to fault signals:
➭
42
TR-M30X – TR-M1000X
Commissioning
TR-MR30X – TR-MR1000X