11.
AUMA CDT software (accessories)
The AUMA CDT software (accessories) can be used to establish a connection to a
computer (PC, laptop or PDA).
It can be downloaded free of charge from our web site www.auma.com.
Figure 22: Connection with service cable
For connecting the computer to the integral actuator controls, a service cable (AUMA
article no.: Z100.999) is required.
Read/perform basic settings via AUMA CDT software
Basic settings at the device (in controls) made via switches are read only via AUMA
CDT on delivery and cannot be modified. To be able to change these parameters
via software, position switch [S5] in controls to "Software mode". Refer to <Settings
via hardware (switches) or via software> chapter.
Switches and software parameters are set to the same values upon delivery (factory
settings).
Further settings via AUMA CDT software
Apart from basic settings, the following functions may additionally be set via AUMA
CDT software:
●
Torque by-pass
Allows increasing the pre-set torque limitation to 130 % for actuator start to
unseat blocked valves. Duration for torque by-pass is adjustable.
●
Electronic positioner (option)
●
Failure behaviour (on loss of signal)
●
EMERGENCY behaviour (option)
●
Timer function (option)
●
Motion detector
●
Type of duty monitoring (motor starts and running time)
●
Operating time monitoring
●
Self-retaining local
For detailed information on these functions, refer to the online help of the AUMA
CDT software.
38
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
AUMA CDT software (accessories)
Modbus RTU