Table 14:
SVM/SVMR 07.5
SVM/SVMR 05.1/07.1
Switch [S8]
Step
Output drive speed [rpm]
0.6
1.6
1
0.8
2.2
2
1.1
3.2
3
1.6
4
4
2.2
5.6
5
3.2
8
6
4
11
7
5.6
16
8
8
22
9
impermissible switch position
0
Setting via software parameters (AUMA CDT)
The motor speed can be modified via the software parameters described hereafter:
Contrary to output speed setting using switch [S8], setting via software parameters
offers the following additional possibilities:
●
different motor speeds for operation modes Local and Remote
●
adjustable motor speed setting
●
motor speed setting (target speed) for operation mode Remote by an external
signal (fieldbus command)
Setting parameters
Condition: Switch [S5] is in position ON (software mode).
Device configuration
Motor speed
Speed LOCAL
Speed REMOTE
Speed fieldbus
Description of parameters:
Speed LOCAL
Output speed for operation via local controls (operation mode Local); Setting range:
linear between 0 – 100 % (0 % = min. motor speed, 100 % = max. motor speed);
Default value = 50.0 %
Speed REMOTE
Output speed in operation mode Remote for setting the
Speed fieldbus
=
Internal
parameter; Setting range: linear between 0 – 100 % (0 % = min. motor speed, 100
% = max. motor speed); Default value = 50.0 %
Speed fieldbus
=
External
In operation mode Remote, the output speed is defined via fieldbus.
=
Internal
In operation mode Remote, the output speed is not defined via fieldbus but by means
of the
Speed REMOTE
software parameter.
31
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Modbus RTU
Commissioning (basic settings of controls)